Tips for correct Installation:
1) The cross section of the cables should be calculated according to their length and absorbed current.
2) Do not use a single cable of the "multi-core" type for all the connections (line, controls, etc.) or in common with other equipment.
3) Use at least two cables for the installation, e.g.:
cable (A) minimum wire section 1.5 sq.mm
- power supply line - courtesy / flashing light line
cable (B) minimum wire section 0.75 sq.mm
- auxiliaries power supply - controls - safety contacts.
4) When the control cables are very long (over 50 metres), de-coupling is advisable with relays mounted near the control unit.
5) Any N.C. Inputs (photocells, limit switches, fixed safety edge and stops) that are not used In the control unit should be short-
circuited with the common terminal terminal.
6) All the N.C. contacts linked with the same input should be connected in series.
7) All the N.O. contacts linked with the same input should be connected in parallel.
F6,3A
230V
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
27
28
29
30
31
F0,3A
24V
RECEIVER mod.
OC2
motor
P1
(P/P)
P2
(PED)
MEMORIA
TRANSMITTER
Rx
Tx
Sec. 24Vac (Orange)
230V
Flasher
230V
Courtesy light
OPENING input
PROG.
STOP
P/P
CLOSING input
Step/step input
Stop input
JOLLY input
FT1
Photocell input
Common input
SPIA 24Vac CA
power supply
photocells with
FOTO-TEST
RECEIVER
ANTENNA
Com. Motor (Blue)
ENCODER
230V primary
transformer
Sec. 12Vac (White)
24V (Yellow)
Com. (Brown)
FC(1) Green
FC(2) White
24Vac
EVO1200R
Fuse
F1A
Condensatore
FCC
Ap
Ch
P/P
Stop
Jolly
FT1
FCA
Power
Supply
230V 50Hz
N
L
Содержание EVO1200
Страница 2: ...1 Fig A 1 5 4 3 2 18 I F E GB D NL 6 12 11 10 9 8 15 16 17 13 14 7 ...
Страница 3: ...2 190 153 177 305 165 140 276 206 60 Fig B I F E GB D NL ...
Страница 4: ...Fig C dx dx sx sx Fig D 90 309 Fig E 40 80 40 3 I F E GB D NL ...
Страница 5: ...Fig F Fig H Fig G 5 10mm 4 I F E GB D NL ...
Страница 55: ...NOTE ...