background image

10

Step Six

Essential control settings

To obtain the best operation from a reset control, it is important to measure the system supply temperature as accurately
as possible. Whenever the control receives a heat demand signal, the system pump must be operated to maintain
continuous water flow past the supply temperature sensor.

For specific application details refer to Application Brochure A 258.
A more detailed technical description of the effect of control settings on overall system operation is described in the tekmar Essay, E 002.

Reset operation

Stpnt — Reset switch

When the boilers are used in a heating system and the supply temperature is to be
controlled on an outdoor reset schedule (Heating Curve), this switch must be set
to "Reset".
Programming the control for Occupied/Unoccupied room temperatures and setback
schedules will be covered in the "Programming" section starting on page 15.

Heat Demand switch

When the heating system uses zone valve end switches or some other means of
delivering an external heat demand signal to terminals 

Heat Dem (5 and 6), set this

selector switch to "External Demand" and the control will be enabled when it receives
a 24Vac signal from the heat demand circuit. If an external heat demand signal is not
used, set the switch to "Permanent Demand".

Auto

Stage

1   2   3   4   5   6   7   8

Perm.
Demand

Ext. timer

Fixed last

Int. timer

Lo-Hi fire

Fixed lead

Rotate

Off

1

2

3

4

5

6

7

8

9

External
Demand

Off

1

2

3

4

5

6

Stpnt

Reset

Heating Curve

As outdoor temperatures drop, heat losses from a building become greater and the
heating system supply water temperature must be raised to maintain a constant room
temperature. The heating curve value describes how many degrees the supply water
temperature is raised for a one degree drop in outdoor temperature. The supply
temperature starts to increase when the outdoor temperature falls below the WWSD
point. To calculate the correct setting for the Heating Curve, use the following
formula.

Outdoor air  temperature

Supply water temperature

50

(10)

30

(-1)

10

(-12)

-10

°

F

(-23)

°

C

110

(43)

70

(21)

70

(21)

90

(32)

210

(99)

170 

(77)

150 

(65)

130 

(54)

190

(88)

3.6 3.0 2.4 2.0

1.6

0.8

0.4

1.0

0.6

90

(32)

50

°

F

(10)

°

C

Heating

Curve

WWSD

Point

1.2

For more information regarding the Heating Curve, refer to page 2 of this brochure.
If the actual design supply water temperature for a system is unknown, a trial setting
can be calculated using these typical supply temperatures:
• Fan coils …180

°

 to 210

°

F (82

°

 to 99

°

C)  • Baseboards …160

°

 to 190

°

F (71

°

 to 88

°

C)

• Radiant floors …100

°

 to 130

°

F (38

°

to 54

°

C).

160

°

F - 70

°

F

70

°

F - 5

°

F

90

°

F

65

°

F

design supply temperature – room temperature

room temperature – design outdoor temperature

Heating Curve  =

For example:

•  design outdoor temperature =  5

°

F (-15

°

C)

•  room temperature =  70

°

F (21

°

C)

•  design supply temperature =  160

°

F (71

°

C)

Heating Curve  =

  =

  =   1.4

Setpoint operation

Stpnt — Reset switch

When the boilers are used to maintain the supply temperature at a setpoint, set this
switch to "Stpnt".
Programming the control for Occupied/Unoccupied setpoint temperatures and set-
back schedules will be covered in the "Programming" section starting on page 15.

Setpoint Demand switch

End switches, aquastats or some other means of delivering an external setpoint
demand signal can be used to bring 24Volts to terminals 

Heat Dem (5 and 6) when

the control is used as a setpoint control. This selector switch should be set to "External
Demand" and the control will be enabled when it receives the 24Vac signal. If an
external setpoint demand signal is not used, set to "Permanent Demand".

Auto

Stage

1   2   3   4   5   6   7   8

Perm.
Demand

Ext. timer

Fixed last

Int. timer

Lo-Hi fire

Fixed lead

Rotate

Off

1

2

3

4

5

6

7

8

9

External
Demand

Off

1

2

3

4

5

6

Stpnt

Reset

Auto

Stage

1   2   3   4   5   6   7   8

Perm.
Demand

Ext. timer

Fixed last

Int. timer

Lo-Hi fire

Fixed lead

Rotate

Off

1

2

3

4

5

6

7

8

9

External
Demand

Off

1

2

3

4

5

6

Stpnt

Reset

Auto

Stage

1   2   3   4   5   6   7   8

Perm.
Demand

Ext. timer

Fixed last

Int. timer

Lo-Hi fire

Fixed lead

Rotate

Off

1

2

3

4

5

6

7

8

9

External
Demand

Off

1

2

3

4

5

6

Stpnt

Reset

0.4

2.0

3.6

Heating Curve

Settings

Содержание Eight Stage Boiler Control 258

Страница 1: ...mand Minimum WWSD Pump Stage 1 Stage 2 Comb air Stage 3 Stage 6 Stage 5 Stage 8 Stage 7 Stage 4 Menu Item Override Setpoint Actual Supply Target Supply S PRGM TEMP F C TIME USE AMPM UNOCC OVR M T W T...

Страница 2: ...ugh water to keep the room temperature warm particularly during the colder weather If the Heating Curve selected is too high the supply water will be too hot for the conditions and the building will o...

Страница 3: ...ntrol The effect of the Integral function can also be easily viewed by not allowing a rise in supply temperature when the control asks for more heat The displayed target temperature will show a slow b...

Страница 4: ...allow Heating Curve operation System pump light on the system pump relay is on closing the contacts between terminals System Pmp 3 4 Comb air light on the combustion air relay is on closing the contac...

Страница 5: ...e Occupied room temperature setting the control enters WWSD When switched into Unoccupied mode the UNOCC display element will replace the OCC display element and the control will switch from operating...

Страница 6: ...e Stage and Comb air lights will be shut off with the boilers and combustion air damper The control will continue to cycle the boilers and combustion air damper to maintain the supply at the target te...

Страница 7: ...lighter guage wire is too fragile and may also contribute too much resistance to the circuit Power should not be applied to any of the wires during this rough in wiring stage Step Four Electrical con...

Страница 8: ...nals Heat Dem 5 and 6 When 24Vac is applied to these terminals the control will recognize a call for heat from the system DIP switch must be set to Reset If a 24Vac Setpoint Demand signal is used aqua...

Страница 9: ...powered up the combustion air damper should operate If it does not come on check the circuit wiring for errors and ensure that it is powered up and the voltage is correct Check the devices in the cir...

Страница 10: ...e Heating Curve use the following formula Outdoor air temperature Supply water temperature 50 10 30 1 10 12 10 F 23 C 110 43 70 21 70 21 90 32 210 99 170 77 150 65 130 54 190 88 3 6 3 0 2 4 2 0 1 6 0...

Страница 11: ...w Domestic Hot Water boilers to be switched over to assist the heating boilers during peak load times Int timer switch The 258 control has an internal timer programmed using the LCD display and keypad...

Страница 12: ...tback and delivering cold water to the boilers increased load Typically this will cause many or all of the boilers to be staged on with minimum delay which is the correct control action for the situat...

Страница 13: ...ustion air damper will remain open After the 5 minutes the control will automatically exit the test routine and enter the normal operating mode If there is no Heat Demand the control will not allow a...

Страница 14: ...ply temperatures and the LED system status lights display the operation of the various system components A competent troubleshooter can locate system faults without having to go any further than obser...

Страница 15: ...tual Supply Target Supply F S TEMP OCC S M W T F T Auto Stage 1 2 3 4 5 6 7 8 Perm Demand Ext timer Fixed last Int timer Lo Hi fire Fixed lead Rotate Off 1 2 3 4 5 6 7 8 9 External Demand Off 1 2 3 4...

Страница 16: ...ress or to change the day pointer PROGRAM MENU VIEWING Must be set to Int timer Auto 1 2 3 4 5 6 7 8 Perm Demand Ext timer Int timer Off 1 2 3 4 5 6 7 8 9 External Demand Off 1 2 3 4 5 6 Stpnt Reset P...

Страница 17: ...button when the control is showing a fixed display Setpoint Actual Supply Target Supply F S TEMP S M W T F T OVR UNOCC Which mode is selected See page 3 Menu Item Override Menu Item Override Menu Item...

Страница 18: ...nOcc 1 5 00 pm Occ 2 10 30 pm UnOcc 2 Friday 6 00 am Occ 1 8 30 am UnOcc 1 5 00 pm Occ 2 11 30 pm UnOcc 2 Saturday 8 00 am Occ 1 11 30 pm UnOcc 1 Null Occ 2 Null UnOcc 2 Schedule P 5 Day Time Temperat...

Страница 19: ...when powered down for up to 10 years Battery backup Maintains clock operation for 24hrs when powered down Dial Switch Settings Heating Curve 0 4 to 3 6 Minimum Off 80 to 170 F Off 27 to 77 C Boiler D...

Страница 20: ...antability and fitness for a particular purpose shall not extend beyond 24 months from the date of invoice or 12 months from the date of installation of the product whichever occurs first Replacements...

Отзывы: