TFM-1010, TFM-1110,
And TFM-1320
Analogue Input / Output Modules
Installation & Operation Manual
Issue Date: 16/12/2019
Rev:04
Important Warnings
General
✓
Before using the device read this manual carefully. Keep it just in case of necessity.
✓
Abide all the rules and precautions stated in the manual. Follow all the instructions one by one.
✓
Keep the devices away from water and moisture
Conditions
Do not energize the device above or below the given limits of extreme hot or cold conditions,
Temperature
:
Between
-
10°C and +55°C
Relative Humidity:
%95 RH max
Service
Do not try to fix the device on your own. Removal of cover may end up with electricity shock.
In case of any defect or malfunction, contact with your dealer or with authorized service. All the technical
interventions have to be done by technicians of company.
Malfunctions that require technical service
In case of any malfunction or below conditions contact with your authorized service,
✓
When Mains cable or the plug is harmed,
✓
Contact of device with a fluid,
✓
Exposure of rain and water,
✓
Fell down of device or harmed outer cover,
✓
Serious performance fall on the device,
✓
Depending on the instructions stated in manual, if your device not working properly
Contact with your authorized service in such terms.
Maintenance on your own
Do not try to fix the device on your own. Removal of cover may end up with electricity shock. In case of any
defect or malfunction, contact with your dealer or with authorized service. All the technical interventions have
to be done by technicians of company. Device must be cleaned up with a dry fabric. No-chemicals are
allowed for cleaning
Transportation
Device must be carefully transported avoiding all physical bump, stroke and possible fluid entry. Malfunctions
that caused by improper transportation is not under warranty.
Human and Environmental Health
This device contains no chemical or biological elements that could harm human condition.
Technical Features
Power Input
15V (min)
–
32V (max)
Average Current Consumption (Normal Condition)
180uA (@24V)
Average Current Consumption (Alarm Condition)
500uA (@24V)
Operating Temperature Range
-10
C ~ 55
C (14
F ~ 131
F)
Humidity
95% RH (max)
Dimensions (mm)
15,6mmx44,8mmx62,6mm
Weight
50gr(max)
Setup
Teknim Analogue Addressable Input / Output Modules communicate via Flashlink protocol. The device is
compatible with Analogue Addressable Panels (TFP-12XX series). The input / output connections of each
model must be checked before terminal connections are made. Modules should also use 33K as the line end
resistance and 10K as the alarm resistance.
Addressing
A special addressing module (TFCM-1801) designed by Teknim must be used to address the input and output
modules. Modules can be addressed from 1 to 240. It should be noted that the addresses of each device in
the vicinity must be unique.
TFM-1010 Dry Contact Input Module
The TFM-1010 module is used for dry contact monitoring. The input is determined via the panel that will
operate as "Normally Open" or "Normally Closed". (TFP-12XX Analogue Addressable Panel Operating Guide -
Monitoring Type for details). Whether the status changes in the input modules are monitored once or
continuously can be selected again via the panel. (For details TFP-12XX Analogue Addressable Panel
Operating Guide - Latch Type)
The line end resistance is (
𝑅
𝑠
) 33K and the alarm resistance
(
𝑅
𝑎𝑙𝑎𝑟𝑚
) is 10K.
Terminal Explanation
1
Loop line INPUT (+)
2
Loop line INPUT (-)
3-4
Earth connection
5
Loop line OUTPUT(-)
6
Loop line )
7
Input (+)
8
Input (-)
Warning:
Do not attempt to remove the electronic board from its plastic case. The electronic board is
closed for your safety. Users should avoid from interference.