This list of specific instructions will help you make certain 
that every installation operation is done correctly. Complete 
the installation steps in the sequence shown. 
Local building codes should be consulted in all cases as to 
the particular requirements concerning the installation of 
factory built fireplaces. Select the location for the fireplace 
by taking into consideration the factors previously outlined 
in the 

Planning Ahead

 section of the manual. 

TLC36-3MB, TFC36-3M and TLC42-4MB fireplaces are 
Underwriters Laboratories listed for installation in a 
manufactured (mobile) home  with TEMCO double-wall 8” 
air-cooled chimney and components. 
TEMCO glass doors, firestop thimble, and Model AK-18 
combustion air kit must be installed for manufactured 
(mobile) home use.  The duct for the combustion air kit may 
go through the floor or the side wall of the home.  A BL-1 
Blower Accessory is factory installed on louvered circulator 
models only. 
See Figure 10 for minimum system height.  The height of 
the system is measured from the base of the fireplace and 
includes 6” of the chimney cap. 

INSTALLING THE FIREBOX

 

STEP 1.  FRAMING THE FIREBOX

 

When framing the opening for the fireplace, make certain 
that the header is the correct height above the surface upon 
which the fireplace will sit. The header must be level. The 
header and framing may be installed as shown in figure 5 or 
figure 7 according to the installer's preference. 
The entire fireplace can be elevated above  the floor to 
achieve a raised hearth effect. This can be done by adding 
a small platform to achieve the desired height. 
The nailing flanges on the side of the firebox were designed 
to allow the installation of ½" wallboard or plywood flush 
with the face of the firebox.  Metal floor tabs are provided to 
secure the fireplace to the floor of the home.

 

STEP 2.  HEARTH SAFETY STRIP 

If used, a Hearth Safety Strip should be installed under the 
fireplace when the fireplace is installed on a combus tible 
floor. This strip should be positioned on the floor to extend 
2" under the fireplace, 2" under hearth extension and 6" on 
either side of the firebox opening at the point where the 
hearth extension meets the fireplace.   If a hearth safety 
strip is not used, the g ap between the hearth extension and 
the fireplace face must be sealed or grouted (400

F min.).  

See Figures 4 and 6. 

 

 

 

 

 

STEP 3.  INSTALL THE FIREBOX 

Install fireplace into the framed opening by setting the unit 
directly in front of the opening and then sliding it into the 
proper position. 

STEP 4.  LEVEL THE FIREBOX 

Check the level of the fireplace by placing a level on the top 
edge of the fireplace face. Shim with sheet metal if 
necessary. 

STEP 5. SECURE THE FIREBOX

 

Secure the fireplace to the framing. The nailing flanges on 
the firebox will make securing the firebox to the frame quick 
and easy. Secure the unit to the floor of the home using 
tabs at the bottom of each side.  Use the appropriate size 
nails or 

screws to  

secure 

the firebox. 

FIREPLACE INSTALLATION 

Figure 5  

Framing Dimensions  

 

36" models 

38 3/4  21  8 7/8  22 

38 

65 

32 1/2  46  14 3/8 

42" models 

44 13/16  22  8 1/2  32  41 3/4  76 1/4  38 1/8  54  17 5/8 

Figure 7  

Figure 6  

fireplace 
face 

hearth safety strip 
(grouting of joint optional when safety strip is used) 

seal crack with noncombustible 
material (manditory if a safety strip 
is not used) 

hearth 

Содержание TLC36-3M

Страница 1: ...ormed by a qualified installer Do not attempt to install this fireplace yourself If the information in this manual is not followed exactly a fire or explosion may result causing WARNING THIS FIREPLACE HAS NOT BEEN TESTED WITH AN UNVENTED GAS LOG SET TO REDUCE RISK OF FIRE OR INJURY DO NOT INSTALL AN UNVENTED GAS LOG SET INTO FIREPLACE WARNING P O Box 1349 Manchester TN 37349 P O Box 1148 Perris CA...

Страница 2: ...low all of the instructions contained in this book regarding installation and operation of the fireplace These instructions should be read carefully in their entirety before beginning installation of the fireplace ONCE THE FIREPLACE HAS BEEN INSTALLED THE SECTION USING YOUR FIREPLACE FOUND ON PAGE 14 OF THIS MANUAL SHOULD BE REVIEWED IN ITS ENTIRETY PRIOR TO OPERATING THE FIREPLACE It is suggested...

Страница 3: ...x 52 42 models 20 x 66 Since many hearth extension materials are not insulating materials a layer of noncombustible inorganic insulating material must be used also See pages 6 and 7 for R factor requirements 8 Adhere to the 10 Rule of Thumb for chimney height see page 9 9 Chimney supports a Flue support is required for every 35 of vertical system height b Flue support is required for every 6 of of...

Страница 4: ...MAY REQUIRE ADDITIONAL FOUNDATION SUPPORT ALTHOUGH THIS UNIT MAY BE INSTALLED ON COMBUSTIBLE SURFACES IT MUST NOT BE Figure 1 Figure 2 Fireplace and Framing Dimensions inches A B C D E F G H I J K L M N O P Q R S T TLC36 3MB 36 38 1 2 35 37 3 4 7 31 1 4 2 12 1 8 8 5 8 15 1 2 9 21 38 3 4 38 1 4 22 8 7 8 46 65 32 1 2 14 3 8 TLC36 3MBE 36 38 1 2 35 37 3 4 7 31 1 4 2 12 1 8 8 5 8 15 1 2 9 21 38 3 4 38...

Страница 5: ...e structural integrity of a home s floor walls ceiling and roof must be maintained It is not recommended to cut roof trusses CHIMNEY OUTLET Thought should be given to the proposed location of the chimney outlet on the roof Objects such as trees adjacent buildings or embankments that are too close to the chimney can create air circulation problems during windy weather that could affect the way the ...

Страница 6: ...ed on the wall The wall shield must be 40 x 40 and be constructed of a noncombustible inorganic material having a thermal resistance of R 1 49 Determining the R Values The hearth extension must be constructed of non combustible materials which have a total thermal resistance R factor equal to or greater than 80 for floor level hearth extensions or 1 20 for raised hearth extensions and be a minimum...

Страница 7: ...eve the desired height The nailing flanges on the side of the firebox were designed to allow the installation of wallboard or plywood flush with the face of the firebox Metal floor tabs are provided to secure the fireplace to the floor of the home STEP 2 HEARTH SAFETY STRIP If used a Hearth Safety Strip should be installed under the fireplace when the fireplace is installed on a combustible floor ...

Страница 8: ...top thimble and is fastened to the thimble with sheet metal screws A model 8206F roof flashing storm collar and the TEMCO 8203D termination cap are required to complete the installation NOTE When clearances are a concern for home transportation to site the last piece of vent pipe and termination cap may be installed at destination INSTALLING THE CHIMNEY Double Wall Chimney pipe has two sections th...

Страница 9: ...ill be the amount of the offset dimension away from the ceiling nail See figure 15 The X dimen sion in the drawing is the amount of the offset Be sure to consider the direction that your offset will incline To achieve the minimum offset see table attach the return elbow to the first elbow To achieve further offset you may install various lengths of pipe between the elbows to a maximum length of 72...

Страница 10: ... 0 0 1 0 46 3 10 0 0 0 1 50 4 2 0 1 1 0 56 4 8 1 0 0 1 62 5 2 0 1 0 1 66 5 6 2 0 0 1 72 6 0 1 1 0 1 80 6 8 0 0 1 1 92 7 8 0 0 0 2 96 8 0 0 1 1 1 102 8 6 1 0 0 2 108 9 0 0 1 0 2 112 9 4 2 0 0 2 118 9 10 1 1 0 2 126 10 6 0 0 1 2 136 11 4 1 0 1 2 138 11 6 0 0 0 3 142 11 10 0 1 1 2 148 12 4 1 0 0 3 154 12 10 0 1 0 3 158 13 2 2 0 0 3 164 13 8 1 1 0 3 172 14 4 0 0 1 3 182 15 2 1 0 1 3 184 15 4 0 0 0 4 1...

Страница 11: ... 1 2 1 77 7 8 149 3 8 1 1 0 0 3 2 80 7 8 154 5 8 1 0 1 0 3 2 82 7 8 158 1 2 0 0 3 2 85 7 8 163 1 4 1 1 1 0 3 2 89 7 8 170 1 8 1 0 0 1 3 2 94 7 8 178 3 4 1 1 0 1 3 2 95 7 8 180 5 8 1 0 0 0 4 2 97 7 8 184 1 0 1 1 3 2 100 7 8 189 1 4 1 1 0 0 4 2 103 7 8 194 1 2 1 0 1 0 4 2 105 7 8 197 7 8 1 2 0 0 4 2 108 7 8 203 1 8 1 1 1 0 4 2 112 7 8 213 1 4 1 0 0 1 4 3 117 7 8 221 7 8 1 1 0 1 4 3 118 7 8 223 3 4 1...

Страница 12: ... inlet hole of the fireplace Slide a 1 2 gas line nipple through the tube and attach to the line Finish installation by either capping gas line inside fireplace or by attaching an approved gas appliance in accordance with its installation instructions Re install insulation around the gas line to seal between the gas line and gas conduit Seal around the gas line and the refractory with refractory c...

Страница 13: ...the face of the fireplace Some of these products contain combustible materials Combustible wall coverings such as paneling or wallboard may not overlap the black face of the fireplace The space between the wall covering and the fireplace should be sealed with a heat resistant material such as rock wool insulation or mortar 4000 F Min NOTE An L shaped steel lintel must be installed across the top o...

Страница 14: ... to the floor of the home to prevent shifting Various methods of attachment may be used including screws nails or common construction adhesives 2 After the fireplace and hearth extension have been secured the gap between the fireplace and hearth extension must be filled or sealed with a non combustible grout caulk or sealant OR If a protective metal strip is used under the space between the firepl...

Страница 15: ...THE GLASS AND IS NOT RESPONSIBLE FOR CONSEQUENTIAL PROPERTY DAMAGE AS STATED IN THE SEPARATE GLASS DOOR WARRANTY 13 Creosote Formation and Need for Removal When wood is burned slowly it produces tar and other organic vapors which combine with expelled moisture to form creosote The creosote vapors condense in the relatively cool chimney flue of a slow burning fire As a result creosote residue accum...

Страница 16: ...ight side refractory 1 70355 68337 10 Left side refractory 1 70355 68338 11 Back refractory 1 70357 66993 12 Bottom refractory 1 70354 68336 13 Integral grate 1 70361 68373 14 Grate retaining bracket 2 66130 66130 REPLACEMENT PARTS The following replacement parts are available from your TEMCO dealer 16 Description Quantity Part 1 Handles 2 67987 2 Door Guide 1 68344 3 Spring Push 1 69891 4 Spring ...

Страница 17: ...nyone other than the original owner Shipping costs after the first year of coverage Labor after the first year of coverage Damage caused by improper installation misuse abuse or alteration of the fireplace or chimney system Cracks in refractories that do not affect safe operation Any work done or cost incurred without written consent from TEMCO Fireplace Products Installation performed by unlicens...

Страница 18: ...k in Order of Importance 1 6 ___Appearance ___Location Flexibility ___Builder Decided Purchaser Address Phone Retailer Address Phone Date of Purchase CUT ALONG LINE To register your warranty please provide the information indicated on this form and mail it to TEMCO Fireplace Products 301 Perimeter Park Dr Suite 227 Nashville TN 37211 WARRANTY REGISTRATION Please Answer the Following Questions Chec...

Страница 19: ...glass door kits be effective after the expiration date of the above limited warranty A Glass Breakage Temco Fireplace Products does not warrant against breakage of glass Breakage is normally due to handling and shipping which is covered by the freight handler Breakage during use can be attributed to over firing the fireplace which means flames are going up the chimney or licking against glass when...

Страница 20: ...at its option either repair or replace the part at no cost to purchaser however any labor or other charges incurred in the removal or replacement of the part as well as any delivery or shipping charge will be the sole responsibility of purchaser This warranty is not transferable in any manner by the original purchaser and is effective only if the part of TEMCO s blower is accompanied by proof of p...

Отзывы: