background image

© 2008 

 W 162 - 12/08 

6 of 8 

tN4

C

R Com S1

1

2

3

4

5

tN4

C

R

W

Zone Manager

Wiring the Setpoint Control

 Power 24 V (ac) 

Terminals 2, 3

Wire 24 V (ac) to terminals C and R.

If a Zone Manager is used:

• 

Connect C on the setpoint control to C on the proper 
zone of the Zone Manager. 

• 

Connect R on the setpoint control to R on the proper 
zone of the Zone Manager.

If a 24 V (ac) transformer is used: 

• 

Connect C on the setpoint control to C on the 
transformer. 

• 

Connect R on the setpoint control to R on the 
transformer.

 tN4 Communication 

Terminals 1, 2

Wire the tN4 communication to terminals tN4 and C.

If a Zone Manager is used:

• 

Connect tN4 on the setpoint control to the tN4 on the 
proper zone of the Zone Manager. The C terminal is 
already connected.

If a Zone Manager is not used:

• 

Connect tN4 on the setpoint control to the tN4 terminal 
on another tN4 device on the same tN4 bus. 

• 

Connect C on the setpoint control to the C terminal on 
another tN4 device on the same tN4 bus.

Setpoint Control

Zone Manager

tN4

C

R Com S1

1

2

3

4

5

tN4

C

R

W

 Relay 1 and Relay 2 

Terminals 6, 7, 8

Relay 1 is used to switch the heat or cooling.

Relay 2 is used to switch the recirculation pump.

If a Zone Manager is used:

• 

Connect Relay 1 to W on the proper zone on the Zone 
Manager.

• 

Connect Relay 2 to W on the proper zone on the Zone 
Manager.

If a Zone Manger is not used:

• 

Determine if the jumper must be cut.

• 

When the jumper is not cut, Relay 1 and Relay 2 is 
internally powered through terminal 3.

• 

When the jumper is cut, Rh   and Relay 1 and Relay 2 
are isolated switches.

Setpoint Control

Zone Manager

R

Rh R1 R2

3

6

7

8

tN4

C

R

W

Zone Manager

tN4

C

R

W

 Sensor Input 

Terminals 4, 5  

The sensor is connected to the setpoint control on terminals 
Com and S1.

• 

• 

Connect sensor to terminals S1 and Com.

Do not apply power

 to terminals S1 and Com,

 

permanent damage to the sensors and / or setpoint 
control will result!

Universal 

Sensor

Setpoint Control

tN4

C

R Com S1

1

2

3

4

5

Do N

o

t Apply P

o

w

er 

Setpoint Control

Содержание tekmarNet4 Setpoint Control 162

Страница 1: ...t Control 162 The 162 has two outputs one for heat or cool and the other for a recirculation pump The 162 has one sensor input Definitions 2 Rough In Wiring 2 Remove the Wiring Cover 3 Mounting the Setpoint Control 3 Wiring Symbols 3 Electrical Drawings 3 5 Wiring the Setpoint Control 6 Troubleshooting the Wiring 7 Testing the Wiring 7 Technical Data 8 Table of Contents 24 V 10 50 60 Hz 3 2 VA 24 ...

Страница 2: ...voids warranty and could result in damage to the equipment and possibly even personal injury or death Caution Choose the placement of the setpoint control early in the construction process to enable proper wiring during rough in Consider the following Interior Wall Keep dry Avoid potential leakage onto the control RH 80 to 88 F 31 C down to 50 from 104 to 122 F 40 to 50 C Non condensing environmen...

Страница 3: ...l Stud Switch Box Control Base 007 Adaptor Plate Control 3 1 4 83 mm Mounted on switch box Stud 23 8 60 mm screwhole 23 8 60 mm screwhole Control Control Base Wall Mounted on wallboard Dry contact switch Operates a device Do not apply power to these terminals Serious control damage will result tekmarNet 4 Wiring Symbols Electrical Drawings The electrical drawing examples on the following pages sho...

Страница 4: ...s Class B Canadian ICES FCC Part 15 Cut jumper to isolate relay For product instructions see brochure Use at least 194 F 90 C conductors 162 tN4 C R W Zone Manager tN4 C R W Heat Zone Recirculation Zone Recirculation Zone Pump Heat Zone Pump Sensor Electrical Application 162 E1 Description Setpoint Control used with tN4 System Zone Managers ...

Страница 5: ... instructions see brochure Use at least 194 F 90 C conductors R C Relay 003 Relay 003 External Class 2 Transformer 24 V ac P2 P1 162 3 4 5 6 2 1 8 7 3 4 5 6 2 1 8 7 L N Sensor Electrical Application 162 E2 Description Setpoint Control used as a stand alone device Relay 1 is used to cycle a pump to provide heat Relay 2 is used to operate a recirculation pump Legend P1 Pump cycled for heating P2 Rec...

Страница 6: ...etpoint control to the C terminal on another tN4 device on the same tN4 bus Setpoint Control Zone Manager tN4 C R Com S1 1 2 3 4 5 tN4 C R W Relay 1 and Relay 2 Terminals 6 7 8 Relay 1 is used to switch the heat or cooling Relay 2 is used to switch the recirculation pump If a Zone Manager is used Connect Relay 1 to W on the proper zone on the Zone Manager Connect Relay 2 to W on the proper zone on...

Страница 7: ...elay s symbol is not displayed in the LCD there should be no continuity 4 Reconnect the wires to the relay 5 Install the front cover on the setpoint control 162 LCD Display Relay 1 Testing the Sensor To test the sensor the actual temperature at the sensor location must be measured Use a good quality digital thermometer with a surface temperature probe for ease of use and accuracy Where a digital t...

Страница 8: ...ry II Pollution Degree 2 Power Supply 24V ac 10 50 60 Hz 3 2 VA NEC CEC Class 2 Relays 24V ac 2 A Sensors NTC thermistor 10 k 77 F 25 C 0 2 C ß 3892 Included Universal Sensor 071 Optional tekmar type 070 071 072 073 076 077 078 079 082 083 084 The installer must ensure that this control and its wiring are isolated and or shielded from strong sources of electromagnetic noise Conversely this Class B...

Отзывы: