Telefire LI-3000 Скачать руководство пользователя страница 4

 

 

LI-3000 / LI-3000E 

© 1999

 

 

2015 Telefire Fire & Gas Detectors Ltd 

 

Revision 1.14   May 2015 

 

– Page 2 of 6 – 

Class A configuration in an ADR-3000 requires a minimum of 3 line isolators per loop.  
The first two line isolators shall be connected to the control panel and adjacent to it.  
Connect the line card to the two as per  Figure 1.  Configure the line card as a Class A 
loop. 

   Note    

For each Class A loop one of the line isolators that is connected to the line 
card shall have the lowest address of all addressable line isolators.  Remove 
jumper Jp1 from this module and connect it as per  Figure 1.  Other line 
isolators can be either LI-3000 or LI-3000E.  Other LI-3000 modules shall 
have the jumper in place. 
In ADR-3002C dual-loop line cards both loops shall be Class A or both loops 
shall be Class B – this definition is done for each line card and not for each 
loop.  Control panels that have two line cards can have one of the cards 
operate in Class B and the other as Class A. 

 

Figure 1  Connecting Class A loop for ADR-3000 

3.3 

Class B Configuration 

3.3.1 

Branching SLC Loop without Isolators 

When a short-circuit occurs in this configuration the system will stop communicating with 
the entire loop, and a trouble message will be displayed indicating the fault. 
If a disconnection occurs, devices connected to the circuit beyond the open wire will stop 
operating and a trouble message will be displayed on the ADR-3000’s panel indicating 
the faults. 

Содержание LI-3000

Страница 1: ...Technical Manual TELEFIRE FIRE GAS DETECTORS LTD PO Box 7036 Petach Tikva 49250 Israel Tel 972 3 970 0400 Fax 972 3 921 1816 eMail info telefire co il Web www telefire co il LI LI LI LI 3000E 3000E 3...

Страница 2: ...line and UL standards and Fault as used in EN 54 standards are used interchangeably throughout this manual i Note Do not install operate and maintain this LI 3000 or LI 3000E before fully reading this...

Страница 3: ...ble devices 3 Application 3 1 Characteristics After power up or reset of the system the isolator checks for short circuit condition If no short circuit is detected the isolator switches the circuit on...

Страница 4: ...r LI 3000 or LI 3000E Other LI 3000 modules shall have the jumper in place In ADR 3002C dual loop line cards both loops shall be Class A or both loops shall be Class B this definition is done for each...

Страница 5: ...e temporary disconnected before adding devices to a control panel Measure the wiring to ensure there are no shorts before connecting the wiring to the control panel Connecting or adding devices to a c...

Страница 6: ...nable key again to switch between Class A and Class B again To disable the line card press the Disable key To add an Isolator module to the system select the manual device programming screen in the co...

Страница 7: ...Ltd Revision 1 14 May 2015 Page 5 of 6 Figure 3 LI 3000 and LI 3000E Line Isolation Modules Figure 4 Connecting an LI 3000E in a raised base 4 3 Post Installation Tests Test that the system still work...

Страница 8: ...4 0 mA during short or open 5 2 LI 3000E Module PCB Dimension W H 25 75 mm AIB 800 Dimensions W H D 133 119 36 mm Operating Temperature Range 10 C 60 C 14 F 140 F Relative Humidity Range 10 93 non con...

Отзывы: