NT935 ETH

 

 

 

 

 
 
         
 
 
 
 
                                                                                                      
 
 
 
                                                                                                       
 

              
       
 
 
 
 
 
 
 
 
 
 
 
 

 

TROUBLESHOOTING 

 

CAUSES AND 

SOLUTIONS

 

The  control  unit  does  not  switch  on  and  the 
supply to terminals 40-42 is correct. 

Check that: the connector is correctly inserted into its housing, the 
wires  are  tightened,  there  is  no  evidence  of  burning  on  the 
connectors. Disconnect the power supply, carry out the above and 
reconnect. 

CH4 is in FAULT because of FOC  
(only the 3 Pt100 sensors are connected) 

Programming error of the CH4 / YES control unit. 

Check and repeat 

programming as per page 13-14, select CH4 / NO.

 

One of the three/four channels is in FAULT due 
to FOC/FCC 

Check the connections of the Pt100 sensors, check the instructions 
given  in  the  paragraphs: 

measurement  signal  transfer  and 

temperature sensor diagnostics on page 14-15.

 

When turning on, the display shows 

“ECH” 

Strong interference damaged  the  stored  data. See the paragraph 
Programmed data diagnostics on page 16.  

All the PT100 sensors are in FCC. 

Incorrect  sensor  connection,  the  terminal  block  has  been  inserted 
upside down. 

Check the connections and the terminal board.

 

The  temperature  shown  by  one  or  more 
channels is wrong. 

Contact the 

TECSYSTEM Technical Department.

 

Sudden trip of the main switch. The temperature 
is  on  standard  levels.  Just  one  channel  has 
caused the trip. 

Check the temperatures recorded in T-MAX, check the instructions 
given  in  the  paragraphs: 

measurement  signal  transfer  and 

temperature  sensor  diagnostics  on  page  16.  Activate  the  FCD 
function.

 

FCD warning  

See the FCD function on page 31. 

Contact 

TECSYSTEM Technical Department if the problem persists.

 

European  directives  2012/19/EC  (WEEE)  and  2011/65/EC  (RoHS)  have  been  approved  to  reduce  electrical  and 
electronic waste and promote the recycling and reuse of the materials and components of said equipment, cutting down 
on the disposal of the residues and harmful components of electrical and electronic materials. 
   

All the electrical and electronic equipment supplied after 13 August 2005 is marked with this symbol, pursuant to 
European  directive  2002/96/EEC  on  electrical  and  electronic  waste  (WEEE).  Any  electrical  or  electronic 
equipment marked with this symbol must be disposed of separately from normal domestic waste. 

  
Returning  used  electrical  devices:  contact  TECSYSTEM  or  your  TECSYSTEM  agent  for  information  on  the  correct 
disposal of the devices. 
  
TECSYSTEM is aware of the impact its products have on the environment and asks its customers active support in the 
correct and environmentally-friendly disposal of its devices. 

  
 

TECHNICAL INFORMATION 

:  [email protected] 

  

SALES INFORMATION 

[email protected]   

  

  
  
  
 

EQUIPMENT DISPOSAL 

USEFUL CONTACTS  

Содержание 1CN0134

Страница 1: ...with ISO9001 certified quality system http www tecsystem it R 1 5 06 09 17 Translations of the original instructions TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 NT935 ETH INST...

Страница 2: ...35 ETH PROGRAMMING NOTES 14 TEMPERATURE SENSORS 15 MEASUREMENT SIGNAL TRANSFER TEMPERATURE SENSOR DIAGNOSTICS 16 VOTING FUNCTION PROGRAMMED DATA DIAGNOSTICS TEMPERATURE DIAGNOSTICS COOLING FAN CONTROL...

Страница 3: ...19 ERROR CODES UNACCEPTABLE DATA ILLEGAL DATA 20 MODBUS MAPPING TABLE 9 FAIL SAFE FUNCTION 25 10 ETHERNET MODULE PARAMETER PROGRAMMING 26 ETH0 CONNECTIONS TELNET ENABLING 27 TELNET SCREEN IP PARAMETER...

Страница 4: ...during storms If any liquid penetrates the control unit disconnect immediately and contact technical service CLEANING Disconnect the power cable before cleaning the control unit using a dry cloth wit...

Страница 5: ...ws tightening torque 0 5Nm 1 relay terminal 12 poles pitch 5 Code 2PL0361 Screws tightening torque 0 5Nm 1 Pt100 sensors terminal 12 poles pitch 3 81 Code 2PL0420 Screws tightening torque 0 25Nm ACCES...

Страница 6: ...FAULT relay SPST Output relays with 10A 250Vac res COS 1 contacts 2 ventilation management relays SPST FAN 1 AND FAN 2 Ethernet output 10Base T 100Base TX Modbus TCP slave DIMENSIONS 100x100 mm din437...

Страница 7: ...N2 Temperature control from 0 C to 240 C 2 alarm thresholds for channels 1 2 3 2 alarm thresholds for channel 4 2 ON OFF thresholds for FAN 1 and FAN 2 Sensor diagnostics Fcc Foc Fcd Data memory diagn...

Страница 8: ...LED 5 FAULT red LED 16 3 digit channel display 6 FAN 1 yellow LED 17 T max mode selection red LED 7 FAN 2 yellow LED 18 Man mode selection yellow LED 8 Display mode selection key 19 Auto mode selecti...

Страница 9: ...the measurement circuit The temperature values displayed might be incorrect Return the control unit to TECSYSTEM for repairs 4 Pt Err This message appears when it is detected that one or more PT100 s...

Страница 10: ...lied 1 Control unit 2 Panel hole dimensions 0 8mm tolerance 3 Identification label 1 Control unit 3 Fixing screw 2 Fixing block 4 Cross head screwdriver 1X100mm MOUNTING 1 1MN0007 REV 0 2 3 1 2 3 4 1M...

Страница 11: ...ts COS 1 STOP SYSTEM ALARM CONDITION AUDIO AND VISUAL INDICATION Pt100 CONNECTION EXAMPLE Note before connecting the sensors to the control unit read the Measurement signal transfer paragraph on page...

Страница 12: ...t does not monitor the temperature and the relays are all blocked The fault contact switches and the fault LED flashes Vis programming display PRG Programming Relay test The ALARM and TRIP relays swit...

Страница 13: ...INT If you select INT read the function notes on page 17 8 CH4 is displayed CH4 enabling 9 Set YES or NO with YES CH4 is enabled with NO CH4 is disabled 10 The ALARM threshold for CH4 is displayed the...

Страница 14: ...ES or NO Default YES 36 END is displayed End of programming 37 Press ENT to save the set data and exit programming Err incorrect programming of the LED values note 6 38 Return to step 1 PROGRAMMING NO...

Страница 15: ...n a straight line without any winding 7 Any caps used to butt conductors must be crimped properly to avoid false contacts NOTE to install the sensors and signal transferring cable correctly read the S...

Страница 16: ...unit compares the temperature values recorded on the monitored CH1 CH2 CH3 channels and enables the switching of the TRIP contact only if the TRIP threshold has been exceeded on at least two channels...

Страница 17: ...their control apparatus periodically By setting NO this function is inhibited To enable the HFN function read the programming section on pages 13 14 INTELLIFAN FUNCTION What it is used for The Intell...

Страница 18: ...those in the paragraph regarding the remote programming notes The ETH module is always in slave mode The NT935 ETH control unit is in communication with the network only when it is in temperature read...

Страница 19: ...n and the data packet is refused in full The code of the first wrong datum can be requested reading the Datum error received register NB this code is lost during RESET switching on or data writing in...

Страница 20: ...ramming errors because they are wrong settings in this case the error code is ILLEGAL_DATA This information is accessible to ModBus reading the register 7 NO ERROR CH_1 Trip Alarm CH_4 Trip Alarm FAN_...

Страница 21: ...el for 4 20 mA 0 hot 1 4 ch1 4 5 scan RW Only for AD version 17 00 Address Modbus address 1 255 R 18 00 Bdr Modbus baud rate 0 2400 1 4800 2 9600 3 19200 4 38400 R 19 00 Parity Modbus parity bit 0 N 1...

Страница 22: ...h2 temper alarm set point 1 C 240 C 1 C 200 C As AL R 32 2 compl sign 2 compl Ch2 temper trip set point 1 C 240 C 1 C 200 C As TRP R 33 2 compl sign 2 compl Ch3 temper 10 C 240 C 48 C 200 C R 34 2 com...

Страница 23: ...h1 Setting See Note CHx RW 58 00 Ch2 Setting See Note CHx RW 59 00 Ch3 Setting See Note CHx RW 60 00 Ch4 Setting See Note CHx RW 61 00 00 R 62 00 00 R 63 00 00 R 64 00 00 R 48 00 00 R 49 00 00 R 50 00...

Страница 24: ...00 R 70 00 00 R 71 00 00 R 72 00 00 R INFO various causes READ BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 RESET R has taken place COMMANDS WRITE BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 R...

Страница 25: ...ature Setting YES Fail Safe normally closed contacts are in positions 5 7 Alarm and 8 10 Trip they switch only when limits are reached preset temperature FAULT Setting YES Fail safe the contact 11 12...

Страница 26: ...net program to set the Ethernet IP parameters 1 START menu Windows If already enabled the program appears 2 Start the search with the Telnet program Press ENTER to launch the program Entering telnet i...

Страница 27: ...restart the PC if required 9 START menu Windows 10 Search for the Telnet program 15 Enter 192 168 10 120 9999 16 Press ENTER 12 TELNET SCREEN 11 Press ENTER to launch the program 13 Enter OPEN 14 Pre...

Страница 28: ...e modified by the operator 2 Communication parameters between the ETH0 port and the control unit 3 Communication configuration between the ETH0 port and the control unit 4 Communication advanced setti...

Страница 29: ...p 2 Enter the desired new Gateway IP address press ENTER if you wish to keep the set address press ENTER 4 times At the end of the operation the system will ask if you wish to modify Netmask Enter Y t...

Страница 30: ...me retardant PVC sheath 9 External diameter 12mm 10 Standard conformation in 100m coils To check the programmed parameters or repeat programming follow the TELNET SCREEN from step 12 to step 19 page 2...

Страница 31: ...nt signal transfer on page 15 Identification of a sensor fault or faulty connection In case of a faulty connection or sensor fault a quick positive or negative variation in temperature might occur lea...

Страница 32: ...rd levels Just one channel has caused the trip Check the temperatures recorded in T MAX check the instructions given in the paragraphs measurement signal transfer and temperature sensor diagnostics on...

Страница 33: ...ASS OF THE EQUIPMENT 0 45 Kg INPUT SUPPLY 100 240 Vac Vdc 10 50 60 Hz 7 5VA max PROTECTION External switch or circuit breaker OUTPUTS RELAYS 5 relay output 10A 250Vac res COS 1 PORT Ethernet Suitable...

Отзывы: