Press menu button until the Adjust Menu is displayed. Press item button 
to locate the desired setting.

Item Field

Range

Access

Description

Set to

ADJUST

-60 to 45°F

(-51.0 to 7.0°C)

Default = 10°F

(-12.0°C)

Installer

OUTDOOR DESIGN

Typically set to the temperature of the coldest day of 
the year. The outdoor air temperature used in the boiler 
and mixing heating curves that determine the boiler 
target and the mix target temperatures.

ADJUST

70 to 180°F

(21.0 to 82.0°C)
Default = 120°F 

(49.0°C)

Installer

MIX DESIGN

The supply water temperature required for the mix 
zones to heat the building on the typical coldest day 
of the year. Recommendations:
High mass radiant floor = 120°F (50°C)
Low mass radiant floor = 140°F (60°C)
Fancoil or air handling unit = 190°F (90°C)
Copper fin-tube convector = 180°F (80°C)
Radiators = 160°F (70°C)
Low profile baseboard = 150°F (65°C) 

ADJUST

4-20 mA,

0-10 V (dc)

FLOT,

VAR

Default = VAR

Installer

MIX TYPE 

Select the type of mixing device.
VAR = Variable speed injection pump
FLOT = Floating action motor for mixing valves
0-10 = 0 -10 V (dc) analog signal for mixing valves
4-20 = 4-20 mA analog signal for mixing valves

Note:

 0-10 and 4-20 are only available when Boiler 

Type = 1 Stage or 2 Stage.

EMS2,

EMS1,

4-20

0-10,

2STG,

1STG

Default = 1STG

Installer

BOILER TYPE

The type of boiler connected to the control.
1STG = single one-stage on-off boiler
2STG = single two-stage on-off boiler
0-10 = 0-10 V (dc) modulating boiler
4-20 = 4-20 mA modulating boiler
EMS1 = tekmar boiler staging controls
EMS2 = Viessmann modulating boilers with 
OpenTherm

Note:

 Only 1STG and 2STG are available when the 

Mix Type is set to 0-10 V (dc) or 4-20 mA.

11. 

Critical Settings

Содержание tekmarNet 2 House Control 403

Страница 1: ...Zone 4 Zone 2 Zone 1 Variable Speed 115 V ac N1 L1 G 115 V ac N2 G L2 to pump grounds to pump grounds N N L L Back of House Control 403 Boil Sys Pmp DHW Pump Variable Speed Pump Pump Power Zone 4 Zon...

Страница 2: ...4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 C Floating Action Cls Opn Sensors No Power Call Call tN4 tN4 C C Mod dc mA Boil Exp Mix Exp Setpoint DHW R C Input Power Use at least 167 F 75 C conductors Stage 2 S...

Страница 3: ...s saving energy See the Saving Indicator section WWSD WWSD Displays when the system is in Warm Weather Shut Down F C minhr sec F C HOURS MINUTES SECOND Units of measurement for current number UNOCCUPI...

Страница 4: ...water temperature required for the mix zones to heat the building on the typical coldest day of the year Recommendations High mass radiant floor 120 F 50 C Low mass radiant floor 140 F 60 C Fancoil o...

Страница 5: ...s motifs de pompe 115 V ca 115 V ca noir Zone 4 Zone 3 Zone 2 Zone 1 noir noir noir rouge Pompe du DHW Pompe du syst me de la chaudi re Zone decourant Zone 1 Zone 2 Zone 3 Zone 4 Pompe vitesse variabl...

Страница 6: ...1 Zone 2 Zone 3 Zone 4 Zone 1 Appel de point de consigne Appel de DHW Utiliser au moins des conducteurs de 167 F 75 C Expansion du m lange tN4 Expansion d bullition tN4 Chaudi re modulante Flottant a...

Страница 7: ...rtez vous la section de l indicateur d conomie WWSD WWSD S affiche lorsque le syst me s arr te cause d un sur chauffage F C minhr sec F C HEURES MINUTES SECONDE Unit s de mesure pour le nombre actuel...

Страница 8: ...requise pour les zones de m lange pour chauffer le b timent durant le jour le plus froid typique de l ann e Recommandations Sol chauffant haute masse 120 F 50 C Sol chauffant faible masse 140 F 60 C V...

Страница 9: ...ad variable Bomba DHW Potencia de la zona Potencia de la bomba Zona 1 Zona 2 Zona 3 Zona 4 Bomba del sistema de caldera Zona 1 Zona 2 Zona 3 Zona 4 Parte trasera del House Control 403 115 V ca 115 V c...

Страница 10: ...ta tN4 Caldera moduladora Potencia de entrada Usar con conductores que como m nimo soporten 167 F 75 C Zona 2 Zona 3 Zona 4 Zona 1 Acci n otante Orden pre establecida Orden DHW 24 V ca Transformador 0...

Страница 11: ...POR CLIMA C LIDO Muestra cuando el sistema se encuentra trabajando bajo el m todo de Desconexi n por clima c lido F C minhr sec F C HORAS MINUTOS SEGUNDOS Unidades de medida para un n mero actual LIB...

Страница 12: ...mezcladores para poder calentar las instalaciones en el d a m s frio del a o Recomendaciones Piso de losa radiante de alto rendimiento 120 F 50 C Piso de losa radiante de bajo rendimiento 140 F 60 C F...

Отзывы: