Temco ADF3310N-4 Скачать руководство пользователя страница 8

8

Temco ADF3310 Series

78623

When the fireplace is installed over carpeting, vinyl tile
or any combustible material other than wood flooring, it
must be installed on a metal or wood panel extending
its full width and depth.  Alternatively - the carpeting,
vinyl tile, etc., may be removed from beneath the
fireplace before installing.

Combustible materials must not be installed over or
touch the black front surface of the fireplace.

Clearances

To ensure a safe installation, the following instructions
must be carefully observed.
1. Sidewall Clearances:  Clearances from the side of

the fireplace opening to any combustible wall should
not be less than 2”.

2. Ceiling Clearances:  The ceiling height should not

be less than 36” from the top of the fireplace. (Fig.
6a)

3. Mantel and Wall Clearances:

a. Noncombustible materials must be used for all

wall coverings below the top standoffs of the
fireplace. (Fig. 6b)

b. A combustible mantel may project 1" from the

wall 9" above the fireplace opening.  The mantel
may project 7" from the wall at 19" above the top
of the fireplace opening.

c. The mantel that is being used must fall within the

profile that is shown in Figure 6b.

4. Floor Clearances:  No clearance is required if the

appliance is installed per these instructions.

36"

2"

2"

T105

Fig. 6a  Minimum sidewall and ceiling clearances.

1"

9"

Min.

4"

7"

15"

Min.

19"

Min.

Wall Covering

Wall Stud

Header

Top Standoffs

Noncombustible
Sealer, Insulation
or Trim

Fireplace Opening

T162

Fig. 6b  Minimum mantel clearances.

Installation

This list of specific instructions will help you make
certain that every installation operation is done
correctly.  Complete the installation steps in the
sequence shown.

LOCAL BUILDING CODES SHOULD BE CONSULTED
IN ALL CASES AS TO THE PARTICULAR REQUIRE-
MENTS CONCERNING THE INSTALLATION OF
FACTORY BUILT VENT FREE FIREPLACES.

Select the location for the fireplace by taking into
consideration the factors previously outlined in the
Planning Ahead section of this manual.

Step 1:  Framing the Firebox

The entire fireplace can be elevated above the floor to
achieve a raised hearth effect.  This can be done by
adding a small platform to achieve the desired height.

STOP!  THE OPTIONAL CANOPY MAY BE IN-
STALLED AT THIS TIME.  LOOSEN THE SCREWS
LOCATED AT THE TOP FRONT OF THE FIRE-
PLACE.  NEXT, SLIDE THE SLOTTED FLANGE OF
THE CANOPY UNDER THE LOOSENED SCREWS,
THEN RETIGHTEN THE SCREWS TO SECURE THE
CANOPY.  (REFER TO PAGE 12, FIG. 9 FOR AT-
TACHMENT LOCATION)

A CANOPY IS NOT REQUIRED IF COMBUSTIBLE
MANTLES AND PROJECTIONS ABOVE THE FIRE-
PLACE OPENING MEET THE MINIMUM CLEAR-
ANCE REQUIREMENTS ILLUSTRATED IN FIGURE
6B.

Step 2:  Install the Firebox

Install the firebox into the framed opening by setting it
directly in front of the opening and sliding it into the
proper position.

Step 3:  Level the Firebox

Check the level of the firebox on the top edge of the
fireplace face.  Shim if necessary.

Step 4:  Secure the Firebox

Secure the fireplace to the framing.  The nailing flanges
on the firebox will make securing the firebox to the
frame quick and easy.  Use appropriate size nails or
screws to secure the firebox.

Step 5:  Remove Front Screen Panel

To remove the screen panel, first open the control panel
door.  Using a 1/4" nut driver, remove the two screws
that secure the screen panel to the front of the fire-
place, (Refer to Figure 7 for location).  Carefully pull the
bottom of the screen panel out toward you, then pull the
panel down until the two pins at the top of the screen
panel clear the holes in the top of the fireplace.  Re-
move the screen panel to a safe location.

Reverse the above operation to re-install the screen
panel.

Содержание ADF3310N-4

Страница 1: ...Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire depart ment Installation and service must be performed by a qualified in staller service agency or the gas supplier This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combus tion and ventilation air must be provided Refer to Page 4 Vent Free...

Страница 2: ...s your operating and installation instructions and should be kept in a safe place For you to realize all the advantages and use of the reliable service that has been engineered into your TEMCO fireplace you must carefully follow all of the instructions contained in this book regarding installation and operation of the fireplace These instructions should be read carefully in their entirety before b...

Страница 3: ...OT place clothing or other flammable material on or near the appliance This appliance must only be used with pressures at the inlet as shown in Table 1 Page 11 in installation instructions The installation must conform with local codes or in the absence of local codes with the NATIONAL FUEL GAS CODE ANSI Z223 latest edition Any safety screen or guard removed for servicing an appli ance must be rep...

Страница 4: ...0 000 BTU Hr Vent free logs 29 000 BTU Hr Total 89 000 BTU Hr Do not include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum BTU Hr the space can support with the actual amount of BTU Hr used _______ BTU Hr maximum the space can support _______ BTU Hr actual amount of BTU Hr used Example 100 000 BTU Hr maximum the space ...

Страница 5: ...ent openings one within 12 of the ceiling and one within 12 of the floor Con nect these items directly to the outdoors or spaces open to the outdoors These spaces include attics and crawl spaces Follow the National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet a...

Страница 6: ...5 0 Rough Opening Width 36 Rough Opening Height 14 Rough Opening Depth 35 33 14 6 3 1 2 Gas Connection Left Side Only 1 2 2 5 1 2 Clearance to Combustibles not Required at This Point Fireplace Dimensions 78623 Fig 2 ADF3310 specifications and framing ...

Страница 7: ...dered when choos ing the location for the fireplace Partial Room Projection Corner Full Room Projection Room Divider Flush LU584 1 Fig 3 Locating the fireplace Gas Line The gas line must be installed by a licensed gas line installer before framing in the fireplace Drafts Do not locate the fireplace in high traffic areas or areas exposed to high drafts and winds Locate the fireplace away from furni...

Страница 8: ...IN ALL CASES AS TO THE PARTICULAR REQUIRE MENTS CONCERNING THE INSTALLATION OF FACTORY BUILT VENT FREE FIREPLACES Select the location for the fireplace by taking into consideration the factors previously outlined in the Planning Ahead section of this manual Step 1 Framing the Firebox The entire fireplace can be elevated above the floor to achieve a raised hearth effect This can be done by adding a...

Страница 9: ...n Page 10 The normal gas connection is 1 2 NPT made at the center of the unit WARNING DANGER OF PROPERTY DAMAGE BODILY INJURY OR DEATH Never use a match or open flame to test for leaks Never exceed specified pressures for testing High pressures may damage the appli ance regulator which would require replacement Liquified petroleum LP is heavier than air and it will settle in any low area including...

Страница 10: ...r and if pressures are not 10 w c for LP or 3 5 for natural gas then the inlet pressure must be adjusted or increased until the proper pressures are attained If these pressures are greater than 10 w c for LP or 3 5 w c for natural gas contact your gas supplier before operating the appliance Table 1 Gas Inlet Pressure Natural Propane Max 10 5 w c 13 0 w c Normal 7 0 w c 11 0 w c Min 5 5 w c 11 0 w ...

Страница 11: ...0 50 79 105 163 196 304 400 622 610 949 70 46 71 96 151 180 280 370 576 560 872 90 40 61 84 130 160 250 320 497 490 763 100 38 59 79 122 150 235 305 474 460 717 Outside Diameter Copper Tubing Type L 1 000s BTU hr Tubing Length 1 2 5 8 3 4 7 8 Feet 0 43 0 545 0 666 0 785 10 110 206 348 536 20 76 141 239 368 30 61 114 192 296 40 52 97 164 256 50 46 86 146 224 60 42 78 132 203 80 36 67 113 174 100 32...

Страница 12: ... Combustible wall coverings such a paneling or wallboard may not overlap the black face of the fireplace The space between the wall covering and the fireplace should be sealed with a heat resistant material such as rock wool insulation or mortar NOTE An L shaped steel lintel must be installed across the top of the firebox opening where facing materials such as brick or stone are used on the face o...

Страница 13: ...s STOP Follow B in the safety information above If you don t smell gas go to the next step 4 Refer to Figure 11 Locate the pilot 5 Refer to Figure 10 Push in the control knob and turn counter clockwise to the 1 IGN position Hold the control knob in for a few seconds 6 While still holding in the control knob press the ignitor push button several times This will cause a spark at the pilot which will...

Страница 14: ...following flame appearance should be observed Rear Burner Flames The flames at the rear and on either side of the top log should be very similar yellow in color and should extend about 3 4 inches above the large front log Fig 15 NOTE For your safety the appliance is equipped with an oxygen depletion system The system senses the oxygen in the atmosphere and switches off the gas supply before the le...

Страница 15: ...urner area use the brush attachment from your vacuum cleaner to carefully remove dust and loose particles from the base logs and from around the burner Gloves are recommended when handling the logs Use extreme caution when cleaning around the pilot ODS The pilot should not be moved or altered from the original factory setting Pilot to burner preset location To clean the pilot take an Air Duster ca...

Страница 16: ... L5T 2N6 Repair and replacement work should only be done by a qualified service technician Always shut off the gas supply and make sure the appliance is cool before beginning any service operation Always check for gas leaks after servicing Servicing Description ADF3310N 4 ADF3310P 4 Valve 1 Position 70684 70684 Injector 53 74658 Injector 62 78557 Regulator Maxitrol 73332 73333 Pilot Assembly OP 20...

Страница 17: ... TEMCO installation instructions and in compliance with local codes and ordinances The logs must be placed strictly in accor dance with the arrangement described in the installation instructions The Product must be operated and maintained according to the instructions furnished Alteration of the Product in any way is prohibited and voids any and all war ranties Removal of the data plate alters the...

Страница 18: ...s as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer NOTE LP models must not be operated if fuel tank is less than 1 4 full Observe the consumer operating the product pro...

Страница 19: ...rs as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer NOTE LP models must not be operated if fuel tank is less than 1 4 full Observe the consumer operating the product pr...

Страница 20: ...our warranty please provide the information indicated on this form and mail it to TEMCO Fireplace Products Attn Warranty Registration 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 Model ______________________________________ I certify that I have followed all codes and regulations and adhered to the TEMCO installation instructions I have completed the proper installation and startup checklis...

Отзывы: