NT539

 

 

 

 

                

 

 

             NT539

 

 

 

 

STEP

 

 

    PRESS

 

 

EFFECT

 

 

   PRESS

 

 

NOTES

 

 

 

 
 

 
 

 

Keep PRG key pressed until PRG led turns on. After PRG 
indication, the transformer (or coils) number that you want 

to check appears. On “channel” display  

 appears NTR 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set the desired number (1-2-3) 

 

 

 

  

  

 

Default  3 

 

 

 

 

 

 

 

 

 

ALARM threshold for CH 1-2-3 is displayed, TR1 

 

 

 

 

Reference to TR1 

 

 

 

 

 

 

 

 

 

Set the desired threshold 

 

 

 

 

 

Default  90°C 

 

 

 

 

 

 

TRIP threshold for CH 1-2-3 is displayed, TR1 

 

 

 

 

 

 

Reference to TR1 

 

 

 

 

 

 

 

 

Set the desired threshold 

 

 

 

 

 

Default  119°C

 

  

 

 

 

 

 

 

                             FAN YES/NO is displayed, TR1  

 

 

 

Forced ventilation 

command. 

Reference to TR1 

 

 

 

 

 

 

 

 

Select desired option YES/NO 

 

 

 

 

 

 

Default YES

 

  
 

 

 

 

 

 

 

 

°C ON is displayed, TR1 

 

 

 

 

 

 

 

FAN turning on 

 

 

 

 

 

 

 

 

10 

 

 

 
 

Set the desired threshold 

 

 

 

 

 

Default  70°C   

 

 

 

 

11 

 

 

°C OFF is displayed, TR1 

  

 

 

 

 

 

 

FAN turning off 

 

 

 

 

 

 

12 

 

 

 

Set the desired threshold 

 

 

 

 

 

Default 60°C  

 

 

 

 

 

 

 

 

 

Repeat steps from 3 to 12 to program TR2 and TR3 

thresholds (if enabled at point 2) 

 

 

 

 

 

   

 

 

13 

 

      

D

isplay shows FCD <> “datum” 

 

 

         

 

 

Fault for temperature fast 

increase (°C/sec) 

 

 

 

 

 

14 

 

 

Set the desired value 

(see page 16) 

 

 

 

 

 

Default  No  

no = excluded function  

from No to 30 °C/sec 

 

 

 

 

 

 

 

15 

 

                                                     

                                                              

Display shows HFN (only if FAN YES) 

 

 

Fan cyclic test for 5 minutes 

each “n” hours 

 

 

 

      16 

 

 

 

Set the desired number of hours 

 

 

 

   

 

 

Default NO 

no= disabled function 

 

 

 

 

 

 

 

 

17 

 

 

          

  

Display shows 

REL 

 

 

 

 

 

Select outputs relays 

common or independent 

 

 

 

  

 

 

 

18 

 

 

Select desired option 

 

 

 

 

 

Set COM or IND 

Default  COM 

 

 

 

 

 

 

 

PROGRAMMING  

Содержание 1MN0143

Страница 1: ...1 certified quality system http www tecsystem it R 1 2 26 11 20 Translations of the original instructions ENGLISH TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 NT539 INSTRUCTION...

Страница 2: ...Y 8 OPERATING PROGRAM CONTROL LED TEST ALARM RELAY TEST ALARM RELAY SILENCING 5 MOUNTING 9 6 ELECTRICAL CONNECTIONS 10 ELECTRICAL CONNECTIONS NT539 POWER SUPPLY 11 ALARMS AND VENTILATION 7 PROGRAMMING...

Страница 3: ...exceeding 90 and never touch with wet or humid hands If any liquid penetrates the control unit disconnect it immediately and contact technical service CLEANING Disconnect the power cable before cleani...

Страница 4: ...oles pitch 5 Code 2PL0372 Screws tightening torque 0 5Nm 2 relay terminals 9 poles pitch 5 Code 2PL0376 Screws tightening torque 0 5Nm 3 Pt100 sensor terminals 12 poles pitch 3 5 Code 2PL0375 Screws t...

Страница 5: ...T 3 relays of trip TRIP TR1 TRIP TR2 TRIP TR3 SPDT 3 relays of fan FAN TR1 FAN TR2 FAN TR3 SPDT 1 sensor or operating failure FAULT relay SPDT Output relay with 6A 250Vac res COS 1 contacts DIMENSIONS...

Страница 6: ...o displayed channel FAULT FAN ALARM TRIP 3 LED s to show the transformer TR1 TR2 TR3 Temperature control from 0 C to 200 C 2 alarm thresholds ALARM TRIP for each transformer 1 fan threshold ON OFF for...

Страница 7: ...3 digit temperature display 15 3 digit channel display 6 Scan mode selection yellow LED 16 TR 3 red LED 7 Auto mode selection green LED 17 Enter Reset button 8 Man mode selection yellow LED 18 TR 2 r...

Страница 8: ...button LED TEST We suggest carrying out the control unit LED test regularly For this operation press the TEST key briefly all the displays turn on for 2 seconds If one of the LEDS does not work please...

Страница 9: ...1MN0142 REV 0 1 Control unit 2 Panel hole dimensions 0 8mm tolerance 3 Identification label Fix the unit securely with the blocks supplied 1 2 3 4 1MN0144 REV 0 1 Control unit 3 Fixing screw 2 Fixing...

Страница 10: ...64 open NO contacts 63 64 closed NC fault condition identification Read the Alarms and Ventilation paragraph on page 11 and see the fault contact switching RELAY Pt100 CONNECTION EXAMPLE ELECTRICAL CO...

Страница 11: ...he relays are all blocked the fault contact switches and the fault LED flashes Vis programming display PRG programming Relay test The ALARM and TRIP relays switch only when the set temperature thresho...

Страница 12: ...o TR1 8 Select desired option YES NO Default YES 9 C ON is displayed TR1 FAN turning on 10 Set the desired threshold Default 70 C 11 C OFF is displayed TR1 FAN turning off 12 Set the desired threshold...

Страница 13: ...relay switches until the unit is fully restarted 5 If pressing ENT Err appears it means that one of the following mistakes has been made ERR ALL ALARM TRIP ALARM AND TRIP LEDS FLASHING ERR FAN FAN OFF...

Страница 14: ...crimped properly to avoid false contacts NOTE to install the sensors and signal transferring cable correctly read the SCS SENSOR installation rules manual What may happen when installation rules are n...

Страница 15: ...ected channel CHn lights up When the trip temperature threshold is exceeded the TRIP relay switches and the TRIP LED of the interested channel CHn lights up As soon as the temperature goes back to val...

Страница 16: ...t100 sensor line can cause false readings or anomalous alarms Setting the FCD function in a temperature range of between 1 C and 10 C 5 C recommended the effects caused by false readings can be suppre...

Страница 17: ...T100 sensors are in FCC Incorrect sensor connection the terminal block has been inserted upside down Check the connections and the terminal board The temperature shown by one or more channels is wrong...

Страница 18: ...18 NT539 TECHNICAL INFORMATION ufficiotecnico tecsystem it COMMERCIAL INFORMATION info tecsystem it USEFUL CONTACTS...

Отзывы: