AFA1000/BLD Pressure Controller 

 

Installation & Operating Manual

1. 

  There are various operational setting that need 

to be set to give good control of the extract duct 
pressure. These setting are adjustable in the 
‘Control configure menu’. Due to the possible 
variations in the applications each unit will be 
supplied with a printed sheet giving the values 
of the parameters as set in the factory before 
dispatch. (These can also be viewed using a Laptop 
computer plugged into the ‘Com port’). The factory 
settings are based on previous experience of similar 
installations but may require some adjustment to 
suit the particular installation.(These setting should 
only be adjusted by experienced engineers familiar 
with controls and the requirements of the fume 
cupboard installations.)

2.

   Certain parameters can be pre-set from knowledge 

of the installation :-  

     

 Set  point

      This is the desired extract duct 

pressure (during commissioning)                                

      

Damper / Inverter      

For systems with bleed 

damper control or variable speed extract fan using 
an Inverter 

      

Output range

      2-10V or 0-10V depending on 

what is being controlled

3.

   Certain parameters can be adjusted (in small 

increments) to improve the stability and         
performance of the control :-

      Stability:

 The stability of the system can be effected 

by two main items – turbulent airflow across the 
face of the pressure sensor or the ‘sensitivity’ of the 
control loop. It is important to establish the cause 
of the problem before attempting to adjust any 
parameters. 

      

To do this put the control system into ‘Manual’ 
operation and check the stability of the measured 
pressure. In this condition the bleed damper or 

Inverter will be at a fixed    position so any instability 
seen will be due to the extract system or to 
turbulent air across the sensor. This can be check 
and corrected.

       

If the system is stable in the ‘Manual mode’ the 
problem could be due to the control sensitivity 
being too high. The sensitivity is set by the ‘Prop 
Band’ in the ’Control config menu’. This can be 
increased to reduce the sensitivity. 

       Performance:

 To reduce the time for the measured 

value to go to the set point value ( ie removal of the 
‘offset’ ) after a change in duct pressure the ‘Integral 
time’ in the ‘Control config menu’ can be increased. 
This is normally set to 20 reps/min

4.  

 

MIN  ---

 This is a manual fixed position select by the 

Night set-back activation and can be adjusted to the 
desired value.

      MAX  --

 This is a manual fixed position select by the 

Emergency activation and can be adjusted to the 
desired value.

      Low limit -

 This is used to limit the travel of the 

damper in the opening position or the min speed of 
the extract fan to maintain the desired extract rate 
from the fume cupboards in normal operation as 
the sashes are closed.

      High limit -

 This is used to limit the travel 

of the damper in the closing position or                                   
the max speed of the extract fan to maintain the 
desired max extract rate from the fume cupboard in 
normal operation as the Sash is opened.

Note :- 

 The above information is a guide only 

on how to set up and calibrate the controls             
incorporating the AFA1000 / E / Bld controller.

7  CONTROL SETTINGS

7.1  Control Settings 

Содержание AFA1000/BLD

Страница 1: ...Installation Operating Manual Temperature Electronics Ltd Unit 2 Wren Nest Road Glossop SK13 8HB United Kingdom AFA1000 BLD Pressure Controller...

Страница 2: ...ical Protection 8 1 8 EMC Compliance 8 1 9 Warning Labels 8 2 Overview of the Pressure Controller 9 5 2 1 Operator Display Panel 10 2 2 Display Features 11 2 3 Displayed Alarms and Events 12 2 4 LED I...

Страница 3: ...ion Diagram 26 5 3 Dimensions details 27 5 4 Typical Wring diagram Damper Control 28 5 5 Typical Wring diagram Inverter Control 29 6 Operation Notes 30 6 1 Operation Notes 31 7 Control Settings 32 7 1...

Страница 4: ...1 SAFETY...

Страница 5: ...in the other documentation supplied When setting up the equipment or performing analysis or maintenance procedures strictly follow the instructions provided 1 2 Warning Notices Within this User Guide...

Страница 6: ...operative However if any adjustment maintenance or repair is necessary while the covers are open this must be done by a skilled person who is aware of the hazards involved Whenever circumstances arise...

Страница 7: ...nal parts removed Disconnect the equipment from all live voltage sources before opening it to make any adjustments replacements maintenance or repair If the opened equipment must be operated for furth...

Страница 8: ...e expected 1 8 EMC Compliance EC Directive The Airflow Monitor System is designed and tested to meet the requirements of the EC directive 89 336 EEC and 93 68 EEC and complies with the EMC standard EN...

Страница 9: ...2 OVERVIEW OF THE PRESSURE CONTROLLER...

Страница 10: ...ction and up down buttons for Menu Configuration and Calibration ENTER also used as Mute button for audible alarm Note Access to the Calibration and Configuration menus is password protected and is fa...

Страница 11: ...above are configurable via the alarm key pad The displayed pressure colour will change when in an alarm condition Air Safe White Low or High Air Alarm Red Warning Air Alarm Amber An event time line s...

Страница 12: ...ng Set back will be displayed if the night set back function is activated when enabled This display will alternate on off with the pressure reading 2 4 LED Indicators The alarm unit has three LED indi...

Страница 13: ...is multi functional as follows Press Enter momentarily when alarm is sounding will mute the alarm Press Enter for 5 secs will gain access to Calibration and Configuration menus both menus password pr...

Страница 14: ...n Safe LED will illuminate The screen will then show Testing Warning LED and the Amber Warning LED will illuminate The screen will then show Testing Alarm and the Red Alarm LED will illuminate and the...

Страница 15: ...ot assigned Output Data Output 1 Off On A Out 1 10 0 Output 2 Off On A Out 2 10 0 Output 3 Off On Output Off Output Open or not assigned Output On Output Closed A Out 1 Analogue Output 1 voltage 0 10V...

Страница 16: ...t Analogue input 0 5V of the pressure sensor range selectable on the pressure transducer Relay Output 1 Analogue input 0 5V of the pressure sensor range selectable on the pressure transducer Relay Out...

Страница 17: ...t RS 485 to enable connection to Laptop or PC for full diagnostics logging or setting up and for communications to building computer system BMS See section 8 for other specific information on Modbus R...

Страница 18: ...3 FUNCTIONS OPERATION...

Страница 19: ...ber LED on Low pressure Meter reads below Low pressure alarm level for longer than the delay time LOW PRES toggles on off with display Red LED on Flashing Audible alarm sounds can be muted via Enter p...

Страница 20: ...abled Emergency When input configured as Emergency is activated Red LED on Flashing if configured EMERGENCY toggles on off with display if configured Audible alarm sounds can be muted via Enter pushbu...

Страница 21: ...es 0 V Display value below the set point the output voltage increases 10 V b Min Max and Limit settings Direct Action Max Output Output voltage increases 10 V Minimum Output Output voltage decreases 0...

Страница 22: ...4 COMPONENTS...

Страница 23: ...the tube connection adapter with the tapered side facing away from the airflow to prevent the influence of the velocity pressure 3 Select a position on the duct with the minimum number of bends or du...

Страница 24: ...5 INSTALLATION...

Страница 25: ...select CAL Configure and go to Pressure Range and select the pressure range to suit the pressure transducer being used This menu also allows the Low Warning and High pressure alarms to be set When co...

Страница 26: ...Version 01 p 26 AFA1000 BLD Pressure Controller Installation Operating Manual 5 2 Typical Installation diagram...

Страница 27: ...Version 01 p 27 AFA1000 BLD Pressure Controller Installation Operating Manual 5 3 Dimensions details NOT TO SCALE...

Страница 28: ...Version 01 p 28 AFA1000 BLD Pressure Controller Installation Operating Manual 5 4 Typical Wring diagram Damper Control...

Страница 29: ...Version 01 p 29 AFA1000 BLD Pressure Controller Installation Operating Manual 5 5 Typical Wring diagram Inverter Control...

Страница 30: ...6 OPERATION NOTES...

Страница 31: ...s the volume from the fume cupboards varies See Control Settings below for details on the fine tuning of the controls 2 Extract Fan speed control for VAV extract systems This application is for the ex...

Страница 32: ...7 CONTROL SETTINGS...

Страница 33: ...ng to adjust any parameters To do this put the control system into Manual operation and check the stability of the measured pressure In this condition the bleed damper or Inverter will be at a fixed p...

Страница 34: ...8 RS485 COMS OUTPUT...

Страница 35: ...egisters for further technical compliance and register information AFA1000 BLD Modbus Registers AFA1000 BLD BACnet Registers Typical connection diagram Protocol Description TEL Protocol for connection...

Страница 36: ...ess and Hold the Enter button for 5 seconds until the Main Menu is displayed 2 Using the buttons select SET UP and then select CONFIGURE then enter the password the factory default password is 0 0 0 0...

Страница 37: ...ss Enter to continue 6 Using the buttons select the STATION ID parameter and then press Enter then using the buttons select the required ID and press Enter to continue 7 Using the buttons select the B...

Страница 38: ...received the displayed value will rollover to zero when the maximum count is reached BACnet protocol troubleshooting guide Protocol Fault Remedy A BACnet Device not present on Network Ensure the AFA1...

Страница 39: ...also available to buy from directly from TEL Recommended minimum PC requirements Windows XP or later 2GHz processor 3 00GB Ram 1MB free storage space Config Manager uses the TEL protocol on the AFA10...

Страница 40: ...Version 01 p 40 AFA1000 BLD Pressure Controller Installation Operating Manual Connection Diagram with RS232 485 converter...

Страница 41: ...9 WARRANTY...

Страница 42: ...t the Buyer s risk of loss Seller s factory prepaid and will be returned at Seller s risk of loss Buyer s factory prepaid The foregoing is IN LIEU OF all other warranties and is subject to the conditi...

Страница 43: ...Temperature Electronics Ltd Unit 2 Wren Nest Road Glossop SK13 8HB United Kingdom Tel 44 0 1457 865635 Fax 44 0 1457 868843...

Отзывы: