Rev.BRA-v1_6_en
4
9 Wiring diagram
R
- resistance 3.9 kOhm ,
Е1
- button with normally open contacts,
Е2
- button with normally closed contacts,
K1, K2
– valve limit switch
10 Test
Testing is taking place with one of two ways:
1 way
– using button TEST which is
connected to the TST terminal
:
-
set the TEST button to the “Violated” state (press or release depending
on the type and setting of the BRA);
- visually control the transition of the valve to the
РАБ (operation) state,
then to
ИСХ (initial);
- control the state of the valve in Astra Pro PKM (Astra-812 Pro Control
Panel, Astra-814 Pro keypad): after the test is completed, the status is
displayed as “Valve in the initial state”, which means that the equipment is
configured correctly.
Otherwise, the status is displayed as “Failure” and
the BRA settings need to be adjusted.
2 way
- using Astra-942
:
-
light up the SLC indicator of the BRA from the top button of the left side
for at least 1 sec
;
- the test is performed in the same way as described in the first method.
If during the test execution the BRA receives a command from the control
panel, then the test execution is terminated, the new state “Transition to
...” is assigned to the valve state, the control panel generates the “Valve
test completed” event, and the BRA executes the command from the
control panel.
11 Warranty
The operation warranty period is 5 years from the date of operation start-
up, but no longer than 5 years 6 months from the date of manufacturing
subject to the requirements of User guide.