2.  Planning the System

In TKT24C system the monitoring data between the CBU and the luminaires is transferred via 

the circuit cables. There is no need for separate data cabling, and the supply cables can be 

drawn as any emergency lighting cabling would be. The following, how ever, must be taken 

into account:

•  All luminaires must be addressable Teknoware 24 V luminaires. The product code must end with 

..41..K, for example TWT9041WK. These type of luminaires contain the necessary electronics for 

the communication between the CBU and the luminaires.

Each of the luminaires within a circuit must have an individual address. (1..32). Addresses can 

be chosen freely, as long as there is no overlapping addresses within a circuit. The addresses 

are marked to the included label accorging to electrical planning (circuit nr. / luminaire nr.). 

Additional information about setting the address can be found from the documents delivered 

with the luminaires.

3.  Installing the System

Make sure to read Chapter 3.1. "Connections, Parts and Layout" installing the system.

1.  Open the case by unfastening the two screws.

2.  Attach the CBU firmly to a wall. Use all four wall mounting holes (see image in Chapter 

3.1 to locate them), and take notice of the mass of the CBU and batteries.

3.  Make sure that the input- and the battery fuses are in position 0 before connections.
4.  Connect the circuits.
5.  If applicable, connect the ACM data cable, relay-guided devices, and remote control.
6.  Connect mains cable.
7.  Lift the batteries to the battery shelf.
8.  Place the temperature sensor between the batteries.
9.  Connect the batteries in series (check the polarity and insulation distances). Start from 

the furthest battery (looking from the battery fuse), and connect the battery connected to 

the battery fuse last.

10. Check the batteries and connections for short circuits.
11. Switch the battery fuse to position 1
12. Switch the input fuse to position 1.
13. Fasten the case with the two screws
14. The CBU is ready for commissioning

Содержание TKT24 series

Страница 1: ...TKT24series Installation and User Guide Addressable 24 V Central Battery Unit...

Страница 2: ...DICATOR LEDs This product may only be installed or maintained by a qualified electrician Central Battery Unit is ON Mains mode Battery mode Batteries recharging Error see Chapter 8 for details about e...

Страница 3: ...e System 7 3 Installing the System 7 3 1 Connections Parts and Layout 8 4 Commissioning 11 5 Structure of the User Interface 11 6 Main View 12 7 Main Menu 12 7 1 Circuit and Luminaire Configurations 1...

Страница 4: ...LTAGE 16 8 3 DEEP DISCHARGE 16 8 4 BATTERY UNDERVOLTAGE 16 8 5 TEMPERATURE ERROR 16 8 6 MAINS NOT PRESENT 16 8 7 MOSFET BROKEN circuit board number 16 8 8 LUMINAIRE BROKEN 17 8 9 FUSE ERROR 17 9 Mecha...

Страница 5: ...ctions Testing of addressable luminaires and the monitoring of their operation indicaties the address of faulty luminaire Tests the batteries automatically Tests can also be started manually Self lear...

Страница 6: ...4 AT Battery Fuse Circuit breaker32 A 250 VDC Output connector Max wire 4 mm Mass without batteries TKT2404C 11 1 kg TKT2408C 16 0 kg Voltage limits When mains drops below 165 VAC the CBU supplies vol...

Страница 7: ...m the documents delivered with the luminaires 3 Installing the System Make sure to read Chapter 3 1 Connections Parts and Layout installing the system 1 Open the case by unfastening the two screws 2 A...

Страница 8: ...n there is an internal fault in the CBU luminaire error does not change the relay position Remote control When a relay connected to this is in normal open position the CBU goes into battery mode 3 1 2...

Страница 9: ...y connections Relays remote ctrl and temp sensor Output circuits Battery shelf Holes for cables For circuit cables and mains also on top Data connection RS485 Connection for ACM modem Wall mounting Wa...

Страница 10: ...20 240V AC 50 60Hz 1 L N PE RS485 connection for ACM B A ERROR relay BATT relay WORK relay Temperature sensor Remote Control Output Circuits L 1 2 3 4 5 6 7 8 Output Circuits N 1 2 3 4 5 6 7 8 Circuit...

Страница 11: ...rom battery mode see chapter 7 7 3 7 Optional set a password see chapter 7 7 5 8 Optional set a local address for the CBU for ACM see chapter 7 7 6 9 Get luminaire configuration see chapter 7 3 Changi...

Страница 12: ...configuration Empty There is no luminaires in the circuit OK Circuit contains luminaires all functioning normally Error Circuit contains luminaires one or several luminaires have reported and error V...

Страница 13: ...tings Local address Set a local address for the CBU for ACM Setup password Set a password to protect the system from unauthorized access 7 5 Setting the Time Settings Set time and date Set the time an...

Страница 14: ...Battery Settings Settings Battery settings Set operation time Set the intended operation time for batteries for testing purpose Battery test mode Battery test settings Set switch delay Set a delay for...

Страница 15: ...st to a national holiday 7 7 5 Password Protection Settings Setup password Set a four digit password with the selection button Save the pass word and exit by pressing the selection button long If you...

Страница 16: ...lts Error will be removed after the battery voltage exceeds 19 6 volts and the user aknowledges the error message by pressing teh selection button During the error the CBU will be in power save mode 8...

Страница 17: ...uminaire and replace or fix the luminaire 8 9 FUSE ERROR There are luminaires defined for a circuit but there is no electrical load in the circuit Check the circuit fuse If there is only one luminaire...

Страница 18: ...18 6 500 431 62 22 477 604 112 604 477 112 22 9 Mechanical Dimensions TKT2404C...

Страница 19: ...19 6 431 500 62 22 477 604 200 604 477 200 22 10 Mechanical Dimensions TKT2408C...

Страница 20: ...200 Lahti Tel 358 3 883 020 Fax 358 3 883 0240 emexit teknoware com teknoware com We reserve the right to make modifications without notice 2018 Teknoware All rights reserved 11 2018 TKT24 Central Bat...

Отзывы: