TECSYSTEM 1MN0143 Скачать руководство пользователя страница 11

11 

NT539

 

 

 

 

 

POWER SUPPLY

 

 

The NT539  has UNIVERSAL power supply, i.e. it can be supplied by 24 to 240 Vac-Vdc, 50/60Hz irrespectively of  
polarity in Vdc (terminals 40-42).  

This is obtained thanks to the use of a tested power supply unit, newly designed and manufactured, that frees installers 
from worrying about the correct Vac and Vdc supply. 

 

The ground must always be connected to terminal 41. 

When  the  unit  is  supplied  directly  by  the  secondary  of  the  transformer  to  protect,  it  can  be  burnt  out  by  strong 
overvoltages. 
This happens if the main switch is closed and the transformer has no load (blank test). The above-mentioned problems 
are much more evident when the 220 Vac voltage is taken directly from the transformer secondary bars and there is a  
 

 
           
 

 
 

If  an  existing  control  unit  must  be  replaced  with  a  new  one,  to  guarantee  its  correct  and  safe  operation,  the 
sensor/relay/supply connecting terminals must be replaced with the new terminals supplied.

 

 

ALARMS AND VENTILATION

 

Carry out the electrical connections on the removable terminal blocks only after disconnecting them from the unit. 
When the control unit is in one of the modes mentioned below, it does not monitor the temperature and the relays 
are all blocked, the fault contact switches and the fault LED flashes. 

 

 

Vis. programming display 

 

PRG programming 

 

Relay test 

 

The ALARM and TRIP relays switch only when the set temperature thresholds are exceeded. 

The FAULT contact switches when the equipment is powered only if the unit detects no fault on start up, and stays in 
this condition until one of the following events occurs: 

 

 

Data storage fault (Ech message). 

 

Pt100 sensor fault (FCC short-circuited sensor, FOC interrupted sensor or Fcd quick temperature 
increase)  

 

CAL damage to the measurement circuit. 

 

Insufficient supply voltage. 

 

During the power on reset after programming (PRG), displaying the data (VIS) and Test relay. 

       

NOTE: do not connect the FAULT relay to the transformer tripping circuit to avoid unwanted system interruptions 

                       FAULT CONTACT SWITCHING  

 

 

 

 

 

 

 

 
 

The  FAN  contact  can  be  used  to  control  the  cooling  fans,  or  it  can  be  included  in  the  conditioning  system  of  the 
transformer room, see paragraph Fan control on page 15. 

 

NOTE: always disconnect the unit before performing any electrical connections. 

 

 
 
 
 
 
 
 

FAULT  63-64 NC: ALARM FAULT OR POWER 

OFF 

 

 

 

FAULT  63-64 NO: POWER ON  - NO FAULT 

 

 

 

To  protect  the  monitoring  device  from  line  overvoltages,  we  suggest  you  use  the  PT-73-  220  electronic 
discharger,  designed  by  TECSYSTEM  S.r.l.  for  this  specific  purpose.

 

As  an  alternative  we  suggest  using  110 

Vac or, even better, 110 Vdc supply voltages.

 

 

Содержание 1MN0143

Страница 1: ...1 certified quality system http www tecsystem it R 1 2 26 11 20 Translations of the original instructions ENGLISH TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 NT539 INSTRUCTION...

Страница 2: ...Y 8 OPERATING PROGRAM CONTROL LED TEST ALARM RELAY TEST ALARM RELAY SILENCING 5 MOUNTING 9 6 ELECTRICAL CONNECTIONS 10 ELECTRICAL CONNECTIONS NT539 POWER SUPPLY 11 ALARMS AND VENTILATION 7 PROGRAMMING...

Страница 3: ...exceeding 90 and never touch with wet or humid hands If any liquid penetrates the control unit disconnect it immediately and contact technical service CLEANING Disconnect the power cable before cleani...

Страница 4: ...oles pitch 5 Code 2PL0372 Screws tightening torque 0 5Nm 2 relay terminals 9 poles pitch 5 Code 2PL0376 Screws tightening torque 0 5Nm 3 Pt100 sensor terminals 12 poles pitch 3 5 Code 2PL0375 Screws t...

Страница 5: ...T 3 relays of trip TRIP TR1 TRIP TR2 TRIP TR3 SPDT 3 relays of fan FAN TR1 FAN TR2 FAN TR3 SPDT 1 sensor or operating failure FAULT relay SPDT Output relay with 6A 250Vac res COS 1 contacts DIMENSIONS...

Страница 6: ...o displayed channel FAULT FAN ALARM TRIP 3 LED s to show the transformer TR1 TR2 TR3 Temperature control from 0 C to 200 C 2 alarm thresholds ALARM TRIP for each transformer 1 fan threshold ON OFF for...

Страница 7: ...3 digit temperature display 15 3 digit channel display 6 Scan mode selection yellow LED 16 TR 3 red LED 7 Auto mode selection green LED 17 Enter Reset button 8 Man mode selection yellow LED 18 TR 2 r...

Страница 8: ...button LED TEST We suggest carrying out the control unit LED test regularly For this operation press the TEST key briefly all the displays turn on for 2 seconds If one of the LEDS does not work please...

Страница 9: ...1MN0142 REV 0 1 Control unit 2 Panel hole dimensions 0 8mm tolerance 3 Identification label Fix the unit securely with the blocks supplied 1 2 3 4 1MN0144 REV 0 1 Control unit 3 Fixing screw 2 Fixing...

Страница 10: ...64 open NO contacts 63 64 closed NC fault condition identification Read the Alarms and Ventilation paragraph on page 11 and see the fault contact switching RELAY Pt100 CONNECTION EXAMPLE ELECTRICAL CO...

Страница 11: ...he relays are all blocked the fault contact switches and the fault LED flashes Vis programming display PRG programming Relay test The ALARM and TRIP relays switch only when the set temperature thresho...

Страница 12: ...o TR1 8 Select desired option YES NO Default YES 9 C ON is displayed TR1 FAN turning on 10 Set the desired threshold Default 70 C 11 C OFF is displayed TR1 FAN turning off 12 Set the desired threshold...

Страница 13: ...relay switches until the unit is fully restarted 5 If pressing ENT Err appears it means that one of the following mistakes has been made ERR ALL ALARM TRIP ALARM AND TRIP LEDS FLASHING ERR FAN FAN OFF...

Страница 14: ...crimped properly to avoid false contacts NOTE to install the sensors and signal transferring cable correctly read the SCS SENSOR installation rules manual What may happen when installation rules are n...

Страница 15: ...ected channel CHn lights up When the trip temperature threshold is exceeded the TRIP relay switches and the TRIP LED of the interested channel CHn lights up As soon as the temperature goes back to val...

Страница 16: ...t100 sensor line can cause false readings or anomalous alarms Setting the FCD function in a temperature range of between 1 C and 10 C 5 C recommended the effects caused by false readings can be suppre...

Страница 17: ...T100 sensors are in FCC Incorrect sensor connection the terminal block has been inserted upside down Check the connections and the terminal board The temperature shown by one or more channels is wrong...

Страница 18: ...18 NT539 TECHNICAL INFORMATION ufficiotecnico tecsystem it COMMERCIAL INFORMATION info tecsystem it USEFUL CONTACTS...

Отзывы: