![Telect Dual-Feed 350A 10/10-TPA Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/telect/dual-feed-350a-10-10-tpa/dual-feed-350a-10-10-tpa_user-manual_1080085006.webp)
© Telect, Inc., All Rights Reserved, 132505-5 A0
1.509.926.6000 :: telect.com
4
Dual-Feed 350A 8/8-TPA & 10/10
GMT Fuse Alarm Panel
Power
:: 009-8005-0810
1.2.3 Installation Procedure
ALERT
!
ALERT! Only qualified personnel may install and
maintain this product. Verify that all connections
meet requirements specified in local electric
codes or operating company guidelines before
supplying power. Protect this equipment with a
fuse or breaker sufficient to interrupt power levels
specified in Section “1.2 Specifications” on page 1.
Install this product in locations accessible only by
qualified personnel.
Panel brackets provide flush or 5-in. extended EIA
or WECO mounting in a 23-in. or 19-in. rack with an
equipment aperture of at least 17.4 in. (442 mm)
between the rack’s flanges.
1.
If necessary, remove the three screws and reposition
the brackets on the sides of the distribution panel, as
shown in Figure 2.
2. Locate an unused rack position and mount panel
using the four sets of screws and washers provided,
as shown in Figure 3. (It’s best to mount the panel
as high as possible on the rack.)
3.
Tighten the screws to 35 in.-lb (4.29 N•m).
4.
Loosen (you need not remove) the two screws
securing the rear terminal cover on the back of
the panel.
5. Remove the cover
WARNING
!
WARNING! Failure to properly ground this
equipment can create hazardous conditions
for installation personnel and for the equipment.
Holes for
Holes for 5-in.
Flush M ounting
Extended M ounting
Figure 2 - Bracket Orientation
Figure 3 - Rack Mounting