T412 SERIES

 

 

 

 

MEASUREMENT SIGNAL TRANSFER

 

 

All the cables transferring the measurement signals must: 

 

  be separated from the power cables 

  be shielded cables with twisted conductors 

  have at least 0.5 mm² section 

  be twisted with a 60mm pitch maximum 

  be firmly fixed inside the terminal boxes 

  have tinned or silvered conductors 

 

NOTE: to install the sensors and signal transferring cable correctly, read the sensor and SCS/Sensor  installation rule 

manual.

 

 

 

All T series control units have linearity of the sensor signal, with a maximum error of 1% of full scale value. 

 

TEMPERATURE SENSOR DIAGNOSTICS (only control unit with Pt100 sensors)

 

 
 

In case of failure or exceeded minimum/maximum full scale value of one of the thermometric sensors installed on the 
machine  to  be  protected,  the  FAULT  relay  switches  immediately  with  the  relative  warning  of  faulty  sensor  on  the 
corresponding channel. 

 

Fcc highlights that the sensor is short-circuited or that the minimum full scale value of the unit has been 

exceeded. 

 

Foc highlights that the sensor is open or that the maximum full scale value of the unit has been exceeded.  

 

To eliminate the message and reset FAULT switching, it is necessary to check the Pt100/TCK connections and replace 
the faulty sensor (if any). If the minimum/maximum full scale value has been reached, check that the ambient conditions 
match the control unit reading. 

 

Note: exceeding the minimum/maximum full scale value can be caused by interference on the sensor lines; in this case 
we recommend that you check: 

 

the correct installation of the sensors and above all of the extension cable (as stated in the paragraph MEASUREMENT 
SIGNAL TRANSFER) 
the activation of the FCD function of the control unit (as stated in the FCD FUNCTION NOTES on page 15). 

 

TEMPERATURE DIAGNOSTICS

 

 

When  the  temperature  sensor  detects  the  temperature  is  1°C  higher  than  the  value  set  as  pre-alarm  limit,  relay  L1 
switches after about 4". 

 

The same happens when the trip temperature threshold is exceeded and the L2 relay switches. 

 

As  soon  as  the  detected  temperature  goes  1°C  below  the  limit  set  for  the  L1  and  L2  relays  switching,  these  relays 
deenergize and the relative LEDs switch off. 

 

If  the FLAG function  has been programmed,  the  L1  and/or L2 relays  shall  remain  energised  from  the moment 
the type of alarm is recognized to the following RESET.

 

 

L1 AND L2 RELAY RESET (FLAG)

 

 

To reset the alarm relays (if the HOLD function is ON), just press the RESET key. 

 

PROGRAMMED DATA DIAGNOSTICS

 

 

In case of failure of the internal memory or alteration of the programmed data, at start-up 

Ech 

 is displayed 

with the relative warning of the Fault contact. 
In this case, for safety reasons, the default parameters are loaded automatically (see the programming table on pages 
11 and 12 according to the model purchased). 
Eliminate the 

Ech 

 message by pressing RESET and enter the desired values. 

Finally switch the unit off and back on to check the memory works correctly, if it is damaged 

Ech 

 will be displayed again 

(send the control unit to TECSYSTEM srl for repair). 

NOTE: 

the use of cables not complying with the above might cause reading anomalies. It is always important to take 

into account that any interference on the signal lines might cause anomalies on the inputs or the sensors themselves.

 

Содержание T412 Series

Страница 1: ...with ISO9001 certified quality system http www tecsystem it R 1 4 01 08 19 Translations of the original instructions ENGLISH TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 T412 SE...

Страница 2: ...NTING 8 6 ELECTRICAL CONNECTIONS 9 T412 PT100 BACK T412 TCK BACK POWER SUPPLY 10 ALARM ELECTRICAL CONNECTIONS 7 PROGRAMMING T412 STANDARD 11 T412 CODE T412 CODE T OFF 12 CORRECTING THE SET VALUES CHEC...

Страница 3: ...ity exceeding 90 and never touch with wet or humid hands If any liquid penetrates the control unit disconnect it immediately and contact technical service CLEANING Disconnect the power cable before cl...

Страница 4: ...367 Screws tightening torque 0 5Nm 1 TCK sensor terminal 2 poles pitch 5 Code 2PL0364 Screws tightening torque 0 5Nm 1 sensor terminal 9 poles pitch 5 Code 2PL0376 Screws tightening torque 0 5Nm 1MN00...

Страница 5: ...electromagnetic interference Cable compensation for sensor 500 m 1 mm Pt100 100 m 1 mm Tck 100 m 1 mm Tck OUTPUTS 2 alarm relays L1 and L2 SPDT 1 fault sensor or operating failure FAULT relay SPDT Ou...

Страница 6: ...ED showing the FAULT LED showing PRG LED showing HOLD LED showing T MAX LED showing T MIN Temperature control from 0 C to 200 C for Pt100 0 C to 999 C for TcK Only TCK Only TCK 2 L1 L2 alarm threshold...

Страница 7: ...10 LTest Reset key 3 FAULT warning red LED 11 Programming Confirmation key 4 T MAX warning red LED 12 PRG ON red LED 5 UP T MAX key 13 ALL1 alarm red LED 6 DOWN T MIN key 14 ALL2 trip red LED 7 T MIN...

Страница 8: ...et 2 1 3 1MN0062 REV 0 1 Control unit 2 Panel hole dimensions 0 8mm tolerance 3 Identification label Fix the unit securely with the blocks supplied 1 2 3 4 1MN0064 REV 0 1 Control unit 3 Fixing screw...

Страница 9: ...50 60Hz T412 TCK 1 TCK sensor red yellow conductor ASTM E608 regulations 3 Relays L1 L2 FAULT 2 Power supply 24 240Vac cc 50 60Hz Note with the power to the unit ON the FAULT relay switches contacts...

Страница 10: ...itch only when the ALL1 and ALL2 set temperature thresholds are exceeded The FAULT relay switches when the unit is powered and holds till one of the following events takes place Pt100 sensor fault FCC...

Страница 11: ...control unit performs the lamp test and stores the settings END OF PROGRAMMING T412 CODE STEP PRESS EFFECT PRESS NOTES 1 Keep the PRG key pressed until the PRG ON LED lights up Cod is displayed PIN c...

Страница 12: ...the alarm temperature limits is highlighted by the ERR display i e when the L1 limit is higher than the L2 limit for 2 after which L1 is displayed again CORRECTING THE SET VALUES If programming is not...

Страница 13: ...installation of the sensors and above all of the extension cable as stated in the paragraph MEASUREMENT SIGNAL TRANSFER the activation of the FCD function of the control unit as stated in the FCD FUN...

Страница 14: ...CHECKING THE WORK PROGRAM To check the set values of the temperature thresholds L1 and L2 press the PRG button repeatedly instantaneous PROG LED OFF program display set PROG LED ON access to programm...

Страница 15: ...erefore only the quick temperature increase is highlighted Press Reset to delete the FCD warnings and reset the FAULT relay Possible FCD applications Identification of a possible induced disturbance o...

Страница 16: ...s displayed Strong disturbance has damaged the data in the memory See the paragraph Programmed data diagnostics on page 13 The main switch is tripped unexpectedly The temperature is within range Check...

Страница 17: ...17 T412 SERIES TECHNICAL INFORMATION ufficiotecnico tecsystem it SALES INFORMATION info tecsystem it USEFUL CONTACTS...

Отзывы: