background image

© 2009 

  D 512 - 09/09 

4 of 20 

TWO STAGE HEAT

The two stage mode of operation is selected using the DIP switch located on the circuit 
board inside the thermostat.

In cases where a one stage heating system can not provide sufficient heat under all 
conditions, a second stage of heat can be added to supplement the first stage. A two stage 
system therefore has one thermostat controlling two output relays.

Two Stage Logic

The temperature in a two stage zone is controlled by varying the on time of the Heat 1 
and Heat 2 relays during a cycle. Under light loads, the Heat 1 relay is cycled on and 
off. As the load increases, the Heat 1 relay on time is increased until it reaches the 
maximum of the cycle length or, if a slab sensor is used, the slab temperature reaches 
the slab maximum setting. The Heat 2 relay is then cycled and its on time is increased 
as the load increases. When the heating load decreases, the on time of the Heat 2 
relay is reduced until the Heat 2 relay is turned off completely. The thermostat then 
reduces the on time of the Heat 1 relay

.

NOTE: 

When using a slab sensor, the Heat 2 relay may be on while the Heat 1 relay is 

off if the slab temperature has reached the slab maximum setting

.

Air Sensor(s) Only Operation

When operating with only an air sensor, the on times for the Heat 1 and Heat 2 relays 
are calculated to satisfy the requirements of the air sensor.

Slab Sensor Only Operation

When operating with only a slab sensor, the on times for the Heat 1 and Heat 2 relays 
are calculated to satisfy the requirements of the slab sensor. The thermostat operates to 
maintain the slab at the minimum slab temperature setting

.

NOTE:

 Operating with only a slab sensor can lead to either overheating or underheating 

of the space

.

Air and Slab Sensor Operation

When operating with both air and slab sensors, the thermostat calculates an on time for 
the Heat 1 relay to satisfy the slab sensor’s requirements and on times for the Heat 1 
and Heat 2 relays to satisfy the air sensor’s requirements. The thermostat operates the 
Heat 1 relay for the longer of these two on times.

While the minimum slab temperature is satisfied, the on times of the Heat 1 and Heat 2 
relays are calculated to satisfy the air temperature requirements

.

During heavy loads, the maximum slab temperature setting limits the on time of the Heat 
1 relay. In this situation, the Heat 2 relay may be on while the Heat 1 relay is off.

NOTE:

 During light heating loads, overheating can occur due to the minimum slab 

temperature requirements

.

 Mode

Heat

  In the heat mode, the Heat 1 and Heat 2 relays are operated to satisfy the 

temperature requirement of the zone

.

Off 

In the Off mode, the Heat 1 and Heat 2 relays are not operate

d.

NOTE:

 If an air or slab sensor is active in the Off mode, a freeze protection is enabled 

that allows the relays to be operated to keep the zone above 35°F (2°C).

Содержание D 512

Страница 1: ...on pg 1 Display Symbols pg 2 General pg 2 3 Sequence of Operation pg 4 6 Type 512 Two Stage Heating pg 4 Type 512 Heat Cool pg 5 6 Menus pg 6 10 View Menu pg 6 Adjust Menu pg 7 10 Error Messages pg 11...

Страница 2: ...ing relay s the thermostat ensures that the relay s remains on or off for a minimum amount of time In order to prevent short cycling of the Cool relay the minimum cooling on time and minimum cooling o...

Страница 3: ...eat relay and allows the thermostat to operate the slab between the slab minimum and slab maximum settings If more than one slab sensor is used the slab temperatures are averaged by the thermostat Rem...

Страница 4: ...ted to satisfy the requirements of the air sensor Slab Sensor Only Operation When operating with only a slab sensor the on times for the Heat 1 and Heat 2 relays are calculated to satisfy the requirem...

Страница 5: ...s requirements In this situation heating and cooling can happen at the same time to prevent the space from overheating This is most likely to occur when the slab is operating at the slab minimum tempe...

Страница 6: ...cooling setpoint When operating in the Cool mode there is no interlock between the heating and cooling temperature View Menu 1 of 1 ROOM TARGET The current desired air temperature for the space This...

Страница 7: ...an active slab sensor OFF 34 to 122 F OFF 1 0 to 50 0 C ROOM HEAT WAKE Desired temperature for heating during Wake Must have an active air sensor and be set to either Heat or Auto 35 to 100 F 1 5 to...

Страница 8: ...o 35 to 100 F 1 5 to 38 0 C ROOM COOL Sleep Desired temperature for cooling during Sleep Must have an active air sensor and be set to either Cool or Auto 35 to 100 F 1 5 to 38 0 C SLAB MINIMUM Wake Mi...

Страница 9: ...built in sensor is functional or not This item is only available in the Installer access level OFF ON HEATING CYCLE Determines the number of cycles per hour for the heating equipment This item is onl...

Страница 10: ...y available in the Installer access level 0 30 to 10 00 min Adjust Menu 4 of 4 EARLY START Selects whether or not the Early Start feature is active This item is only available in the Installer access...

Страница 11: ...ernal sensor and use an auxiliary sensor set to INDR or replace the thermostat After the fault is corrected press any button to clear the error message SENSOR 1 SHORT The auxiliary sensor connected to...

Страница 12: ...floor Do not mount the thermostat in a location that may be affected by localized heat sources or cold drafts It may be necessary to install a draft barrier behind the thermostat to prevent air from...

Страница 13: ...age or high current device Heat 2 Cool The Heat 2 Cool terminals 8 and 9 are an isolated output There is no power available on these terminals from the thermostat This circuit can operate a low curren...

Страница 14: ...User 2 Stage Heat Cool Made in Canada Meets Class B Canadian ICES FCC Part 15 Power 24 V 10 60 Hz 3 VA Relay 24 V ac 2 A Class 2 938 02 512 Switch Settings Installer User 2 Stage Heat Cool Made in Ca...

Страница 15: ...ne Pump 24 V ac Class 2 Transformer Made in Canada Meets Class B Canadian ICES FCC Part 15 Power 24 V 10 60 Hz 3 VA Relay 24 V ac 2 A Class 2 938 02 512 Switch Settings Installer User 2 Stage Heat Coo...

Страница 16: ...FCC Part 15 T T 1 2 L N M Stage 2 Zone Valve 24 V ac Class 2 Transformer Stage 1 Zone Pump Typical Powered Relay Two Stage with Zone Pump and Zone Valve Power 24 V 10 60 Hz 3 VA Relay 24 V ac 2 A Cla...

Страница 17: ...Part 15 2 1 8 7 3 4 5 6 2 1 8 7 3 4 5 6 Stage 2 Zone Pump Stage 1 Zone Pump 24 V ac Class 2 Transformer Unpowered Relay Unpowered Relay Power 24 V 10 60 Hz 3 VA Relay 24 V ac 2 A Class 2 938 02 512 S...

Страница 18: ...2009 D512 09 09 18 of 20 Notes...

Страница 19: ...19 of 20 2009 D512 09 09 Notes...

Страница 20: ...g from ownership or use of the product or from defects in workmanship or materials including any liability for fundamental breach of contract The pass through Limited Warranty applies only to those de...

Отзывы: