![TELEDYNE OLDHAM SIMTRONICS Everywhereyoulook BM 25A Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/teledyne-oldham-simtronics/everywhereyoulook-bm-25a/everywhereyoulook-bm-25a_user-manual_1081074043.webp)
BM 25A/AW
AREA GAS MONITOR
USER MANUAL
NPB25AEN
Revision D.0
35
Gas
Molecular
formula
LEL
1
LSE
2
Vapor
density
Coef. /
CH
4
.
Recom-
mended
calgas
Abbreviat
ion
(French)
Acetone
C
3
H
6
O
2.15 % 13 %
2.1
1.7
But/Prop ACO
Acetylene
C
2
H
2
1.5 %
100 %
0.9
1.3
But/Prop ACY
Butane
C
4
H
10
1.5 %
8.5 %
2.0
2.13
But/Prop BUT
Ethanol
C
2
H
6
O
3.3 %
19.0 %
1.6
1.5
But/Prop ETA
Ethylene
C
2
H
4
2.7 %
34.0 %
0.98
1.3
But/Prop ETY
G.P.L.
Prop+But
1.65 %
∼
9.0 % 1.85
1.9
But/Prop GPL
Natural gas
CH4
5.0 %
15.0 %
0.55
1.05
CH4
GNT
Hexane
C6H14
1.2 %
7.4 %
3.0
3.6
But/Prop HEX
Hydrogen
H2
4.0 %
75.6 %
0.069
0.89
But/Prop H2
Isopropanol
C3H8O
2.15 % 13.5 %
2.1
1.6
But/Prop ISP
Methane
3
CH4
5.0 %
15.0%
0.55
1.00
CH4
CH4
4.4 %
1.14
Methanol
CH3OH
5.5 %
44.0 %
1.1
1.25
But/Prop MTL
Pentane
C
5
H
12
1.4 %
8.0 %
2.5
2.08
But/Prop PNT
Propane
C
3
H
8
2.0 %
9.5 %
1.6
1.77
But/Prop PRO
Propylene
C
3
H
6
2.0 %
11.7 %
1.5
1.2
But/Prop PRY
Toluene
C
7
H
8
1.2 %
7.0 %
3.1
2.1
But/Prop TOL
Xylene
C
8
H
10
1.0 %
7.6 %
3.7
2.5
But/Prop XYL
List of pre-programmed combustible gases with coefficients
(1) Lower flammable limit.
(2) Upper flammable limit.
(3) The LEL adopted value for methane varies by country. The monitor integrates two
different LEL values for CH4 (4.4% vol. and 5.0% vol.)
5.3
Sensor calibration menu
Calibration consists of a zero adjustment in clean air (free from any gases that could be
detected by the gas monitor), as well as a sensitivity adjustment using calibration gas of
concentration between 15% and 100% of the full sensor range. Test gas shall be applied at a
60 liters per hour flow rate.
Содержание Everywhereyoulook BM 25A
Страница 1: ...NPB25AEN Revision D 0 BM 25A AW AREA GAS MONITOR USER MANUAL...
Страница 6: ...BM 25A AW AREA GAS MONITOR USER MANUAL VI NPB25AEN Revision D 0...
Страница 10: ...BM 25A AW AREA GAS MONITOR USER MANUAL 2 NPB25AEN Revision D 0 1 2 Product Overview Figure 2 Product Overview...
Страница 62: ...BM 25A AW AREA GAS MONITOR USER MANUAL 54 NPB25AEN Revision D 0...
Страница 67: ...BM 25A AW AREA GAS MONITOR USER MANUAL NPB25AEN Revision D 0 59 CSA Control Drawing for BM 25A AW Connections...
Страница 70: ...BM 25A AW AREA GAS MONITOR USER MANUAL 62 NPB25AEN Revision D 0...
Страница 71: ...BM 25A AW AREA GAS MONITOR USER MANUAL NPB25AEN Revision D 0 63...