background image

 

BA_LMD-508_150602_GB.doc 

- 8 - 

02.06.2015 

 
 

 Operation of the system 

 

 

Attention: 

Possibilities of adjustment of the programme, menu navigation ecc of the system you will find in the 
attached manual of the steering. 

 
 

 

Maintenance 

The  filtering  out  of  dust  particles  means  that  the  prefilter  (coarse)  and  the  particle  filter  (fine) 
become increasingly dirty, and the suction power decreases. 

The  mechanical  filter  insert  ensures  that  more  than  90%  of  the  pollutants  that  are  sucked  in  are 
trapped in the filter. This is still so, even if the filter insert is partially or completely saturated. But 
the suction power of the filter unit drops as the saturation level increases. 

The  saturation  level  of  the  filter  is  electronically  monitored.  In  order  to  maintain  the  rated  suction 
power  of  the  unit,  the  filters  must  be  replaced  when  the  red  flow  volume  indicator  lamp  (Pos.5) 
lights up. 

The  prefilter  matting  (Pos.13)  must  be  replaced  at  regular  intervals. 

(see  Section  7.1:  “Replacing 

the prefilter matting”). 

Please check at least weekly the pollution of the pre-filter mat

 .

 

As  soon  as  the  airflow  resistance  of  the  filter  has  increased  to  the  point  where  the  suction  force 
decreases,  the  particle  filter  (Pos.14)  must  be  replaced,  because  it  is  clogged  with  the  extracted 
dust and smoke particles. 

(see Section 7.2: “Replacing the particle filter”)

 

The  activated-carbon  cassette  (Pos.15)  must  be  replaced  if  gas  starts  to  come  through  to  the 
clean-air side. At the very latest, the activated-carbon cassette must be replaced when the particle 
filter is replaced. 

(see Section 7.3: “Replacing the activated-carbon cassette”)

 

The working  lives  of the  prefilter matting, the particle  filter, and the  activated-carbon cassette are 
strongly dependent on the specific conditions of use. So they cannot be determined in advance.  

The filter equipment includes a maintenance-free AC-operated turbine. 

 

Warning: 

The operation of the filter unit must be stopped while the filter insert is being replaced. 
Filter  replacement  and  disposal  must  only  be  carried  out  in  well-ventilated  rooms,  and  a  proper 
respiratory mask must be worn. 
We  recommend:  a  respiratory  half-mask  to  DIN  EN  141/143  protective  level  P3  or  equivalent 
national standard. 
The filters should only be replaced by a member of staff who has been properly trained! 
Dispose of the filter inserts in accordance with the legal regulations! 
If the filter is manually tapped out, washed, or blown out, then the filter material will be damaged. 
The pollutants will spread into the air of the room. 

 
 

Содержание LMD 508

Страница 1: ...nstructions Type TEKA LMD 508 TEKA Absaug und Entsorgungs technologie GmbH Industriestra e 13 D 46342 Velen Postfach 1137 D 46334 Velen Tel 49 0 2863 9282 0 Fax 49 0 2863 9282 72 E Mail sales teka eu...

Страница 2: ...mmissioning 6 5 1 Attaching the extractor fittings 6 5 2 Electrical connection of the unit 7 6 Operation of the system 8 7 Maintenance 8 7 1 Replacing the prefilter matting 9 7 2 Replacing the particl...

Страница 3: ...Filter door Ventilator housing Ventilator door Castor Castor with brake Twist lock fastener Lifting mechanism Pos 11 Pos 13 Pos 14 Pos 15 Pos 16 Pos 17 Pos 18 Pos 19 Locking screw for the lifting mec...

Страница 4: ...complete volume of air in the workshop is replaced However this method only achieves a small reduction in the level of pollution within the breathing space of the user The same applies to the so call...

Страница 5: ...to the point where the suction force decreases the filter must be replaced because it is clogged with the extracted dust and smoke particles see Section 7 1 Replacing the prefilter matting Section 7...

Страница 6: ...possible damage The unit must not be used if the mains supply cable is not in perfect condition Do not use the filter unit if one or more of its components are faulty missing or damaged In any of the...

Страница 7: ...e motor speed of the turbine 3 4 Filter alarm Floating output normal open contact for interpretation of the warn alarm Filter alarm 5 6 Operation control Floating output normal open contact for interp...

Страница 8: ...ce decreases the particle filter Pos 14 must be replaced because it is clogged with the extracted dust and smoke particles see Section 7 2 Replacing the particle filter The activated carbon cassette P...

Страница 9: ...14 Use the fixing screw Pos 11 to raise the lifting mechanism Pos 10 so that the particle filter Pos 14 fits tightly underneath the equipment cover Pos 2 Close the filter door Pos 4 Connect the filte...

Страница 10: ...activated carbon cassettes Use the fixing screw Pos 11 to raise the lifting mechanism Pos 10 so that the particle filter Pos 14 fits tightly underneath the equipment cover Pos 2 Close the filter door...

Страница 11: ...e Ph 1 Frequency Hz 50 Motor power kW 1 2 Max airflow volume m h 320 Max partial vacuum Pa 21000 Enclosure type IP 54 ISO class F Operating voltage V 230 Duty cycle 100 Width x depth x height mm 365 x...

Страница 12: ...article filter Pos 14 Activated carbon cassette Pos 15 Activated carbon pouring Turbine 1 2kW with elektronic Castor Pos 11 Castor with brake Pos 12 Suction hose length 2 5m NW45 with air intake Sucti...

Страница 13: ...ng directives Machinery directive 2006 42 EG Electromagnetic compatibility 2014 30 EU Pressure equipment device 97 23 EG Low voltage directive 2006 95 EG Applied harmonised standards DIN EN 349 DIN EN...

Отзывы: