12
T412 SERIES
T412 CODE OFF
STEP
PRESS
EFFECT
PRESS
NOTES
1
Keep the PRG key pressed until the PRG-ON LED lights up.
"Cod" is displayed
(PIN code to access programming)
2
Set 375 to proceed
3
The ALL1 (L1) threshold is displayed
2
Set the desired threshold
Default 90°C
3
The ALL2 (L2) threshold is displayed
4
Set the desired threshold
Default 119°C
5
The T°MIN. level is displayed The LED T MIN lights up
6
Set the desired threshold
7
“- - -”
is displayed
8
Select:
Hld
HOLD flag inserted (HOLD LED ON)
“- - -”
flag not inserted (HOLD LED OFF)
Default “- - -”
9
FCD is displayed (only Pt100 model)
10
Set YES or NO
Default "no"
(function excluded)
11
The control unit performs the lamp test and stores the settings
END OF PROGRAMMING
NOTE: the incorrect programming of the alarm temperature limits is highlighted by the "ERR" display (i.e. when
the L1 limit is higher than the L2 limit) for 2", after which L1 is displayed again.
CORRECTING THE SET VALUES
If programming is not carried out within 60", the program resets automatically reverting to the previously stored values and
the channel temperature is displayed.
CHECKING THE WORK PROGRAM
To check the set protection levels, press the PRG key briefly.
By pressing the PRG key repeatedly, all the previously set values are scrolled through in sequence.
After 1 minute's keyboard inactivity, the programming viewing procedure is automatically abandoned.
THERMOMETRIC SENSOR CONNECTION
Each Pt100 thermometric sensor has one white and two red connectors (IEC 751 regulations).
Each TCK temperature sensor has a red (-) and a yellow (+) conductor (ASTM E 608 regulations).
On page 9 you will find the positions on the terminal block of the connecting cables for both models.