Charger Operation 

The Teledyne Battery Products TDMC+-01 offers two distinctive battery charging methods that are 
recommended for all lead-acid batteries.  The choice of method is guided by user selections that the 
user makes based upon the condition of the battery.  Once a charge cycle is initiated the charger will 
operate automatically and stop. The LCD text display and the LED color lights display inform the user of 
proper connection, charger operation and status of an operational charge cycle. 

Organization of the Screen and Options 

 

When not charging, the charger screen looks similar to the 
illustration shown on the right.  The screen is organized in 6 
sections as denoted by letters A-F: 

 

Battery Voltage, Battery Current and Charger Temperature: 
this information is shown in all modes and updates 
continuously. 

 

Indicated Voltage will be 00.0V when a battery is not 
connected; or will reflect the voltage of a connected 
battery. 

 

Indicated Amperage will be 00.0A 

 

Charger Operational Status: 

 

indicates whether the charger is “not charging” and idle, or if a charge cycle is in process.

 

 

Other possible indications include: 

 

Error: Rev Polarity 

 indicates an error that the charger senses that a battery has been 

connected in reverse polarity.   
For proper polarity connect the Positive (Red / +) charging cable to the Positive terminal 
on the battery.  Connect the Negative (Black / -) charging cable to the Negative terminal 
on the battery.  Reversing these connections results 

in the charger displaying a “Reverse 

Polarity” error.

  In the ev

ent “Rev Polarity” is displayed, disconnect the battery and check 

connections.  This error does not require a power reset to clear the error. 

 

Error: Not Connected 

 indicates an error that the charger senses a connection problem 

or under-voltage condition during a charge.  Disconnect the battery.  Inspect the power 
cabling for worn, frayed, corroded, or broken wiring. Verify the battery shows a nominal 
voltage for its rating, and that the charger is properly configured.  Reset the charger by 
disconnecting and reconnecting power.  

 

Error: Over-Voltage 

 indicates an error that the charger reaches an over voltage 

condition during the charge.  There may be a problem with the connected battery or an 
opening in the output cabling.  Disconnect the battery.  Inspect the power cabling for 
worn, frayed, corroded, or broken wiring. Verify no other circuits are connected to the 
battery.  Reset the charger by disconnecting and reconnecting power. 

 

Error: Over-Current 

 indicates that the charger reaches an over current condition during 

the charge.  There may be a problem with the connected battery or a short in the output 
cabling. Disconnect the battery.  Inspect the power cabling for worn, frayed, corroded, or 
broken wiring. Verify no other circuits are connected to the battery.  Reset the charger 
by disconnecting and reconnecting power. 

00.0V          00.0A
  - Not Connected -
Volt Cur  End At    
24V   6A    .5A

A

D

B

C

E
F

A

B

C

C

Idle Screen 

Содержание TDMC+

Страница 1: ...rights reserved TDMC Teledyne Dual Mode 12 and 24 VDC Lead Acid Battery Charger Redlands CA 92374 1 800 456 0070 1 909 793 3131 support teledynebattery com Product Name TDMC Part Number TDMC 01 Docume...

Страница 2: ...e 3 Product Description 4 Precautions and Warnings 5 Batteries 5 Location 5 Grounding and AC Power Cord 5 DC Output Connection 6 Charger 6 Personal Precautions 6 Charger Operation 7 Organization of th...

Страница 3: ...oltage mode User selects charger voltage for 12V or 24V operation as appropriate for the battery to be charged by pressing the button in Screen Section A Caution If a 12V battery is charged with a 24V...

Страница 4: ...Teledyne Battery Products TDMC is a battery charger for 12V and 24V lead acid batteries It offers two microprocessor controlled precision charging method a three stage charging method for normally dis...

Страница 5: ...smooth even uncluttered surface Allow adequate airflow around the unit during charging to prevent overheating Maintain minimum 3 7cm distance to wall Do not use the charger on a soft carpeted upholste...

Страница 6: ...C connection Make sure that the cable s terminals are free of any corrosion Charger Never operate a charger that has been damaged in any way including impact shock or excessive exposure to moisture pl...

Страница 7: ...g cable to the Positive terminal on the battery Connect the Negative Black charging cable to the Negative terminal on the battery Reversing these connections results in the charger displaying a Revers...

Страница 8: ...lete in the allotted time See charging Method details for allotted times Note in most Error conditions Selection Items A B C and D will vanish and the charger will not allow further operation until po...

Страница 9: ...ging Charger is idle Red Stopped on Error Red Green Charging Green Charge Complete Connection Red Battery is reverse polarity Red Green Battery not detected Green Battery is connected correctly Charge...

Страница 10: ...For Normally Discharged Lead Acid Battery Charge Method select End at 5A in Screen Section E With this selection the charger will follow the three stage charge mode recommended for use with all normal...

Страница 11: ...dition The Deeply Discharged or Sulphated Lead Acid Battery Charge Method ending condition is based on time The time should be based upon the battery capacity in amp hours and the desired charging cur...

Страница 12: ...the button in Screen Section F to start the charge cycle Details of the Two Stage Charge Mode 1 Stage 1 Constant Current Bulk Charge With the battery in a discharged state charging initiates in consta...

Страница 13: ...of Stage 1 2 10 80 hours selectable Max Absorption Voltage 15 0V 100mV 30 0V 100mV Unit Specifications Electrical Input Voltage 85 VAC 270 VAC 50 60 Hz Max Power 250 Watts Configuration Line neutral c...

Страница 14: ...ular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correc...

Страница 15: ...battery 5 Verify DMM matches voltage on screen 5V 6 Press Pause 7 Verify DMM matches voltage on screen 2V 8 Set DMM to current mode connect DMM in series with battery 10A mode 9 Resume charge press Go...

Отзывы: