25 of 32

© 2007

D 422 - 08/07

DHW with Low Temperature Boilers 

Section I

If DHW heating is to be incorporated into a low temperature 
system such as a radiant floor heating system, a mixing 
device is often installed to isolate the high DHW supply 
temperature from the lower system temperature. If a mixing 
device is not installed, high temperature water could be 
supplied to the low temperature system while trying to 
satisfy the DHW demand. This may result in damage to 
the low temperature heating system.

The control is capable of providing DHW heating in such a 
system while minimizing the chance that the temperature 
in the heating system exceeds the design supply water 
temperature. In order to do this, the control must be set 
to DHW MODE 2 or DHW MODE 4 and Boil MIN must be 
set to OFF.

On a call for DHW, the control provides DHW priority by 
sending a message on the boiler temperature bus to the tN4 
thermostats to shut off the heating zones for a period of time. 
The length of time is based on the outdoor air temperature as 
described in the DHW Priority Override section. However, if 
the DHW Demand is not satisfied within the allotted time, the 
boiler shuts off and the heat of the boiler is purged into the 
DHW tank. A DHW mixing purge occurs in order to reduce 
the boiler water temperature and once the boiler supply 
temperature is sufficiently reduced, the DHW Pump contact 
shuts off. The heating system zones are allowed to turn on 
for a period of time to prevent the building from cooling off. 
After a period of heating, and if the DHW Demand is still 
present, the control shuts off the heating system and provides 
heat to the DHW tank once again.

Setpoint Temperature Operation 

Section J

Setpoint

The control can operate to satisfy the requirements of a 
setpoint load in addition to a space heating load and a 
DHW load. A setpoint load overrides the current outdoor 
reset temperature and WWSD setting in order to provide 
heat to the setpoint load.

Setpoint Demand

A Setpoint Demand is required in order for the control to 
provide heat to a setpoint load.
The control registers a setpoint demand when a voltage 
between 24 and 230 V (ac) is applied across the Setpoint 
Demand terminals (55 and 56). Once voltage is applied, 
the Setpoint Demand segment turns on in the LCD.

Conditional DHW Priority

If the boiler supply temperature is maintained at or above the 
required temperature during DHW generation, this indicates 
that the boiler has enough capacity for DHW and possibly 
heating as well. As long as the boiler supply temperature 
is maintained near the target, DHW and heating occurs 
simultaneously.

DHW Post Purge

After the DHW Demand is removed, the control performs 
a purge on the boiler. The control shuts off the boiler and 
continues to operate the DHW pump and the primary pump 
(P1) if applicable. This purges the residual heat from the 
boiler into the DHW tank. The control continues this purge 
for a maximum of four minutes or until the boiler supply 
water temperature drops 20°F (-6.5°C) below the boiler 
target temperature during the DHW operation. The control 
also stops the purge if the boiler supply temperature drops 
below the current boiler target temperature.

DHW Mixing Purge

After DHW operation, the boiler is extremely hot. At the same 
time, the heating zones may have cooled off considerably 
after being off for a period of time. When restarting the 
heating system after a DHW demand with priority, the control 
shuts off the boiler and continues to operate the DHW pump 
while the primary pump is turned on. This allows some of 
the DHW return water to mix with the cool return water from 
the zones and temper the boiler return water.

DHW

Pump

Primary

Pump

OFF

Содержание Universal Reset Module 422

Страница 1: ...er temperature to provide Domestic Hot Water or Setpoint operations The 422 can operate two outdoor reset water temperatures either one boiler water temperature and a single mix water temperature or t...

Страница 2: ...witchtolockandunlocktheAccess Level of the 422 and all connected tN4 devices including tN4 thermostats For details see Access Levels Once locked the access level in all devices cannot be viewed or cha...

Страница 3: ...r Off Flushing The Off Flushing DIP switch selects whether the control operates a Flushing feature Heating systems that use potable water require periodic flushing to prevent the water from stagnating...

Страница 4: ...Displays when a mix 2 demand is present DHW DEMAND Displays when a DHW demand is present SETPOINT DEMAND Displays when a Setpoint demand is present DEVICE OUTPUT SCALE Displays output of the modulati...

Страница 5: ...be selected The abbreviated name of the selected item displays in the Item field of the LCD display To view the next available item press and release the Item button To view the previous item hold do...

Страница 6: ...Current Mix 2 supply water temperature as measured by the Mix 2 supply sensor Note This item is only available when the tN4 DIP switch is set to Mix 2 35 to 230 F 1 5 to 110 0 C Ad MIX 2 TARGET SECTIO...

Страница 7: ...r Note This item is only available when the Boiler Sensor Sup Ret DIP switch is set to Ret 0 100 Ad BOILER MODULATION SECTION C Current percent modulation of the boiler s burner Note This item is only...

Страница 8: ...inal units that are being used in Mix 1 zones 40 to 100 F 4 5 to 38 0 C Default 70 F 21 0 C Ad MIX 1 INDOOR SECTION B The design indoor air temperature used in the heat loss calculation for Mix 1 zone...

Страница 9: ...on the typical coldest day of the year Note This item is only available when the tN4 DIP switch is set to Mix 2 OFF 40 to 150 F OFF 4 5 to 65 5 C Default OFF Ad MIX 2 MINIMUM SECTION G The minimum all...

Страница 10: ...et temperature Note This item is only available when the Boiler Sensor Sup Ret DIP switch is set to Sup and the tekmar stager DIP switch is set to OFF 0 00 to 3 00 min Default 0 10 min Ad FIRE DELAY S...

Страница 11: ...lel no priority 2 parallel priority 3 pri sec no priority 4 pri sec priority Default 1 InS Ad DHW MODE SECTION H Selects the DHW mode of operation This determines the operation of the primary pump in...

Страница 12: ...uring the Sleep and Unoccupied periods Note This item is only available when Setpoint Mode is set 1 through 4 and a network setback schedule is selected 40 to 100 F OFF 4 5 to 38 0 C OFF Default 70 F...

Страница 13: ...henthetN4Boil Mix2 DIP switch is set to Boil 0 to 24 Ad BUS 1 DEVICES Displays the number of devices on Bus 1 0 to 24 Ad BUS 2 DEVICES Displays the number of devices on Bus 2 Note Thisitemisonlyavaila...

Страница 14: ...nctions The control continually monitors the sensors and displays an error message whenever a fault is found The individual outputs and relays are tested using a test sequence Test Sequence Each step...

Страница 15: ...st mode each tN4 device is individually turned on one at a time The control tests each zone for up to 5 minutes of no button activity Use this feature to purge air out of each zone and assist in troub...

Страница 16: ...at to the building as the outdoor temperature drops The rate at which the water temperature is changed is defined by the characterized heating curve Characterized Heating Curves A characterized heatin...

Страница 17: ...The amount of natural convection is dependant on the supply water temperature to the heating element and the room air temperature Radiator 5 Terminal type 5 is a radiator terminal unit has a large hea...

Страница 18: ...00 F 93 C 140 F 60 C Radiator 5 160 F 71 C 180 F 82 C 140 F 60 C Baseboard 6 150 F 76 C 170 F 77 C 140 F 60 C Boiler Indoor Design Theboilerindoordesigntemperatureistheindoortemperature the heating de...

Страница 19: ...ated by tN4 thermostats connected to this bus The boiler water temperature target will be determined based upon boiler outdoor reset and indoor feedback from the tN4 thermostats Mix Temperature Zones...

Страница 20: ...odulating boiler to go through the ignition sequence the boiler contact may not be required on all modulating boilers A 0 10 V dc analog signal is used to modulate the boiler firing rate from the Mini...

Страница 21: ...ust menu To calculate the Maximum Modulation use the following formula For 0 10 V dc Maximum Modulation 0 V dc Boiler s Maximum Input Signal x 100 0 10 V dc Example A boiler s input signal range is 2...

Страница 22: ...without a boiler sensor and prevent the control from displaying an error message set the boiler sensor DIP switch to Return and power up the control without the boiler sensor connected The control op...

Страница 23: ...x 1 and the Mix 2 Minimum settings in the Adjust menu Mix 1 and Mix 2 Maximum The Mix 1 Maximum and Mix 2 Maximum set the highest water temperature that the control is allowed to use as a mix target t...

Страница 24: ...W Pump Primary Pump Mode 4 OFF DHW Pump Primary Pump DHW MODE 2 DHW in Parallel with Priority When a DHW Demand is present the DHW Pump contact closes The primary pump P1 can operate when a boiler dem...

Страница 25: ...sfy the requirements of a setpoint load in addition to a space heating load and a DHW load A setpoint load overrides the current outdoor reset temperature and WWSD setting in order to provide heat to...

Страница 26: ...p P1 can operate when a boiler demand is present If the boiler is unabletomaintaintheboilertargettemperature spaceheating zones are shut off sequentially using tN4 communication in order to provide pr...

Страница 27: ...P1 is switched on only when there is a Mix 1 Demand and that zone s thermostat has H1 Pump set to On Variable Speed Pump The variable speed injection pump output operates only when there is a Mix 1 D...

Страница 28: ...aller access level available in MISC menu When an error message is present it is available as an item in the VIEW menu Device is attempting to show supply temperature but cannot because of sensor prob...

Страница 29: ...ix 1 bus Check the tN4 C and R wires for each tN4 device Check the polarity of the C and R wires Check for loose or broken wires BUS 1 DEVICE LOST Communication is lost to tN4 device AA on the Mix 1 b...

Страница 30: ...e to a short circuit the control failed to read the boiler sensor When there is a call for heat the control no longer controls the boiler s Instead the control provides a boiler enable to the boiler s...

Страница 31: ...rotor pumps Read E 021 and check pump type Fuse is blown Determine if pump is jammed or seized Replace fuse Display is not on No voltage to control Check breaker panel or disconnect Check voltage usin...

Страница 32: ...rranty does not cover the cost of the parts or labor to remove or transport the defective Product or to reinstall the repaired or replacement Product all such costs and expenses being subject to Purch...

Отзывы: