
4220 Flow Meter
Section 1 Introduction
1-10
1.7 How to Make Battery
Calculations
To calculate battery life expectancy for an installation, you must
know two things:
• The
capacity
of the battery you are using
• The
average current draw
of the flow meter or (other
device) powered.
Compensated Temperature Range 32° to 122°F (0° to 50° C).
Temperature Error (over compen-
sated temperature range)
0.1 to 4.0 ft. (0.03 to 1.2 m) ±0.005 ft. per degree F
4.0 to 10.0 ft. (1.2 to 3.1 m) ±0.007 ft. per degree F
Table 1-3 Technical Specifications for the 3222 Submerged Probe (Continued)
Table 1-4 Chart Longevity
Chart Speed, Inches/Hour
Time to Empty Roll
4
195 Hours (8
1
/
2
Days)
2
16
1
/
4
Days
1
32
1
/
2
Days
0.5
65 Days
Note: Times assume Report Generator is turned
off
.
Table 1-5 Battery Life Expectancy
1
Flow Meter Settings Minimum
Default
2
Maximum
Reading Interval
5 Minutes
Continuous
Continuous
Printer
Off
Off
4” per Hour
Report Generator
Off
Off
Every Hour
Average Current
14 mA
9 mA
23 mA
Nickel-Cadmium
3
10.7 Days
5
16.6 Days
6.5 Days
Lead-Acid
4
17.4 Days
27 Days
10.5 days
Notes:
1.
These figures are approximations based on calculations; actual times for your flow meter may vary due to
factors of battery age, charge condition, operating temperatures, and component differences.
“Minimum” set-
tings are those providing the lowest average current draw. “Maximum” settings are those requiring the highest current
draw. Your program should draw somewhere between the two.
2. The default settings are the program entered at the factory. You can reset the flow meter to the default program at
any time by holding down the
1
and
Clear Entry
keys at the same time.
3. The nickel-cadmium battery has a capacity of 4.0 ampere-hours at 20° C.
4. The lead-acid battery has a capacity of 6.5 ampere-hours at 20° C.
Both batteries are assumed to be fully charged with at least
95% of rated capacity
and in good condition. These cal-
culations also assume a
5% safety factor
at the end of discharge. Lead-acid batteries should
never
be completely
discharged.
5. All fractional times are rounded down, rather than up.
Содержание 4220
Страница 2: ......
Страница 4: ......
Страница 8: ...4220 Flow Meter Safety ...
Страница 14: ...vi ...
Страница 19: ...4220 Flow Meter Section 1 Introduction 1 5 Figure 1 2 4220 Controls and Indicators ...
Страница 28: ...4220 Flow Meter Section 1 Introduction 1 14 ...
Страница 94: ...4220 Flow Meter Section 3 Installation 3 12 ...
Страница 156: ...4220 Flow Meter Appendix A Replacement Parts A 2 ...
Страница 157: ...4220 Flow Meter Appendix A Replacement Parts A 3 ...
Страница 160: ...4220 Flow Meter Appendix A Replacement Parts A 6 ...
Страница 164: ...4220 Flow Meter Appendix B Accessories List B 4 ...
Страница 172: ...4220 Flow Meter Appendix C Programming Worksheets C 8 ...
Страница 182: ...4220 Flow Meter Appendix D General Safety Procedures D 10 ...
Страница 194: ......
Страница 196: ...Warranty ...
Страница 198: ......