4.1.2 Power Connector Cable
Warning
The power cable is not supplied with the router. The estimated peak consumption for 230V AC opera-
tion is 100 mA. Any cable with a cable gauge equal or greater than a 0.75 mm2 section (AWG18 con-
ductor) and approved by IEC 60227 is acceptable.
Warning
All interconnected communication devices should be plugged into THE SAME GROUNDED POWER
OUTLET, which should at the same time be of good quality (lower than 10 ohms).
Whether the workplace is provided with an uninterrupted power supply system (UPS), regulated supply
or it is independent from the rest (such as lighting, etc.); it is highly recommended that all data devices
should be connected to the same power source. This will avoid operating and premature aging prob-
lems of drivers and other components.
4.1.3 Connecting
• Ensure that the power supply is NOT connected to either the electricity supply
or the router.
• Connect all data cables.
• Connect the power supply cable to the device.
• Install the protective case for connectors.
• Connect the power supply cable to the electricity supply.
4.1.4 Disconnecting
• Disconnect the power supply from the electricity supply.
• Remove the protective case.
• Disconnect the power supply from the router.
• Disconnect the data cables.
4.2 Data connections
The Regesta Smart PLC has the following data connections.
4.2.1 LAN connection
The Regesta Smart PLC incorporates one 10/100/1000 BaseT Gigabit Ethernet port with automatic MDI/MDIX to
connect to a local area network (LAN).
Please pay careful attention to the labeling to avoid mistaking this port for other types of ports: