4. Mounting

The transducers of the Tek-Clamp 1200A-100F1 can be mounted in 2 ways: the V method and the Z method.

 

 

V Method

The V method is a standard installation method and convenient to use for precise measurement of flow. While 

installing the two transducers, they are horizontally aligned. The transducers center lines are parallel with the 

pipe axis line. They are suitable for pipe diameter range ½” to 16” (DN15 mm-DN400 mm).

Z Method

When the pipe diameter is wide, there are suspended matters in the fluid, or the scaling is too thick, it can inter-

fere with the normal functioning of the flowmeter, this weakens the signal in a V method installation. If this hap-

pens, the Z method of installation is used. It is also called the single sound path as it can directly transfer the 

pulse without any reflection required, which is required in V method and therefore has less signal attenuation.

Содержание Tek-Clamp 1200A

Страница 1: ...QuickStartGuide Tek Clamp1200A UltrasonicClamp OnFlowmeter 796 Tek Drive Crystal Lake IL 60014 USA 1 847 857 6076 1 847 655 7428 1 847 655 6147 www tek trol com...

Страница 2: ...e transmitter is installed by qualified personnel and in accordance with the applicable code of practice Disconnect the power before servicing to prevent ignition of flammable or combustible atmospher...

Страница 3: ...parallel with the pipe axis line They are suitable for pipe diameter range to 16 DN15 mm DN400 mm Z Method When the pipe diameter is wide there are suspended matters in the fluid or the scaling is too...

Страница 4: ...6 Power Supply 5 Display TheTek Clamp 1200A Ultrasonic Flowmeter uses of a 16 key keyboard monitor The 16 keys include 10 Digit keys 2 Up Down arrow keys 1 Menu key 1 Enter key 1 Decimal Point key and...

Страница 5: ...ed with the help of a 16 key keyboard monitor Below some of the keyboard uses are outlined 0 9 and are used to input numerical values and menu numbers key is used to left backspace or delete left char...

Страница 6: ...uide QuickStartGuide QuickStartGuide 796 Tek Drive Crystal Lake IL 60014 USA 1 847 857 6076 1 847 655 7428 1 847 655 6147 www tek trol com The length of pipe that is more than 5 times pf pipe diameter...

Страница 7: ...be taken from floor level Mount the enclosure on a vibration free surface Avoid sites such as the plenum of a fan coil heat exchanger or other housings containing motors Avoid mounting the enclosure...

Страница 8: ...QuickStartGuide Tek Clamp1200A 796 Tek Drive Crystal Lake IL 60014 USA Tel 18478576076 18476557428 Fax 18476556147 Email tektrol tek trol com www tek trol com Technology Solutions...

Отзывы: