Minimum Modulation

The minimum modulation defines the minimum output 
signal from the control to the boiler burner. It is based on 
a percentage of the control’s output signal range.

The Minimum Modulation default setting is 0%.

For boilers with electronic operators, the boiler’s input signal 
range may not match the output signal range of the 422 
control. The Minimum Modulation setting limits the control 
output range in order to match the boiler’s input range. 

• 

• 

Locate the Minimum Modulation setting in the Adjust 
menu.

To calculate the Minimum Modulation, use the following 
formula:

For 0-10 V (dc):

Minimum Modulation = 
 

0 V (dc) - Boiler’s Minimum Input Signal x 100%

 0-10 

(dc)

Example:

A boiler requires a 1.8 V (dc) signal to fire the boiler at 
low fire. The boiler can be modulated to 10 V (dc) where 
it reaches high fire.
This means the boiler’s input signal range is 1.8 to 
10 V (dc). The 422 control has an output signal range of 
0-10 V (dc).
To make the two signal ranges the same, the Minimum 
Modulation required is:

Minimum Modulation = 0 V-1.8 V x 100% = 18%

 0 

V-10 

V

Maximum Modulation

The maximum modulation defines the maximum output 
signal from the control to the boiler burner. It is based on 
a percentage of the control’s output signal range.

The Maximum Modulation default setting is 100%.

For boilers with electronic operators, the boiler’s input signal 
range may not match the output signal range of the 422 
control. The Maximum Modulation setting limits the control 
output range in order to match the boiler’s input range.

• 

• 

Locate the Maximum Modulation setting in the Adjust 
menu.

To calculate the Maximum Modulation, use the following 
formula:

For 0-10 V (dc):

Maximum Modulation = 
 

0 V (dc) – Boiler’s Maximum Input Signal x 100%

 0-10 

(dc)

Example:

A boiler’s input signal range is 2-9 V (dc). The 422 control 
has an output signal range of 0-10 V (dc).

To make the two signal ranges the same, the Maximum 
Modulation required is:

Maximum Modulation = 0 V-9 V x 100% = 90%
 0 

V-10 

V

1.8 V (dc)

10 V (dc)

Control Rang

e

Boiler Rang

e

0 Vdc

18%

In some cases, multiple boilers may be required. In these 
cases, the 422 allows for a connection to a tekmar Boiler 
Control 264, 265, or 268. The 422 uses the modulating 
output to provide a 0-10 V (dc) signal to the external input 
terminals on the Boiler Control. The 422 controls the Boiler 
Control target temperature by changing the voltage signal. 
The Boiler Control responds to the boiler target by staging 
the multiple boilers.

The following table can be used to convert a 0-10 V (dc) 
signal to a boiler target temperature:

tekmar Stager Operation 

Section D

To use the tekmar Staging operation, the following DIP 
switch settings are required:

1. 

Set the 422 Off / tekmar Stager DIP switch to tekmar 
Stager.

2. 

Set the 422 Boil Sup / Ret DIP switch to Sup.

3. 

Set the 422 Boil On-Off / Mod DIP switch to Mod.

The 422 boiler sensor must be located on the supply pipe 
leading from the boilers. On the Boiler Control 264, 265, 
or 268, the External Input / Stand Alone DIP switch must 
be set to External Input. Any domestic hot water (DHW) 
demands or setpoint demands in the system must connect 
to the 422 in order to allow for DHW or setpoint priority.

10 V (dc)

Control

Rang

e

Boiler

Rang

e

0 Vdc

0 V (dc)  

2.0 V (dc)

20%

90%

Voltage (dc)

0

1

2

3

4

5

6

7

8

9

10

Boiler Target

Off

50°F 

(10°C)

68°F 

(20°C)

86°F 

(30°C)

103°F 

(40°C)

121°F 

(50°C)

139°F 

(60°C)

157°F 

(70°C)

174°F 

(80°C)

192°F 

(90°C)

210°F 

(99°C)

Содержание Universal Reset Module 422

Страница 1: ...er temperature to provide Domestic Hot Water or Setpoint operations The 422 can operate two outdoor reset water temperatures either one boiler water temperature and a single mix water temperature or t...

Страница 2: ...witchtolockandunlocktheAccess Level of the 422 and all connected tN4 devices including tN4 thermostats For details see Access Levels Once locked the access level in all devices cannot be viewed or cha...

Страница 3: ...r Off Flushing The Off Flushing DIP switch selects whether the control operates a Flushing feature Heating systems that use potable water require periodic flushing to prevent the water from stagnating...

Страница 4: ...Displays when a mix 2 demand is present DHW DEMAND Displays when a DHW demand is present SETPOINT DEMAND Displays when a Setpoint demand is present DEVICE OUTPUT SCALE Displays output of the modulati...

Страница 5: ...be selected The abbreviated name of the selected item displays in the Item field of the LCD display To view the next available item press and release the Item button To view the previous item hold do...

Страница 6: ...Current Mix 2 supply water temperature as measured by the Mix 2 supply sensor Note This item is only available when the tN4 DIP switch is set to Mix 2 35 to 230 F 1 5 to 110 0 C Ad MIX 2 TARGET SECTIO...

Страница 7: ...r Note This item is only available when the Boiler Sensor Sup Ret DIP switch is set to Ret 0 100 Ad BOILER MODULATION SECTION C Current percent modulation of the boiler s burner Note This item is only...

Страница 8: ...inal units that are being used in Mix 1 zones 40 to 100 F 4 5 to 38 0 C Default 70 F 21 0 C Ad MIX 1 INDOOR SECTION B The design indoor air temperature used in the heat loss calculation for Mix 1 zone...

Страница 9: ...on the typical coldest day of the year Note This item is only available when the tN4 DIP switch is set to Mix 2 OFF 40 to 150 F OFF 4 5 to 65 5 C Default OFF Ad MIX 2 MINIMUM SECTION G The minimum all...

Страница 10: ...et temperature Note This item is only available when the Boiler Sensor Sup Ret DIP switch is set to Sup and the tekmar stager DIP switch is set to OFF 0 00 to 3 00 min Default 0 10 min Ad FIRE DELAY S...

Страница 11: ...lel no priority 2 parallel priority 3 pri sec no priority 4 pri sec priority Default 1 InS Ad DHW MODE SECTION H Selects the DHW mode of operation This determines the operation of the primary pump in...

Страница 12: ...uring the Sleep and Unoccupied periods Note This item is only available when Setpoint Mode is set 1 through 4 and a network setback schedule is selected 40 to 100 F OFF 4 5 to 38 0 C OFF Default 70 F...

Страница 13: ...henthetN4Boil Mix2 DIP switch is set to Boil 0 to 24 Ad BUS 1 DEVICES Displays the number of devices on Bus 1 0 to 24 Ad BUS 2 DEVICES Displays the number of devices on Bus 2 Note Thisitemisonlyavaila...

Страница 14: ...nctions The control continually monitors the sensors and displays an error message whenever a fault is found The individual outputs and relays are tested using a test sequence Test Sequence Each step...

Страница 15: ...st mode each tN4 device is individually turned on one at a time The control tests each zone for up to 5 minutes of no button activity Use this feature to purge air out of each zone and assist in troub...

Страница 16: ...at to the building as the outdoor temperature drops The rate at which the water temperature is changed is defined by the characterized heating curve Characterized Heating Curves A characterized heatin...

Страница 17: ...The amount of natural convection is dependant on the supply water temperature to the heating element and the room air temperature Radiator 5 Terminal type 5 is a radiator terminal unit has a large hea...

Страница 18: ...00 F 93 C 140 F 60 C Radiator 5 160 F 71 C 180 F 82 C 140 F 60 C Baseboard 6 150 F 76 C 170 F 77 C 140 F 60 C Boiler Indoor Design Theboilerindoordesigntemperatureistheindoortemperature the heating de...

Страница 19: ...ated by tN4 thermostats connected to this bus The boiler water temperature target will be determined based upon boiler outdoor reset and indoor feedback from the tN4 thermostats Mix Temperature Zones...

Страница 20: ...odulating boiler to go through the ignition sequence the boiler contact may not be required on all modulating boilers A 0 10 V dc analog signal is used to modulate the boiler firing rate from the Mini...

Страница 21: ...ust menu To calculate the Maximum Modulation use the following formula For 0 10 V dc Maximum Modulation 0 V dc Boiler s Maximum Input Signal x 100 0 10 V dc Example A boiler s input signal range is 2...

Страница 22: ...without a boiler sensor and prevent the control from displaying an error message set the boiler sensor DIP switch to Return and power up the control without the boiler sensor connected The control op...

Страница 23: ...x 1 and the Mix 2 Minimum settings in the Adjust menu Mix 1 and Mix 2 Maximum The Mix 1 Maximum and Mix 2 Maximum set the highest water temperature that the control is allowed to use as a mix target t...

Страница 24: ...W Pump Primary Pump Mode 4 OFF DHW Pump Primary Pump DHW MODE 2 DHW in Parallel with Priority When a DHW Demand is present the DHW Pump contact closes The primary pump P1 can operate when a boiler dem...

Страница 25: ...sfy the requirements of a setpoint load in addition to a space heating load and a DHW load A setpoint load overrides the current outdoor reset temperature and WWSD setting in order to provide heat to...

Страница 26: ...p P1 can operate when a boiler demand is present If the boiler is unabletomaintaintheboilertargettemperature spaceheating zones are shut off sequentially using tN4 communication in order to provide pr...

Страница 27: ...P1 is switched on only when there is a Mix 1 Demand and that zone s thermostat has H1 Pump set to On Variable Speed Pump The variable speed injection pump output operates only when there is a Mix 1 D...

Страница 28: ...aller access level available in MISC menu When an error message is present it is available as an item in the VIEW menu Device is attempting to show supply temperature but cannot because of sensor prob...

Страница 29: ...ix 1 bus Check the tN4 C and R wires for each tN4 device Check the polarity of the C and R wires Check for loose or broken wires BUS 1 DEVICE LOST Communication is lost to tN4 device AA on the Mix 1 b...

Страница 30: ...e to a short circuit the control failed to read the boiler sensor When there is a call for heat the control no longer controls the boiler s Instead the control provides a boiler enable to the boiler s...

Страница 31: ...rotor pumps Read E 021 and check pump type Fuse is blown Determine if pump is jammed or seized Replace fuse Display is not on No voltage to control Check breaker panel or disconnect Check voltage usin...

Страница 32: ...rranty does not cover the cost of the parts or labor to remove or transport the defective Product or to reinstall the repaired or replacement Product all such costs and expenses being subject to Purch...

Отзывы: