background image

OUTSIDE AIR KIT AND GLASS DOOR
ACCESSORIES

A fireplace needs a steady supply of air in order to draw
properly. Many houses and apartments which are well
sealed lack sufficient air for normal operation. IN SUCH
HOUSES, IT IS RECOMMENDED THAT A COMBUSTION
AIR KIT BE INSTALLED. A combustion air kit will improve
the efficiency of any fireplace, especially if used in conjunc-
tion with glass doors, because it allows you to use outside
air for combustion instead of heated room air.
Installing the fireplace on an outside wall will simplify the
installation of the combustion air kit and reduce the amount
of necessary duct work. Install the air kit according to the
separate installation instructions packed with it. If an air kit
is to be installed, IT MUST BE INSTALLED AT THE TIME
THE FIREPLACE IS INSTALLED, before its enclosure is
finished.
The fireplace includes an integral barometric damper. The
control lever is located on the left side behind the mesh
screen.

GAS LOG

If you plan to install a gas log, the gas line must be installed
before framing in the fireplace. The gas line must be in-
stalled by a licensed gas line installer. See p.12 for installa-
tion instructions.

DRAFTS

The location for the fireplace should be away from objects
such as frequently opened doors and central heat air outlets
and inlets that will create drafts and possibly hamper the
normal flow of air into the fire.

LOCATING THE AREA WHERE THE FLUE
PIPE WILL PASS THROUGH THE CEILING
AND THE ROOF

It is very important that you determine where the flue
(chimney) will go through the ceiling and roof. Check the
structure of your home to see that the location you have
chosen will make installation as easy as possible. Using a
plumb bob, hold the string from the ceiling and drop it,
moving the string until the plumb bob is in the center of the
flue collar opening, (see figure 3). Mark the spot on the
ceiling. You may wish to drive a nail through the ceiling at
this spot. Then go into the attic and find the nail. Using the
plumb bob with the ceiling nail as the center point of the
flue, mark the center of the area on the roof through which
the flue will pass. This is to see if it is possible to cut your
opening for the flue in both the ceiling and roof without cut-
ting either roof rafters or ceiling joists. A location that
requires cutting the least number of joists and rafters will
simplify the installation and reduce the cost. The structural
integrity of a home's floor, walls, ceiling and roof must be
maintained. It is not recommended to cut roof trusses.

CHIMNEY OUTLET

Thought should be given to the proposed location of the
chimney outlet on the roof. Objects such as trees, adjacent
buildings or embankments that are too close to the chimney
can create air circulation problems during windy weather
that could affect the way the fireplace draws air.
After careful consideration, choose the location for your fire-
place to achieve the simplest installation for maximum effi-
ciency.

FIREBOX AND CHIMNEY SYSTEM CLEAR-
ANCES

The fireplace may be placed directly on a combustible floor,
against a combustible wall at marked clearances or on a
raised wooden platform.

If the fireplace is to be installed on a raised platform, the
platform must be a continuous level surface.

The fireplace must be secured in place so it cannot shift
positions. The nailing flanges on the sides of the firebox
make securing the firebox to the frame quick and easy. The
nailing flanges were designed to allow the installation of
1/2" wallboard or plywood flush with the face of the fire-
place.

Only the header (see figure 4) may rest on the standoffs on
top of the firebox.

Combustible materials may not cover any part of the black
metal surrounding the firebox opening. See figure 4.

Do not install the firebox over vinyl floors or carpet.

Combustible floors in front and to the sides of the firebox
opening must be protected by a noncombustible hearth ex-
tension as shown in figure 4.

THE CAUTIONS BELOW RELATE TO LOCATIONS ON
FIGURE 4, (letters on pictures correspond with items be-
low).

A. The hearth safety strip must be used under the crack be-

tween the fireplace and the hearth extension when the
fireplace is installed on a combustible floor. Seal the
crack with a noncombustible material such as mortar,
grout, etc.

B. COMBUSTIBLE MATERIALS MUST NOT BE IN-

STALLED OVER OR TOUCH ANY BLACK PAINTED
SURFACE.

  

DO NOT BLOCK HEAT CIRCULATING AIR INLETS
OR OUTLETS. DOING SO MAY RESULT IN A POTEN-
TIAL FIRE HAZARD.

C. If the floor in front of the fireplace is combustible, either

a raised or floor-level protective hearth extension must

be constructed. For flush-face models only, a raised
hearth extension may be flush with the fireplace hearth.
To construct a raised hearth extension with louvered
models, the fireplace must rest on a raised platform. A

Figure 3

Use of the Plumb Bob

X

Y

36" models

16"

52"

39" models

16"

55"

42" models

20"

66"

Содержание A36F-3

Страница 1: ...irculating Fireplace FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Installation and service must be performed by a qualified installer Do not attempt to install this fireplace yourself If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or...

Страница 2: ... suggested that you wear work gloves and safety glasses to protect your hands and eyes when installing your fireplace NOTE Authorities having jurisdiction i e building inspec tors fire marshals etc should be consulted before instal lation to determine the need to obtain a permit All models are listed for use in residential construction in the United States with a TEMCO double wall 8 diameter air c...

Страница 3: ...e fireplaces 11 The barometric damper on the Combustion Air Kit al lows air to be drawn from above below or behind the fireplace but air must never be drawn from the attic or garage spaces Refer to the air kit installation manual for complete installation and use information 12 Check your local building code to determine if grounding is required and what procedure should be fol lowed Grounding is ...

Страница 4: ...E INSTALLED ON CARPET OR VINYL Figure 1 Figure 2 Fireplace and Framing Dimensions A B C D E F G H I J K L M N O P Q R S T TFC36 A36F 36 38 1 2 35 37 3 4 7 31 1 4 2 12 1 8 8 5 8 15 1 2 9 21 38 3 4 38 22 8 7 8 46 65 32 1 2 14 3 8 TLC36 A36L 36 38 1 2 35 37 3 4 7 31 1 4 2 12 1 8 8 5 8 15 1 2 9 21 38 3 4 38 22 8 7 8 46 65 32 1 2 14 3 8 TFC39 A39L 39 41 9 16 39 41 1 2 8 33 3 17 9 3 4 18 10 1 2 22 41 13...

Страница 5: ...f joists and rafters will simplify the installation and reduce the cost The structural integrity of a home s floor walls ceiling and roof must be maintained It is not recommended to cut roof trusses CHIMNEY OUTLET Thought should be given to the proposed location of the chimney outlet on the roof Objects such as trees adjacent buildings or embankments that are too close to the chimney can create ai...

Страница 6: ... have a total thermal resis tance R factor equal to or greater than 80 for floor level hearth extensions or 1 20 for raised hearth extensions and be a minimum size as shown in the table on page 5 Choose the desired materials and obtain the K value at 75 mean temperature The C value and the R value may be calculated with the following formulas K Thermal conductivity K BTUs ins hrs ft 2 0 F T thickn...

Страница 7: ...ight The nailing flanges on the side of the firebox were designed to allow the installation of wallboard or plywood flush with the face of the firebox STEP 2 HEARTH SAFETY STRIP A Hearth Safety Strip must be installed under the fireplace when the fireplace is installed on a combustible floor This strip must be positioned on the floor to extend 2 under the fireplace 2 under hearth extension and 6 o...

Страница 8: ...h length of chimney used in the system STEP 8 Insert the inner 8 pipe with the male end pointing DOWN into the inner collar The inner flue section fits inside the inner collar Push the pipe until it bottoms and the snap locks engage Check each joint to ensure that the sections are securely locked together STEP 9 Slip the outer 12 pipe with the male end UP over the other pipe and over the outer col...

Страница 9: ...he chimney sections Minimum system height without elbows 12 6 with two elbows 13 6 with four elbows 21 Maximum height 60 Four 30 elbows maximum per system Lineal Gain Chart Model Lineal Gain 36 fireplaces 37 3 4 39 42 fireplaces 41 1 2 8212D Chimney 10 3 4 8218D Chimney 16 3 4 8224D Chimney 22 3 4 8236D Chimney 34 3 4 3248D Chimney 46 3 4 8232E Elbow set 14 5 8 8204S Flue Support 3 8203D Round ter...

Страница 10: ...2 section 9 1 4 58 7 8 One 18 section 12 1 4 64 Two 12 sections 14 5 8 68 1 4 One 12 and one 18 section 17 5 8 73 1 4 Add to Add to Two 18 sections 20 5 8 78 5 8 Components Dimension X Dimension R One 36 section 21 1 4 79 5 8 12 section 55 93 One 12 and one 36 section 26 5 8 88 7 8 18 section 83 14 1 2 One 48 section 27 1 4 90 36 section 17 3 8 30 One 18 and one 36 section 29 5 8 94 48 section 23 ...

Страница 11: ...A metal cover made by a local sheet metal shop is re quired to complete a chase installation This cover be comes a flashing that prevents water from entering the chase The chase cover should be sealed at the corners A minimum 1 high collar is required at the point where the chimney pipe or slip section will penetrate the chase cover It requires 12 5 8 diameter collar for 36 models 13 5 8 for 39 an...

Страница 12: ...n avoid future cold air problems The time taken to install the firebox correctly is well worthwhile The following steps are recommended to stop potential cold air problems INSULATION OF THE FIREPLACE ENCLOSURE When in a chase or on an outside wall the fireplace enclo sure should be insulated like any other outside wall Insula tion should be installed on the outside walls and the wall above the fir...

Страница 13: ...me ceilings 0 to 30 The firestop thimble is designed to eliminate the need to cut trusses when installing the 8 chimney between stan dard mobile home roof trusses fabricated on 16 centers Locate and mark the center of the chimney on the mobile home ceiling Cut a 14 1 2 square in the ceiling Position the firestop thimble with the flanges up and with the cylin drical portion extending up into the ho...

Страница 14: ...rature adhesive or mortar when anchoring brick stone or tile to the face of the fireplace Check to see whether man made brick and stone are made of non combustible materials before using them on the face of the fireplace Some of these prod ucts contain combustible materials Combustible wall cov erings such as paneling or wallboard may not overlap the black face of the fireplace The space between t...

Страница 15: ...MANTEL PROJECTION Mantel legs may project along the radiation line as illustrated A B 6 min 2 5 8 7 min 3 8 min 3 1 2 10 min 4 3 8 12 min 5 1 4 Figure 26 Figure 27 Hearth Installa ...

Страница 16: ...AT TER RESULTING IN PROPERTY DAMAGE AND OR PER SONAL INJURY TEMCO DOES NOT WARRANT THE GLASS AND IS NOT RESPONSIBLE FOR CONSEQUEN TIAL PROPERTY DAMAGE AS STATED IN THE SEPA RATE GLASS DOOR WARRANTY 13 Creosote Formation and Need for Removal When wood is burned slowly it produces tar and other organic vapors which combine with expelled moisture to form creosote The creosote vapors condense in the r...

Страница 17: ... 1A62222 5 Refractory retainer right side 1 2B70358 2B70358 2B68316 6 Refractory retainer left side 1 2B70358 2B70358 2B68339 7 Refractory retainer front 1 2C68372 8 Screws for refractory retainers 2 1A68188 1A68188 1A68188 9 Right side refractory 1 2D70355 2D70355 2D68337 10 Left side refractory 1 2D70355 2D70355 2D68338 11 Back refractory 1 2D70357 2D70425 2D66993 12 Bottom refractory 1 2D70354 ...

Отзывы: