Setting
Display
STATUS INFO
Toggles between “Status Info” and the current status including
any overrides from the tekmarNet
®
system control.
System Normal
= Thermostat operating normally.
Override W
= The tekmarNet
®
system control is either
forcing the W relay on or off.
Cooling Floor
= Floor cooling is in effect.
WWSD
= Warm Weather Shut Down is in effect.
CWSD
= Cold Weather Shut Down is in effect.
Air Group Master Cool
= The air group master thermo-
stat is cooling.
Optimum Start Heat or Cool
= Heating or cooling system
starts early in order to meet setpoint at Event 1 or 3.
Floor Max
= The floor has reached its maximum tempera-
ture. Some under heating could occur.
Floor Min
= The floor is operating at its minimum tempera-
ture. Some over heating could occur.
Baseload On
= Baseload heating is on even though the
room temperature is satisfied. Reduces heat up time when
the sun sets in the evening.
Hydronic Heat Off
= The air group master is in cooling
mode and air group member thermostats’ heating is shut off.
Interlock Wait
= The thermostat is switching between heating
to cooling or from cooling to heating.
Priority Heat
= Air group members are calling for heat. Cooling
is suspended.
Access Level: Installer, User
Range: See Description
Conditions: Always available.
Default: System Normal
ADDRESS
The tekmarNet
®
address of this thermostat. To manually set
the address, use the up or down arrow buttons.
Access Level: Installer
Range: AUTO, 01 to 24,
b:01 to b:24, 1:01 to 1:24,
2:01 to 2:24, 3:01 to 3:24
Conditions: tekmarNet
®
2 or 4 detected.
Default: AUTO
SOFTWARE AND TYPE VERSION
Displays the software version and the tekmar type number.
Access Level: Installer, User, Limited, Secure
Range: 553
Conditions: Always available.
Default: 553
Toolbox Menu (2 of 3)