background image

© 2013 

 400_D - 09/13

24 of 32

 Setpoint Operation 

Section D

A Setpoint Call is required in order for the control to provide 
heat to a setpoint load, such as a spa, pool, or snowmelt 
load. This can be done in two ways:

Contact Closure

 --------------------------------

 --------------------------------

A dry contact or 24 V (ac) signal is applied across the 
Setpoint Call terminals on the 400.

tekmarNet

®

 Setpoint Control with Sensor

 

-------

 

-------

A Setpoint Call is provided through the tekmarNet

®

 

system. This can be done through the tN4 Expansion 
terminals with a setpoint device such as a Setpoint 
Control 161.
Once the control registers a Setpoint Call, it will display 
the “Setp” icon under Calls in the display.

Note:

 Setpoint operation has a fixed priority of on.

Setpoint Operation

 -----------------------------

 -----------------------------

The control can operate to satisfy the requirements of a 
setpoint load in addition to a space heating load and a 
DHW load. A setpoint load overrides the current outdoor 
reset temperature and WWSD setting in order to provide 
heat to the setpoint load.

Setpoint Priority

Boiler System

Pump

Setpoint

Pump

Zone

Valve

Setpoint

ON

OFF

OFF

When the control receives a Setpoint Call:

All Boiler zones are turned off.
The boiler will operate to maintain the Setpoint tem-
perature as set in the Adjust menu, or as set on the 
tekmarNet

®

 Setpoint control if one is being used.

         Setp

Calls

It is assumed that the Setpoint pump will provide adequate 
flow through the heat exchanger and the boiler.
Setpoint calls will also be responded to when the system 
is in 

Away

, which can be set using a 479 User Switch.

Setpoint Priority Override

 ----------------------

 ----------------------

To prevent the building from cooling off too much or 
the possibility of a potential freeze up during setpoint 
priority, the control attempts to limit the amount of time 
for setpoint priority.
As the outdoor air temperature becomes colder, the length 
of time the control provides setpoint priority is reduced. 
Once the allowed time for priority has elapsed, the control 
will check the space heating target. 

If there is a space heating target, the boiler operates at 
that target for 15 minutes. 
If after 15 minutes there is still a Setpoint Call, the con-
trol will, shut off all boiler heating zones and target the 
Setpoint temperature.
Note: It is possible to disable Setpoint Priority by using 
a tekmarNet

®

 Setpoint control and turning the priority 

to Off in the Setpoint control. 


 Boiler Operation 

Section E

The 400 is able to operate a single 1-stage or 2-stage on-
off boiler or a single modulating boiler as a heat source. 
For proper operation of the boiler, the 400 must be the only 
control that determines when the boiler is to fire.

*Important note:

 The operating control in the boiler, also 

known as an aquastat, remains in the burner circuit and acts 
as a secondary upper limit on the boiler temperature. The 
boiler operator temperature setting can be adjusted above 
210°F, which is the fixed Boiler Maximum on the 400.

Boiler Target Temperature

 ----------------------

 ----------------------

The boiler target temperature is the temperature which 
the control is trying to operate the boiler at. There are 
four items that determine the boiler target temperature:

Boiler Call
DHW Call
Setpoint Call 

If the control receives more than one call for heat at the 
same time, it will operate the boiler at the highest of the 
four calls.



The control displays the temperature that it is currently 
trying to maintain as the boiler supply temperature in the 
View menu. If the control does not presently have a call for 
heat, it does not show a boiler target temperature. Instead, 
‘– – –’ is displayed on the LCD.

Boiler Minimum

 --------------------------------

 --------------------------------

When operating non-condensing boilers, it is important 
to prevent cool water from returning to the boiler. Cold 
return temperatures create flue gas condensation, which 
if left too long, can severely damage the boiler.
The 400 protects the boiler through the Boiler Minimum 
setting. The boiler minimum is the lowest temperature that 
the control is allowed to use as a boiler target temperature.  
If the boiler is operating at the boiler minimum temperature, 
the “MIN” segment is turned on in the display when viewing 
either the boiler supply temperature or the boiler target 
temperature.

Содержание tN2 house control 400

Страница 1: ...tion It can be used in applications ranging from a single zone of baseboard with an on off boiler to multiple radiant floor zones with a modulating condensing boiler This control regulates one space h...

Страница 2: ...tallers responsibility to ensure that this control is safely installed according to all applicable codes and standards Improper installation and operation of this control could result in damage to the...

Страница 3: ...te toutes les exigences du R glement sur le mat riel brouilleur du Canada Radio Frequency Interference Preparation Tools Required tekmar or jeweller screwdriver Phillips head screwdriver Needle nose P...

Страница 4: ...if applicable Setpoint Device if applicable Pull three conductor 18 AWG LVT cable for the following equipment tekmarNet 4 Accessories User Switch Timer and Wiring Center Low Voltage Wiring Rough In Wi...

Страница 5: ...e L N Figure 3 Connect Line Voltage Hot Strip wires 1 2 inch 13 mm Installed wires are not removable 12 18 AWG DHW Pump Pump Power L 400 Boil System Pump DHW Pump Power Source L N Boil System Pump Fig...

Страница 6: ...fasten it to the electrical junction box with 2 10 screws as shown in Figure 5 Install The Enclosure Figure 5 Domestic Hot Water DHW or Setpoint Call When the control receives a DHW Call or Setpoint...

Страница 7: ...ectly onto a wall or a 2 x 4 electrical box When the 070 is wall mounted the wiring should enter through the back or bottom of the enclosure Do not mount the 070 with the conduit knockout facing upwar...

Страница 8: ...y to the pipe using the cable tie provided Insulation should be placed around the sensor to reduce the effect of air currents on the sensor measurement Immersion Well If a Universal Sensor is mounted...

Страница 9: ...asure between 21 6 to 26 4 V ac If the voltage is below this range measure the line voltage side of the transformer The voltage should measure between 103 5 to 126 5 V ac Testing the Thermostats If th...

Страница 10: ...by pressing the Item button once the boiler stage 2 turns on Using an electrical meter measure for continuity over the boiler stage 2 terminals Testing the Boiler Modulating Output This test applies f...

Страница 11: ...ower H8005B Made in Canada Use at least 167 F 75 C conductors Stage 2 Stage 1 Description The House Control 400 operates an On Off boiler with indirect Domestic Hot Water The boiler is operated using...

Страница 12: ...2 18 AWG Expansion tN4 Boil C tN4 Modulating Boiler 1 R C L N 313 red black black Menu House Control 400 Item Com Boil Out DHW Vlv C Vlv C Vlv C Zone 3 Zone 1 Zone 2 Zone 4 Vlv C Com Zone 1 Zone 2 Zon...

Страница 13: ...er UNOCCUPIED Indicates that a User Switch or Timer has put the system into UnOccupied BOILER Indicates that the boiler should be heating MAX MIN MIN MAX Displays when an operating temperature reaches...

Страница 14: ...ng Select the appropriate menu using the Menu button Select the item using the Item button Use the Up or Down button to make the adjustment Default Item When navigating menus the display reverts back...

Страница 15: ...N SECTION E Current percent modulation of the boiler s burner The boiler modulation increases when the boiler supply is less than the boiler target The boiler modulation decreases when the boiler supp...

Страница 16: ...the year Recommendations High mass radiant floor 120 F 50 C Low mass radiant floor 140 F 60 C Fancoil or air handling unit 190 F 90 C Copper fin tube convector 180 F 80 C Radiators 160 F 70 C Low prof...

Страница 17: ...y available when a schedule or User Switch is present on the system Off 1 2 3 4 5 Default 2 Installer DHW MODE SECTION C Selects the DHW mode of operation The mode determines the zone and boiler syste...

Страница 18: ...Default 180 F 82 0 C Installer SETPOINT SECTION D The minimum boiler target temperature when a Setpoint Call is present ADJUST F or C Default F Installer User UNITS Selects units for temperature displ...

Страница 19: ...NITOR hr Boil System Pumps 0 to 9999 Hours Default 0 hr RUN TIME BOIL SYSTEM PUMP The total running time of the Boil System Pump since this item was last cleared Press and hold the Up and Down buttons...

Страница 20: ...access and shows the fewest possible items When set to USER all thermostats are locked and the number of thermostat settings available are reduced OFF SEL Default Off FACTORY DEFAULTS Loads the factor...

Страница 21: ...ler target is determined by the control using the boiler heating curve boiler minimum boiler design and outdoor design settings together with indoor temperature feedback from the thermostats The heati...

Страница 22: ...DHW MODE 1 DHW in Parallel no Priority When a DHW Call is present the DHW pump is activated The boiler system pump does not turn on but may operate based on either a Boiler or Setpoint Call It is assu...

Страница 23: ...nt of time for DHW priority during cold weather During warm weather the DHW priority is 120 minutes During cold weather the DHW priority is 15 minutes Once the allowed time for priority has elapsed th...

Страница 24: ...re is a space heating target the boiler operates at that target for 15 minutes If after 15 minutes there is still a Setpoint Call the con trol will shut off all boiler heating zones and target the Set...

Страница 25: ...st operate before the internal boiler control allows an external signal to operate the burner After the Modulation Delay has elapsed the control uses PID logic to change the boiler firing rate signal...

Страница 26: ...boiler based on the heating load As the load increases the differential will decrease to minimize temperature swings As the load decreases the differential will increase to prevent short cycling This...

Страница 27: ...ssary boiler operation the control goes into Warm Weather Shut Down WWSD when the outdoor temperature rises above the WWSD temperature set in the Adjust menu Energy Saving Features Section G Further S...

Страница 28: ...for heat the control no longer controls the boiler Instead the control provides a boiler enable and the boiler operates on its aquastat limit until the sensor is repaired The control will not operate...

Страница 29: ...t 4 expansion terminals The 400 is a Master Device and no other tekmarNet reset controls can be added to the tekmarNet 4 expansion terminals If one has been added remove it from the system DEVICE ERRO...

Страница 30: ...the control is aware that the DHW tank requires heat DHW tank reading Ensure the DHW tank temperature is accurate and replace if necessary Burner symbol on LCD If the burner symbol is on the LCD there...

Страница 31: ...Setting OUTDOOR DESIGN BOILER TYPE BOILER DESIGN BOILER MINIMUM BOILER MOTOR MINIMUM MODULATION MODULATION DELAY WWSD OCCUPIED Item Setting WWSD UNOCCUPIED DHW MODE DHW EXCHANGE DHW OCCUPIED DHW UNOCC...

Страница 32: ...r misuse or has been damaged by modifications alterations or attachments made subsequent to purchase which have not been authorized by tekmar or if the Product was not installed in compliance with tek...

Отзывы: