3.7
Settings of the implemented configurations
Definition for the following tables:
Lines highlighted in gray mean that the associated parameters can be edited. All other settings are fixed.
Connection Modes
2-wire
Only the voltage between L1 and N is evaluated
3-wire
Only the line to line voltages U
L1-L2
, U
L2-L3
and U
L3-L1
are evaluated
4-wire (LN)
Only the phase-to-neutral voltages U
L1-N
, U
L2-N,
and U
L3-N
are evaluated
4-wire (LN+LL)
Both the phase-to-neutral voltages U
L1-N
, U
L2-N,
and U
L3-N
as well as the phase to
phase voltages U
L1-L2
, U
L2-L3
, and U
L3-L1
are evaluated
Units
%Unom
Percent of the nominal voltage (nominal voltage factor)
Functional safety
Errtol 2ch
2 separated contactors with 2 separated auxiliary contacts are connected
Errtol 1ch
1 external contactor with 1 auxiliary contact is connected
Operational mode
It is possible to switch between 2 different operating modes
Is currently only used for the CEI-021 … see CEI-021 8.6.2.1.1
Mode 0:
transitory mode
Mode 1:
definitive mode
Thresholds
U
THR
OFF
Voltage threshold for the turn-off
U
THR
ON
Voltage threshold for turn-on
f
THR
OFF
Frequency threshold for the turn-off
f
THR
ON
Frequency threshold for turn-on
RoCoF
THR
OFF
Frequency change threshold for the turn-off
RoCoF
THR
ON
Frequency change threshold for turn-on
PShift
THR
OFF
Phase shift threshold for the turn-off
PShift
THR
ON
Phase shift threshold for turn-on
Times
Time OFF
Turn-off delay
T on delay
Turn-on delay
Auxiliary contact
Read back of the position of the actuated contactors (via positively-driven auxiliary contacts) is required for
the necessary functional safety. The following can be selected for these auxiliary contacts:
Contact n.c. (normally closed)
Auxiliary contact is normally opened (recommended implementation)
Contact n.o. (normally opened) Auxiliary contact is normally closed
Contact dis. (disabled)
Auxiliary contact is ignored (impermissible for standards that require
functional safety)
Ranges
Conformity range
Within this range, the device is configured in compliance with the selected
standards. Outside of these ranges, the device is no longer compliant with
standards and the corresponding certificates lose their validity. This status is
shown on the display by the identifier "ncnf." Settings outside of this range are
therefore within the operator's scope of responsibility and/or the acceptance
authority of the system.
Possible range
Technically possible setting range