NT538 WS EVO

 

 

 

 

               

 

 

 

 
    

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 SAFETY REGULATIONS 

                 
    ATTENTION:  

  
  

Read the manual carefully before starting to use the control unit. Keep the instructions for future reference.  
  
 
                Do not open the device.  Touching any internal components can cause electric shock. Contact with a voltage over 
50 Volts can be fatal. To reduce the risk of electric shock, do not dismantle the back of the device for any reason, furthermore 
opening would invalidate the warranty.   
  

Before connecting the device to the power supply, make sure that all the connections are correct.

 Always disconnect 

the unit from the supply before any cabling modification. 
  
                Any work on the equipment must be entrusted to a qualified engineer. 
  

Failure to comply with these instructions can cause damage, fires or electric shock, and possible serious injuries! 

 
 

POWER SUPPLY

 

The NT538 WS EVO control unit has universal power supply, i.e. it can be supplied by 85 to 260 Vac-Vdc, irrespectively of 
polarity in Vdc. Before using it, make sure the power cable is not damaged, knotted or pinched. Do not tamper with the power 
cable.  Never  disconnect  the  unit  by  pulling  the  cable  and  avoid  touching  the  pins.  Do  not  carry  out  any  operations  of 
connecting/disconnecting with wet hands. To disconnect the device, do not use objects such as levers. Immediately disconnect 
the device if you smell burning or see any smoke: contact assistance. 

 

LIQUIDS   

 

Do not expose the equipment to splashes or drops, do not position it in places with humidity exceeding 90% and never touch 
with wet or damp hands. If any liquid penetrates the control unit, disconnect it immediately and contact technical assistance.   

 

CLEANING

 

Disconnect the power cable before cleaning the control unit, use a dry cloth to dust it, without any solvent or detergents, and 
compressed air. 

 

OBJECTS

 

Never insert any objects into the cracks of the control unit. If this happens, disconnect the control unit and contact an engineer.  

 

USE RESERVED TO QUALIFIED PERSONNEL

 

The purchased goods are a sophisticated electronic device that is completely unsuitable to be used by non-qualified personnel. 
Any work must be carried out by a specialist engineer.  

 

ACCESSORIES

 

The use of non-original accessories or spare parts can damage the unit and endanger users' safety. In the event of faults, 
contact technical service. 

 

LOCATION 

Install the control unit indoors, in a place protected from  water splashes and from  the sun’s rays. Do not place near heat 
sources exceeding the parameters stated in this manual. Position on a stable surface, far away from any possible vibrations. 
Position the unit as far as possible from any intense magnetic fields. 

 

REPAIRS

 

Do not open the control unit. For any fault, always use qualified personnel. The opening of the control unit and/or the removal 
of the series identifying label entails the automatic forfeiture of the warranty. The Warranty seal is applied to all devices, any 
attempt to open the unit would break the seal and cause the consequent automatic forfeiture of the warranty. 

 

BATTERY  

Inside the NT538 WS EVO device there is a lithium manganese dioxide battery. Do not open the control unit; the battery used 
is maintenance-free. Do not expose the device to temperatures above or below the operating range (

 

–20°C to +60°); 

do not 

expose it to fire (risk of explosion). In case of liquid leakage from the product and possible contact with persons (hands, eyes 
or other) or inhalation, contact your doctor immediately. 

 

 
 

FUNCTIONS  
To control the transformer correctly from a temperature point of view, enabling of the VOTING function is permitted 
where the load distributed between the phases of the transformer is adequately balanced.   

 

 
TECHNICAL INFORMATION OR REPORTING INFORMATION 
Mail: [email protected] - tel: 02/4581861  

 
 
 

Содержание NT538 WS

Страница 1: ...th ISO9001 certified quality system http www tecsystem it R 1 1 16 11 2020 INSTRUCTION MANUAL NT538 WS EVO TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 ENGLISH Translations of t...

Страница 2: ...538 WS EVO PROGRAMMING NOTES 14 TEMPERATURE SENSORS 15 MEASUREMENT SIGNAL TRANSFER TEMPERATURE SENSOR DIAGNOSTICS 16 VOTING FUNCTION PROGRAMMED DATA DIAGNOSTICS 17 TEMPERATURE DIAGNOSTICS COOLING FAN...

Страница 3: ...TEM WEB SERVER 21 HOME SCREEN 22 TEMPERATURE AND ALARMS SCREEN SETTINGS SCREEN 23 NETWORK SETTINGS 24 OPTIONS 25 E MAIL SETTINGS 26 TREND CHART SCREEN 27 EVENT LOG SCREEN 28 TREND CHART NOTES 29 CSV F...

Страница 4: ...ir OBJECTS Never insert any objects into the cracks of the control unit If this happens disconnect the control unit and contact an engineer USE RESERVED TO QUALIFIED PERSONNEL The purchased goods are...

Страница 5: ...torque 0 5Nm 1 Terminal 12 pitch poles 5 relays Code 2PL0361 Screw tightening torque 0 5Nm 2 Terminal 12 pitch poles 3 81 sensors Pt100 Code 2PL0430 Screw tightening torque 0 25Nm 1 external Wi Fi SMA...

Страница 6: ...nagement relays SPST FAN1 and FAN2 Wi Fi Connection protocol 802 11 b g n frequency 2 4 GHz with removable external antenna Max 100m in open field DIMENSIONS 100 x 100 mm DIN 43700 prof 150 mm includi...

Страница 7: ...nel 2 ON OFF ventilation thresholds FAN1 and FAN2 in common for all enabled channels Sensor diagnostics Fcc Foc Fcd Data memory diagnostics Ech Access to programming through front keyboard Automatic e...

Страница 8: ...FI green LED 5 FAULT red LED 16 3 digit channel display 6 FAN 1 yellow LED 17 T max mode selection red LED 7 FAN 2 yellow LED 18 Man mode selection yellow LED 8 Display mode selection key 19 Auto mode...

Страница 9: ...asurement circuit The temperature values displayed might be incorrect Return the control unit to TECSYSTEM for repairs 4 Pt Err This message appears when it is detected that one or more PT100 sensors...

Страница 10: ...locks 1 Control unit 2 Panel hole dimensions 0 8 mm tolerance 3 Identification label 1 Control unit 3 Fixing screws 2 Fixing blocks 4 Cross head screwdriver 1X100mm ASSEMBLY 1 1MN0007 REV 0 2 3 1 2 3...

Страница 11: ...N Pt100 CONNECTION EXAMPLE Note before connecting the probes to the control unit carefully read the paragraph measurement signal transfer on page 15 Note image relay contacts in non alarm condition ex...

Страница 12: ...y thermal monitoring moreover the relays will all be disabled The fault contact switches and the fault LED flashes Programming viewing display PRG programming Relay test The ALARM and TRIP relays only...

Страница 13: ...8 Set the desired threshold 9 CH1 FAN YES appears on the display and the Fan1 2 LED flash fan operation info fan control paragraph page 17 10 Select YES FAN1 FAN2 enabled flashing YES only FAN1 enable...

Страница 14: ...g without saving the modified data 3 After 1 minute s keyboard inactivity programming is abandoned without saving the data 4 During programming the control unit does not control protect the monitored...

Страница 15: ...ight line without any winding 7 Any caps used to butt conductors must be crimped properly to avoid false contacts NOTE for correct installation of the probes and the signal transport cable consult the...

Страница 16: ...iability How does VOTING work Using the principle indicated use the installed probes to monitor operation of the controlled electrical machine but at the same time ascertain correct functioning of the...

Страница 17: ...following FAN activation modes dedicated to that channel YES FAN1 FAN2 enabled flashing The selected channel CH n will enable the switching of both contacts FAN1 and FAN2 in relation to the ON OFF th...

Страница 18: ...dentified see paragraph on alarms and ventilation on page 12 If the fail safe function is disabled on the fault contact the control unit will no longer be able to signal the fault due to power failure...

Страница 19: ...on the measurement signal transfer on page 15 Identification of a sensor fault or faulty connection In case of a faulty connection or sensor fault a quick positive or negative variation in temperature...

Страница 20: ...of a digital network key TECSYSTEM in the network key window repeat the operation in the network key confirmation window Click on CONNECT Once the connection is established your device will indicate C...

Страница 21: ...in the Access point functions the device automatically keeps the date and time through a back up battery set at the first start up Accessing the Options page it will be possible to set the date time...

Страница 22: ...the label indication can be customised by the user in the options labels settings screen see page 25 HOME SCREEN The home screen allows the user to identify the cabin and to select the various screen...

Страница 23: ...IN CODE settings and operation on page 29 1 Channel reference and enabling CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 10 Enabling of FAILSAFE FUNCTION Relay ALARM TRIP FAULT 2 Channel FAN 1 Enabling CH1 CH2 CH3...

Страница 24: ...evice is the end user s responsibility The settings of the alarm thresholds and enabling of the functions described in this manual must be checked by a specialist engineer according to the application...

Страница 25: ...nclude FAN ON OFF log records 4 Include TRIP achievement log records Labels 5 Station Name label 10 Label channel 5 6 Label channel 1 11 Label channel 6 7 Label channel 2 12 Label channel 7 8 Label ch...

Страница 26: ...activation events 5 Security flags 11 Periodic e mail report 6 Username 12 Test Mail E mails activation event they represent the predefined events for which to send an e mail notification Selection v...

Страница 27: ...abled channels CH channel selection flag Recording points display flag Enabling the recording points display flag it will be possible to identify each recording in the graph Clicking on the individual...

Страница 28: ...l time clock set to last saved Reset of date and time automatic since the last saving W02 Real time clock manually set Manual date and time setting W03 Diagnostic button pressed The access point butto...

Страница 29: ...UP window will confirm the correct saving PIN CODE default setting 00000 Press BACK to main page to return to the main screen TREND CHART NOTES When the graphs page is opened the last seven days recor...

Страница 30: ...hold exceeded count TRIP threshold exceeded count What is the periodic report for It can be used to automatically receive an update on the operation of the monitored electric machine without wasting a...

Страница 31: ...Sudden trip of the main switch The temperature is on standard levels Just one channel has caused the trip Check the temperatures recorded in T MAX check the indications provided in the paragraphs tra...

Страница 32: ...All the electrical and electronic equipment supplied after 13 August 2005 is marked with this symbol pursuant to European directive 2012 19 EU on electrical and electronic waste WEEE Any electrical or...

Отзывы: