Tekmar tekmarNet 553 Скачать руководство пользователя страница 35

© 2013 

 553_D - 04/13

35 of 48

A Watts Water Technologies Company

Fan Operation

Section G

The fan operates together with the air heating or cooling systems. The user can also 
select to operate the fan manually by pressing the Fan button. This allows the user to 
choose between Auto and On. “Auto” allows the fan to operate together with heating or 
cooling but normally the fan is off. “On” forces the fan to operate continuously.

Ventilation Fan

 ------------------------------------------------------

 ------------------------------------------------------

In order to provide ventilation to the building, the fan can also operate for additional 
time beyond what is required for the heating and cooling systems. Ventilation allows the 
user to select the fan to operate for a minimum percentage out of each hour. Options 
are 10 to 90%, in 10% (6 minutes per hour) increments, as well as Auto and On. This 
is available when the Vent Mode setting in the Setup menu is set to On.

Once Ventilation is set to On, the Fan minimum run time percentage during the   and   
events can be set so that the fan can operate on a schedule and/or together with scenes.

Fan Post Purge

 ------------------------------------------------------

 ------------------------------------------------------

The fan relay includes a post purge feature that operates the fan after the heating or 
cooling system has shut off. When a duct temperature sensor is installed the length 
of post purge is based on the air duct temperature and the Heat Purge or Cool Purge 
temperature settings. When there is no duct temperature sensor installed, the length 
of post purge is based upon the Heat Purge and Cool Purge time settings.

Relative Humidity Operation

Section H

Relative Humidity (RH) is controlled by maintaining the Minimum Humidity using 
humidification and by maintaining Maximum Humidity using dehumidification. The RH 
is maintained within a 5% differential. The differential is applied above the minimum 
setpoint, and applied below the maximum setpoint.

To avoid condensation on windows, the minimum relative humidity setting can be 
changed according to the following outdoor temperatures.

Outdoor Temperature

-10°F (-23°C) 0°F (-18°C)

10°F (-12°C)

20°F (-7°C)

30°F (-1°C)

Suggested RH Min

20%

25%

30%

35%

35%

RH is affected by changes in the ambient air temperature. When using a programmable 
schedule, the thermostat calculates the relative humidity setpoint with respect to the Set 
Heat Room   setting when in heat mode, the Set Cool Room   when in cool mode, 
and the average between Set Heat Room   and Set Cool Room   when in auto mode. 
This may result in changes in displayed RH when the mode is changed.

When the mode is set to off, the humidification and dehumidification systems do not 
operate.

Содержание tekmarNet 553

Страница 1: ...res Programmable Schedule Zone Synchronization Zone Post Purge Warm Weather Shut Down Cooling Interlock Auto Heating Cycle Temporary Hold Away Scene Key Additional Features 2 Auxiliary Sensor Inputs t...

Страница 2: ...r Interface 8 Home Screen 8 Symbols Description 8 Programmable Settings 9 Programming Menus 9 Set Temp Menu 10 13 Time Menu 14 Schedule Menu 15 16 Display Menu 16 17 Scenes Menu 17 Monitor Menu 18 21...

Страница 3: ...ring viewing and adjusting the display screen Approximately 5 feet 1 5 m off the finished floor The maximum length of wire is 500 feet 150 m Strip wire to 3 8 10 mm for all terminal connections Use st...

Страница 4: ...e Manager This allows easy wiring for retrofit applications Application specific wiring diagrams are provided in the 553_A brochure Wall Stud Thermostat Front Thermostat Base If a gang box is not used...

Страница 5: ...fault with the previously tried zone on the House Control Wiring Center or Zone Manager If the thermostat display continues to be off or is cycling on and off there may be a fault on the thermostat If...

Страница 6: ...nventional Rc to ACC heat pump Y HEAT ON Rc to Y Y COOL ON Rc to Y W2 HEAT ON Rc to ACC HUMIDIFY ON Rc to ACC W HEAT Rh to W DEHUMIDIFY ON Rc to ACC HUMIDIFY ON Rc to ACC heat and cool Rc to Y two sta...

Страница 7: ...e access level Set to Unlock during the installation process Note tekmarNet system controls include a Global Lock that locks all connected thermostats Set the tekmarNet system control to unlock to all...

Страница 8: ...displayed setting SCENE AWAY Operating at Away temperature TEMPORARY HOLD Holds temperature for 3 6 9 or 12 hours WWSD Warm Weather Shut Down COOL Cooling system is on MIN or MAX Reached the room min...

Страница 9: ...wards counterclockwise in above illustration through the menus Touch ENTER to enter a menu Setting Items Touch or arrow to adjust the setting if required Touch NEXT ITEM to advance to the next item wi...

Страница 10: ...ns Scenes is set to Away All or Guest Default 62 F 16 5 C HEAT MINIMUM ROOM LIMIT Set the minimum room heating limit Access Level Installer Range 40 to 95 F 4 5 to 35 0 C Conditions Always available D...

Страница 11: ...during the event Access Level Installer Range CTRL control 40 to 100 F 4 5 to 38 0 C OFF Conditions An outdoor sensor must be available and Schedules are in use or Scenes is set to All or Guest Defau...

Страница 12: ...HP or AC Default 100 F 38 0 C FLOOR MINIMUM Set the floor heating temperature while in the event Access Level Installer Range OFF 40 to 122 F 4 5 to 50 0 C Conditions Sensor 1 or 2 is set to Floor an...

Страница 13: ...s 6 minutes per hour Access Level Installer User Range Auto 10 to 90 ON Conditions G O RELAY set to FAN or ACC Relay set to FAN and Schedules used or Scenes set to Guest or All 10 to 90 available if V...

Страница 14: ...ions Always available Default JANUARY DAY OF MONTH Select the day of the current month Access Level Installer User Range 1 to 31 Conditions Always available Default 1 YEAR Select the current year Acce...

Страница 15: ...AM when Event Day is 4 EVENT 3 The third programmable schedule time period of the day The temperature settings are used during this time period SuMoTuWeThFrSa Access Level Installer User Range 12 00 A...

Страница 16: ...the number of temperatures per day Access Level Installer User Range 2 or 4 Conditions Schedule setting is set to Zone or Master 1 2 3 4 Default 2 24 HOUR 7 DAY Access Level Installer User Range 24 h...

Страница 17: ...t OFF LOCAL NETWORK GROUP Select if scenes and time clock are shared when connected to a tekmarNet system OFF Send and receive messages ON Receive messages only Access Level Installer Range OFF or ON...

Страница 18: ...stat and all air group member thermostats Access Level Installer Range 58 to 212 F 50 0 to 100 0 C Conditions Setup menu setting Air Group Master must be set to 1 through 16 Default Not applicable W S...

Страница 19: ...ns An outdoor temperature is available Default Not applicable OUTDOOR LOW The lowest recorded outdoor air temperature measurement Touch the number and the ENTER key to reset Access Level Installer Use...

Страница 20: ...hours HEAT Y HOURS The total number of hours the heat pump has been in heating operation Touch the number and the ENTER key to reset Access Level Installer User Range 0000 to 9999 hours Conditions Y...

Страница 21: ...of hours the humidifier has been operated Touch the number and the ENTER key to reset Access Level Installer User Range 0000 to 9999 hours Conditions Humidify Mode is set to HM1 2 3 Default 0000 hour...

Страница 22: ...ing could occur Baseload On Baseload heating is on even though the room temperature is satisfied Reduces heat up time when the sun sets in the evening Hydronic Heat Off The air group master is in cool...

Страница 23: ...taller Range 5 to 5 F 3 0 to 3 0 C Conditions Always available Default 0 F 0 0 C OFFSET HUMIDITY Manual offset correction of the room humidity Access Level Installer Range 10 to 10 Conditions Always a...

Страница 24: ...HUMIDITY SENSOR Select whether the built in humidity sensor is on or off Access Level Installer Range OFF or On Conditions Always available Default On Y RELAY Select the cooling equipment the Y relay...

Страница 25: ...tem control is connected and W TERM is set to HRF1 or HRF2 or connected to a tN2 Wiring Center Default OFF ACCESSORY RELAY Select the equipment the accessory relay operates W2 Second stage heat HUM Hu...

Страница 26: ...r must be operating before the W2 can turn on AUTO Automatic PID staging OVR W2 only turns on when Mode is set to EMER Available only when Y Relay is set to HP Access Level Installer Range AUTO 5 to 1...

Страница 27: ...xcessive heat cool switchovers Access Level Installer Range 10 to 180 minutes Conditions Y RELAY is set to AC or HP Default 30 minutes BALANCE POINT SCHEDULE Select if the heat pump balance point shou...

Страница 28: ...rol Default SYNC Y DURING W2 Select whether the heat pump compressor can operate when W2 heat is on When Mode is set to EMER emergency the heat pump compressor Y is always shut off Access Level Instal...

Страница 29: ...priority Access Level Installer Range HEAT or COOL Conditions Air Group Master is set to 1 to 16 Default COOL G O RELAY Select the operation of the G O relay Access Level Installer Range FAN or OFF Y...

Страница 30: ...set to COIL and W1 or W2 TERMINAL is set to COIL or FURN Default 0 30 minutes HEAT COIL MINIMUM Select the minimum coil temperature before operating the fan for heating Access Level Installer Range O...

Страница 31: ...rature is satisfied When the air temperature is below the Set Heat Room temperature the thermostat operates the heating system to maintain the Set Heat Room temperature The floor is never heated above...

Страница 32: ...h this occurs is known as the balance point When the outdoor temperature falls below the balance point the heat pump is shut off and the backup supplemental heat source is operated to heat the buildin...

Страница 33: ...Shut Down When the outdoor air temperature falls below the Cooling Cold Weather Shut Down CWSD setting on the thermostat the cooling system is shut off The first stage operates on a temperature diffe...

Страница 34: ...e mix system pump is operated If the thermostat operates a motorized or thermal motor zone valve the W1 Pump setting should be set to On If the thermostat operates a thermal motor wax actuator zone va...

Страница 35: ...off When a duct temperature sensor is installed the length of post purge is based on the air duct temperature and the Heat Purge or Cool Purge temperature settings When there is no duct temperature se...

Страница 36: ...ier Dehumidifier operates independently of the HVAC system Available in all modes except off DHM2 Coil Dehumidification A DX coil compressor is operated with the blower fan operating at its dehumidifi...

Страница 37: ...D setting This allows the air system heat pump fan coil or furnace to heat the building during mild outdoor weather and avoids heating up the radiant floor slab If the Set Heat Room temperature is adj...

Страница 38: ...et Heat Room AWAY air heating or air heating with floor sensor Floor Min air heating with floor sensor Floor Min air heating with floor sensor Set Cool Room air cooling Set Cool Room air cooling Set C...

Страница 39: ...uires the thermostat to be connected to a tekmarNet system Once the type of schedule has been selected the thermostat can support schedules that have either 2 events per day 4 events per day Schedules...

Страница 40: ...ion Scenes Away Operation Scenes All Operation Scenes Guest Operation 1 Permanent or Schedule Permanent or Schedule Permanent or Schedule Permanent 2 Scene 1 Away Away Away 3 Scene 1 Scene 1 Permanent...

Страница 41: ...ed back to scene 1 and the spare bedrooms resume operation at the temperature settings Commercial Buildings Commercial buildings are typically in use on a predictable schedule and normally the buildin...

Страница 42: ...rmostats that have errors By referring to the address documentation it simplifies the process to locate and correct error messages Access Levels Section O The thermostat Toolbox menu supports four acc...

Страница 43: ...tings in the Monitor menu SCHEDULE MENU SAVE ERROR The thermostat failed to read the Schedule menu settings from memory and has reloaded the factory default settings The thermostat continues to operat...

Страница 44: ...ust be set to measure an air or floor temperature NO HEAT RELAY There are no heat relays configured To clear the error set W TERM to HRF1 HRF2 CONV COIL FURN or OTHR or set ACC RELAY to W2 W2 SOURCE B...

Страница 45: ...procedures LOCAL HUMIDITY SENSOR ERROR The built in humidity sensor is faulty The error cannot be field repaired Contact your tekmar sales representative for repair procedures SENSOR 1 OR 2 SHORT CIRC...

Страница 46: ...e air group master to None or install an air group master on the system SCHEDULE MASTER ERROR Two thermostats on the tekmarNet system have been set to the same Schedule Master number The thermostat op...

Страница 47: ...tekmarNet system control connected to the tekmarNet system and not on this thermostat Error Messages 5 of 5 Technical Data tekmarNet Thermostat 553 Two Stage Heat One Stage Cool Fan Literature 553_A...

Страница 48: ...ar during the war ranty period This Limited Warranty does not cover the cost of the parts or labor to remove or transport the defec tive Product or to reinstall the repaired or replacement Product all...

Отзывы: