![Teledyne TIENet 310 Ex Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/teledyne/tienet-310-ex/tienet-310-ex_installation-and-operation-manual_1080367031.webp)
TIENet® Model 310 Ex Ultrasonic Level Sensor
Section 2 Installation and Setup for Signature
2-17
2.6 Level Calibration
Although all other programming steps can be performed off-site,
level must be set at the measurement site following installation,
at ambient temperature.
Once the sensor is installed over the flow stream, measure the
present liquid level (see figure at left) and enter this value for
Level, under Adjust Options. Then highlight “Adjust” and press
Enter to confirm.
From this screen, you can also update the display to show the
current level of the stream.
Figure 2-14 Ultrasonic level adjustment and calibration
D
d
h
D – d = h (level)
Configure Options
Adjust
1. Level
310 Level
LEVEL ADJUSTMENT
Adjust Level
1. 310 Level
Last reading:
X.XXX ft
Time of last
adjustment:
MM/DD/YYYY
TT:TT:TT
Update
Adjust
ft
Level:
1. Site Setup
2. Measurement Setup
3. Adjust
4. Equation/Trigger Setup
5. Data Storage/Push Setup
6. Sampler Setup
7. Inputs/Outputs/Alarms Setup
8. Reset Totalizers
9. Reports/History Setup
Display current
real-time level
Reset/calibrate
level
Содержание TIENet 310 Ex
Страница 2: ......
Страница 4: ......
Страница 14: ...TIENet Model 310 Ex Ultrasonic Level Sensor Section 1 Introduction 1 6...
Страница 35: ...TIENet Model 310 Ex Ultrasonic Level Sensor A 3...
Страница 36: ...TIENet Model 310 Ex Ultrasonic Level Sensor A 4...
Страница 38: ......
Страница 40: ......
Страница 42: ......