10
Temco DV5200, DV6400 Series
77531
NOTE: Use only venting systems and components as
certified with the appliance. Use of uncertified vent
systems or components will void the warranty and may
compromise the operation of the fireplace, its systems,
and components as certified with the appliance.
2" (51mm)
1" (25mm)
1"
(25mm)
Top of Vent
Combustibles
NOT Allowed in
Shaded Area
4” Dia. Flue
7” Dia.
Intake
Vent
T181
Fig. 12 Vent clearances.
MILL-P
AC
MILL-P
AC
T182
NOTE:
Apply sealant “Mill-Pac” to innerpipe and “Mill-Pac” or high
temp silicone sealant to outer pipe. Sealant should be
applied at every joint in the vent system including at the
fireplace and at the vent terminal.
Fig. 13 Apply sealant at every joint in vent system.
Roof Pitch
H (Min.)
Flat to 6/12
12” (305mm)
6/12 to 7/12
15” (381mm)
Over 7/12 to 8/12
18” (457mm)
Over 8/12 to 16/12
24” (610mm)
Over 16/12 to 21/12
36” (914mm)
H
12
x
Vent Cap
Lowest Dis-
charge Opening
Gas Vent
Roof Pitch
is X/12
H (Min.) - Minimum height
from roof to lowest
discharge opening
T183
Fig. 14 Vertical termination location.
0
5’
46"
(1168mm)
33
¹⁄₂
"
(851mm)
10’
15’
25’
30’
32’
0
3’
5’
10’
15’
A vent guard should be used
whenever the termination is
lower than the specified
minimum or as per local
codes
*
Min. Refer to Chart on Page 5.
*
T180
Fig. 11 Venting graph.