BA_LMD-508_150602_GB.doc
- 10 -
02.06.2015
7.3 Replacing the activated-carbon cassette
If gas escapes on the clean-air side, or the particle filter (Pos.14) is replaced, then the activated-
carbon cassette (Pos.15) must be replaced, as follows:
•
Disconnect the filter unit from the mains supply.
•
Open the filter door (Pos.4) by use of Allen key.
•
Use the fixing screw (Pos.11) to lower the lifting mechanism (Pos.10).
•
Pull out the activated-carbon cassette (Pos.15) with the particle filter (Pos.14).
•
Push in the new activated-carbon cassette with the particle filter.
Warning:
Use only TEKA activated-carbon cassettes!
•
Use the fixing screw (Pos.11) to raise the lifting mechanism (Pos.10), so that the particle filter
(Pos.14) fits tightly underneath the equipment cover (Pos.2).
•
Close the filter door (Pos.4).
•
Connect the filter unit to the mains supply.