background image

5

Differential 



The differential adjustment sets how far the actual boiler supply water temperature may deviate from the desired temperature before
the boiler is turned on or off, and it is determined by the flow rate through the system pump relative to the heat output by the boiler.
The Differential can be adjusted to Ad (Auto differential) or from 2 to 42

°

F (1 to 23

°

C). The following formula can be used to calculate

the desired differential:

When the adjustment is set to 

Ad (Auto Differential), the differential is continuously calculated by the control, and varies as the heating

load changes. This setting is suggested and therefore it is a factory setting.

Minimum Boiler Supply

 

Most boilers require a minimum operating temperature to prevent corrosion from flue gas condensation. The 

Minimum Boiler setting

should be programmed to the lowest supply water temperature at which the boiler can operate without causing the boiler flue gases
to condense. Consult the boiler manufacturer for recommended minimum boiler supply temperatures. Some typical settings are as
follows:

• Steel fire tube boiler  ….......... 140 to 160

°

F (60 to 71

°

C)

• Condensing boiler  ................. Off

• Cast iron boiler  ….................. 135 to 160

°

F (57 to 71

°

C)

• Electric boiler  ........................ Off

• Copper tube boiler  …............. 125 to 150

°

F (52 to 66

°

C)

Curve (Heating Curve) 



The Heating Curve setting determines the number of degrees the supply water tempera-
ture is raised for every one degree drop in outdoor temperature. The 

Curve setting can

be calculated from the following formula.

design supply temperature – Starting water temperature

Heating Curve

=

WWSD – design outdoor temperature

Curve (Heating Curve) Setting Examples: 



Example #1

Example #2

Example #3

Design Supply Water Temperature

180

°

F (82

°

C)

180

°

F (82

°

C)

180

°

F (82

°

C)

Starting Water Temperature

70

°

F (21

°

C)

150

°

F (66

°

C)

160

°

F (71

°

C)

Design Outdoor Temperature

-5

°

F (-21

°

C)

-5

°

F (-21

°

C)

-5

°

F (-21

°

C)

Warm Weather Shut Down (WWSD)

70

°

F (21

°

C)

65

°

F (18

°

C)

60

°

F (16

°

C)

Minimum Boiler

130

°

F (54

°

C)

130

°

F (54

°

C)

130

°

F (54

°

C)

Differential

=

Example:

=

10

°

F (6

°

C)

Btu/hr input

100,000 Btu/hr

System US GPM x 50

20 US GPM x 500

Outdoor air  temperature

55

(13)

40

(4)

25

(-4)

10

(-12)

70

(21)

°

F

(

°

C)

Supply water temperature

110

(43)

70

(21)

90

(32)

210

(99)

170

(77)

150

(65)

130

(54)

190

(88)

-5

(-21)

Example #3

Example #2

Example #1

WWSD

Design

Condition

Starting
Temp.

Outdoor air  temperature

50

(10)

30

(-1)

10

(-12)

-10

(-23)

70

(21)

3.6 3.0 2.4 2.0

1.6

1.2

0.8

0.4

1.0

0.6

90

(32)

Starting

Point

°

F

(

°

C)

Supply water temperature

110

(43)

70

(21)

90

(32)

210

(99)

170

(77)

150

(65)

130

(54)

190

(88)

0.2

=

Example #1

Heating Curve     =

180 — 70

°

F (82 — 21

°

C)



70 — (-5

°

F) (21 — (-21

°

C))

110

°

F (61

°

C)



75

°

F (42

°

C)

= 1.5

=

Example #2

Heating Curve     =

180 — 150

°

F (82 — 66

°

C)



65 — (-5

°

F) (18 — (-21

°

C))

30

°

F (16

°

C)



70

°

F (39

°

C)

= 0.4

=

Example #3

Heating Curve     =

180 — 160

°

F (82 — 71

°

C)



60 — (-5

°

F) (16 — (-21

°

C))

20

°

F (11

°

C)



65

°

F (37

°

C)

= 0.3

Control Adjustments 



Starting Temp.: __________________________________________

WWSD: ________________________________________________

Curve: _________________________________________________

Differential: _____________________________________________

Minimum Boiler: _________________________________________

Содержание One Stage Boiler Control 253

Страница 1: ... Mar 97 31000265 displays control settings displays hundreds of hours of use displays hours of use Press Hold Item One Stage Boiler Control 253 2 3 Com Sen Boil Sen Out Sen No power 7 8 Power R C NRTL C LR 58223 R USE hours Minimum Boiler Differential Curve Boiler Supply Target Boiler Starting Temp H Dem Boiler OUTDOOR Signal wiring must be rated at least 300V Input Heat Demand Made in Canada Cont...

Страница 2: ...s possible for maximum efficiency Differential An on off boiler must be operated with a differential in order to prevent short cycling When the supply water temperature drops below the bottom rail of the differential the boiler is turned on The boiler is then kept on until the supply water temperature rises above the top rail of the differential If the differential is too wide there can be large s...

Страница 3: ...ur responsibility to ensure that this control is safely installed according to all applicable codes and standards This electronic control is not intended for use as a primary limit control Other controls that are intended and certified as safety limits must be part of the control circuit STEP ONE GETTING READY Check the contents of this package If any of the contents listed are missing or damaged ...

Страница 4: ...d Connect the C side of the transformer to terminal T 6 through a switching device This provides a heat demand to the control Caution The C of the same transformer used to power up the control must be used to provide the heat demand Sensor and Unpowered Input Connections Do not apply power to these terminals as this will damage the control Outdoor Sensor Connect the two wires from the Outdoor Sens...

Страница 5: ... in outdoor temperature The Curve setting can be calculated from the following formula design supply temperature Starting water temperature Heating Curve WWSD design outdoor temperature Curve Heating Curve Setting Examples Example 1 Example 2 Example 3 Design Supply Water Temperature 180 F 82 C 180 F 82 C 180 F 82 C Starting Water Temperature 70 F 21 C 150 F 66 C 160 F 71 C Design Outdoor Temperat...

Страница 6: ...pply pointer WWSD Boiler Supply Target Boiler Starting Temp Minimum Boiler Differential Curve F H Dem Boiler WWSD Boiler Supply Target Boiler Starting Temp Minimum Boiler Differential Curve PRGM F C When the control is powered up a version number followed by all display elements are turned on After approximately 5 seconds the control automatically goes into operating mode OUTDOOR H Dem Boiler WWSD...

Страница 7: ...70 Refer to the troubleshooting section above for operation details WWSD Boiler Supply Target Boiler Starting Temp Minimum Boiler Differential Curve OUTDOOR H Dem Boiler Outdoor Sensor Open Circuit WWSD Boiler Supply Target Boiler Starting Temp Minimum Boiler Differential Curve OUTDOOR H Dem Boiler WWSD Boiler Supply Target Boiler Starting Temp Minimum Boiler Differential Curve OUTDOOR H Dem Boile...

Страница 8: ...n compliance with the local codes and ordinances or if due to defective installation of the product The warranty applicable to a product is as set out in the statement of warranty policy the Warranty above receipt of which is hereby acknowledged The liability of tekmar is limited to those obligations identified in the warranty as obligations of tekmar The warranty is understood to be in substituti...

Отзывы: