STEP FOUR 

 ROUGH IN WIRING

  18 AWG or similar wire is recommended for all 24 V (ac) wiring.

  All wires are to be stripped to 1/4” (6 mm) to ensure proper connection to the control.

  Run wires from the 24 V (ac) power to the thermostat. Use a clean power source to 

  If an auxiliary sensor is used, install the sensor according to the appropriate Data 

Brochure and run two wires from the sensor to the thermostat.

  Run wires from the heating device to the thermostat.

STEP FIVE 

 WIRING THE THERMOSTAT

(Refer to the examples on the following page.)

24 V (ac) Power

Connect the 24 V (ac) power to the 

and 

terminals of the thermostat. This connection 

provides power to the microprocessor and display of the thermostat.

Auxiliary Sensor

Either an indoor, slab, or outdoor sensor may be connected to the auxiliary sensor input. 
Connect the two wires from the auxiliary sensor to the Sensor terminals.

Heat Relay (Rh – W) 

The 

Heat Relay

 

Rh – W

 terminals are an isolated output. There is no power available 

on these terminals from the thermostat. These terminals are to be used as a switch for 
a 24 V (ac) circuit. This circuit can operate a low current 24 V (ac) device directly or an 
external relay to enable a line voltage or high current device.

STEP SIX 

 INSTALLING THE FRONT COVER

Align the hinges on the bottom of the front cover with the bottom of the thermostat mounting 
base. Pivot the front cover around the bottom hinges and push the top against the mounting 
base until it snaps firmly in place.

Pivot front

cover around

bottom hinges

Align hinges

on bottom

of front cover

1

2

Menu

Item

NOTE:

 If the 508 is to be used for remote sensing (i.e. The built-in air sensor is disabled 

and an indoor sensor is being used.) Mount the thermostat in the desired location in an 
appropriate manner.

Содержание D 508

Страница 1: ...he thermostat s display has four distinct fields These fields are the Menu field the Item field the Number field and the Status field The four buttons on the face of the thermostat are used to navigat...

Страница 2: ...th temperature swings and equipment cycles AUXILIARY SENSOR The thermostat has a single built in sensor to measure air temperature at the thermostat In addition to the built in sensor the thermostat h...

Страница 3: ...er of these two ON times During light heating loads overheating can occur due to the minimum slab temperature requirements During heavy heating loads the maximum slab temperature setting limits the ON...

Страница 4: ...a freeze protection is enabled that allows the Heat relay to be operated to keep the zone above 35 F 2 C STEP THREE MOUNTING THE BASE The thermostat should be installed on an interior wall of the des...

Страница 5: ...ected to the auxiliary sensor input Connect the two wires from the auxiliary sensor to the Sensor terminals Heat Relay Rh W The Heat Relay Rh W terminals are an isolated output There is no power avail...

Страница 6: ...d Switch C Input Power R R H8002A X X Input Power 24 V ac 10 60 Hz 11 VA Class 2 End Switch 24 V ac 2 A Pump Relays 115 V ac 5 A Zone Power 115 V ac 12 A Made in Canada tektra 1031 01 Use at least 167...

Страница 7: ...Sensor 24 V ac Class 2 Transformer 115 V ac Unpowered Relay Wiring to Switching Relay Auxiliary Sensor Zone Pump L N 115 V ac W T T R NO POWER 2 Sensor 1 24 V 10 50 60 Hz 1 5 VA 24 V ac 2 A Class 2 I...

Страница 8: ...ing at Slab Minimum MENU BUTTON The menus display in the Menu Field at the left of the LCD Three menus are available View Adjust Schd Schedule To select a menu press and release the Menu button ITEM B...

Страница 9: ...ilable in the Installer access level Must have an active slab sensor 34 to 122 F OFF 1 0 to 50 0 C OFF SENSOR Selects the type of auxiliary sensor present This item is only available in the Installer...

Страница 10: ...hould be replaced or returned for repair ROOM OPEN The thermostat s internal air sensor is open circuit This cannot be repaired in the field Either turn off the internal sensor and use an auxiliary se...

Страница 11: ...11 of 12 2010 D508 05 10 Notes...

Страница 12: ...uct or from defects in workmanship or materials including any liability for fundamental breach of contract The pass through Limited Warranty applies only to those defective Products returned to tekmar...

Отзывы: