NT935 ETH

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

TEMPERATURE SENSOR DIAGNOSTICS 

  
In case of failure or exceeded full scale value of one of the thermometric sensors installed on the machine to protect, the 
FAULT relay opens immediately with the relative warning of faulty sensor on the corresponding channel (PT err). 
  

Fcc indicates sensor short-circuited or minimum full scale value of the control unit exceeded -8°C (version 0°÷240°C) 
and -48°C (version -40°C÷200°C) 
 
Foc indicates sensor interrupted or maximum full scale value of the control unit exceeded 243°C (version 0°÷240°C) 
and 203°C (version -40°C÷200°C) 
 

 To eliminate the message and reset the opening of the Fault contact, it is necessary to check the Pt100 connections and 
replace  the  faulty  sensor  (if  any).    If  the  minimum/maximum  full  scale  value  has  been  reached,  check  that  the  ambient 
conditions match the control unit reading.  
  
Note:  exceeding  the  minimum/maximum  full  scale  value  can  also  be  caused  by  interference  on  the  sensor  lines;  in  this 
case we recommend that you check: 
 

 

the correct installation of the sensors and above all of the extension cable (as stated in the paragraph MEASUREMENT 
SIGNAL TRANSFER)  
the activation of: VOTING (see below) or FCD (see page 31) according to the conditions of the system. 
  
CAL message  display: it  appears  when  damage  is  found  in  the measurement  circuit.  The temperature  values  displayed 
might be incorrect. Return the control unit to TECSYSTEM for repairs. 
  
 
  

VOTING FUNCTION 

  

The  voting  function  derives  from  the  redundancy  concept  that  consists  in  duplicating  the  components  of  a  system  to 
increase their 

reliability

  

How does VOTING work?   

Using  the  redundancy  principle,  we  use  the  sensors  installed  on  the  three  phases  U-V-W  to  monitor  the  transformer's 
operation,  and  at  the  same  time  ascertain  the  sensors  are  working  correctly,  discriminating  against  any  false  alarms 
(generated by installation errors).  
  

  

By  activating the 

VOTING  "YES"

  function,  the control  unit compares  the  temperature  values  recorded  on  the monitored 

CH1-CH2-CH3 channels and enables the switching of the 

TRIP

 contact only if the 

TRIP

 threshold has been exceeded on 

at least two channels over the same period T.   
  
By selecting 

VOTING 

“NO”

 the function will be disabled.  

  
Note:  by  setting  Voting  "Yes"  the  switching  of  the 

ALARM   

contact  will  anyway  indicate  the  alarm  threshold  on  each 

individual channel has been exceeded. 
  
To enable the Voting function, read the programming section on pages 13-14. 
 

 

Attention: To control the transformer correctly from a temperature point of view, enabling the VOTING 
function  is  allowed  where  the  load  distributed  between  the  phases  of  the  transformer  is  adequately 
balanced. In addition, any conditions of FAULT: FCC-FCC-FCD on two or more channels, with active 
voting, can determine the TRIP contact inhibition. 

 

PROGRAMMED DATA DIAGNOSTICS 

 

In case of failure of the internal memory or corruption of programmed data, just  after switching on, 

Ech

 appears with the 

relevant Fault contact. 
In this case, for safety reasons, the default parameters are loaded automatically (see programming table on pages 13-14). 
Eliminate 

Ech

 by pressing RESET and run programming to enter the desired values. 

Finally switch the unit off and back on to check the memory works correctly, if it is damaged 

Ech

 will be displayed again 

(send the control unit to TECSYSTEM srl for repairs). 

  
 

TEMPERATURE DIAGNOSTICS 

 

When  one  of  the  temperature  sensors  senses  a  temperature  1°C  higher  than  the  alarm  threshold,  5  seconds  later  the 

ALARM

 relay switches and the 

ALARM

 LED of the affected channel (CH

n

) lights up. 

When  the  trip  temperature  limit  is  exceeded,  the 

TRIP

  relay  switches  and  the 

TRIP

  LED  of  the  affected  channel  (CH

n

lights up. 
As soon as the recorded temperature returns to values equal to or lower than the limit set for the 

ALARM

 and 

TRIP

 relays 

switching, these relays de-energise and the corresponding LEDs switch off. 
The 

ALARM

  and 

TRIP

  values  are  kept  in  the  internal  memory:  they  can  be  recalled  by  entering  the  Vis  modes 

(programmed parameter display) and modified in PRG (programming) mode.

 

  
 

Содержание 1CN0134

Страница 1: ...with ISO9001 certified quality system http www tecsystem it R 1 5 06 09 17 Translations of the original instructions TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 NT935 ETH INST...

Страница 2: ...35 ETH PROGRAMMING NOTES 14 TEMPERATURE SENSORS 15 MEASUREMENT SIGNAL TRANSFER TEMPERATURE SENSOR DIAGNOSTICS 16 VOTING FUNCTION PROGRAMMED DATA DIAGNOSTICS TEMPERATURE DIAGNOSTICS COOLING FAN CONTROL...

Страница 3: ...19 ERROR CODES UNACCEPTABLE DATA ILLEGAL DATA 20 MODBUS MAPPING TABLE 9 FAIL SAFE FUNCTION 25 10 ETHERNET MODULE PARAMETER PROGRAMMING 26 ETH0 CONNECTIONS TELNET ENABLING 27 TELNET SCREEN IP PARAMETER...

Страница 4: ...during storms If any liquid penetrates the control unit disconnect immediately and contact technical service CLEANING Disconnect the power cable before cleaning the control unit using a dry cloth wit...

Страница 5: ...ws tightening torque 0 5Nm 1 relay terminal 12 poles pitch 5 Code 2PL0361 Screws tightening torque 0 5Nm 1 Pt100 sensors terminal 12 poles pitch 3 81 Code 2PL0420 Screws tightening torque 0 25Nm ACCES...

Страница 6: ...FAULT relay SPST Output relays with 10A 250Vac res COS 1 contacts 2 ventilation management relays SPST FAN 1 AND FAN 2 Ethernet output 10Base T 100Base TX Modbus TCP slave DIMENSIONS 100x100 mm din437...

Страница 7: ...N2 Temperature control from 0 C to 240 C 2 alarm thresholds for channels 1 2 3 2 alarm thresholds for channel 4 2 ON OFF thresholds for FAN 1 and FAN 2 Sensor diagnostics Fcc Foc Fcd Data memory diagn...

Страница 8: ...LED 5 FAULT red LED 16 3 digit channel display 6 FAN 1 yellow LED 17 T max mode selection red LED 7 FAN 2 yellow LED 18 Man mode selection yellow LED 8 Display mode selection key 19 Auto mode selecti...

Страница 9: ...the measurement circuit The temperature values displayed might be incorrect Return the control unit to TECSYSTEM for repairs 4 Pt Err This message appears when it is detected that one or more PT100 s...

Страница 10: ...lied 1 Control unit 2 Panel hole dimensions 0 8mm tolerance 3 Identification label 1 Control unit 3 Fixing screw 2 Fixing block 4 Cross head screwdriver 1X100mm MOUNTING 1 1MN0007 REV 0 2 3 1 2 3 4 1M...

Страница 11: ...ts COS 1 STOP SYSTEM ALARM CONDITION AUDIO AND VISUAL INDICATION Pt100 CONNECTION EXAMPLE Note before connecting the sensors to the control unit read the Measurement signal transfer paragraph on page...

Страница 12: ...t does not monitor the temperature and the relays are all blocked The fault contact switches and the fault LED flashes Vis programming display PRG Programming Relay test The ALARM and TRIP relays swit...

Страница 13: ...INT If you select INT read the function notes on page 17 8 CH4 is displayed CH4 enabling 9 Set YES or NO with YES CH4 is enabled with NO CH4 is disabled 10 The ALARM threshold for CH4 is displayed the...

Страница 14: ...ES or NO Default YES 36 END is displayed End of programming 37 Press ENT to save the set data and exit programming Err incorrect programming of the LED values note 6 38 Return to step 1 PROGRAMMING NO...

Страница 15: ...n a straight line without any winding 7 Any caps used to butt conductors must be crimped properly to avoid false contacts NOTE to install the sensors and signal transferring cable correctly read the S...

Страница 16: ...unit compares the temperature values recorded on the monitored CH1 CH2 CH3 channels and enables the switching of the TRIP contact only if the TRIP threshold has been exceeded on at least two channels...

Страница 17: ...their control apparatus periodically By setting NO this function is inhibited To enable the HFN function read the programming section on pages 13 14 INTELLIFAN FUNCTION What it is used for The Intell...

Страница 18: ...those in the paragraph regarding the remote programming notes The ETH module is always in slave mode The NT935 ETH control unit is in communication with the network only when it is in temperature read...

Страница 19: ...n and the data packet is refused in full The code of the first wrong datum can be requested reading the Datum error received register NB this code is lost during RESET switching on or data writing in...

Страница 20: ...ramming errors because they are wrong settings in this case the error code is ILLEGAL_DATA This information is accessible to ModBus reading the register 7 NO ERROR CH_1 Trip Alarm CH_4 Trip Alarm FAN_...

Страница 21: ...el for 4 20 mA 0 hot 1 4 ch1 4 5 scan RW Only for AD version 17 00 Address Modbus address 1 255 R 18 00 Bdr Modbus baud rate 0 2400 1 4800 2 9600 3 19200 4 38400 R 19 00 Parity Modbus parity bit 0 N 1...

Страница 22: ...h2 temper alarm set point 1 C 240 C 1 C 200 C As AL R 32 2 compl sign 2 compl Ch2 temper trip set point 1 C 240 C 1 C 200 C As TRP R 33 2 compl sign 2 compl Ch3 temper 10 C 240 C 48 C 200 C R 34 2 com...

Страница 23: ...h1 Setting See Note CHx RW 58 00 Ch2 Setting See Note CHx RW 59 00 Ch3 Setting See Note CHx RW 60 00 Ch4 Setting See Note CHx RW 61 00 00 R 62 00 00 R 63 00 00 R 64 00 00 R 48 00 00 R 49 00 00 R 50 00...

Страница 24: ...00 R 70 00 00 R 71 00 00 R 72 00 00 R INFO various causes READ BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 RESET R has taken place COMMANDS WRITE BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 R...

Страница 25: ...ature Setting YES Fail Safe normally closed contacts are in positions 5 7 Alarm and 8 10 Trip they switch only when limits are reached preset temperature FAULT Setting YES Fail safe the contact 11 12...

Страница 26: ...net program to set the Ethernet IP parameters 1 START menu Windows If already enabled the program appears 2 Start the search with the Telnet program Press ENTER to launch the program Entering telnet i...

Страница 27: ...restart the PC if required 9 START menu Windows 10 Search for the Telnet program 15 Enter 192 168 10 120 9999 16 Press ENTER 12 TELNET SCREEN 11 Press ENTER to launch the program 13 Enter OPEN 14 Pre...

Страница 28: ...e modified by the operator 2 Communication parameters between the ETH0 port and the control unit 3 Communication configuration between the ETH0 port and the control unit 4 Communication advanced setti...

Страница 29: ...p 2 Enter the desired new Gateway IP address press ENTER if you wish to keep the set address press ENTER 4 times At the end of the operation the system will ask if you wish to modify Netmask Enter Y t...

Страница 30: ...me retardant PVC sheath 9 External diameter 12mm 10 Standard conformation in 100m coils To check the programmed parameters or repeat programming follow the TELNET SCREEN from step 12 to step 19 page 2...

Страница 31: ...nt signal transfer on page 15 Identification of a sensor fault or faulty connection In case of a faulty connection or sensor fault a quick positive or negative variation in temperature might occur lea...

Страница 32: ...rd levels Just one channel has caused the trip Check the temperatures recorded in T MAX check the instructions given in the paragraphs measurement signal transfer and temperature sensor diagnostics on...

Страница 33: ...ASS OF THE EQUIPMENT 0 45 Kg INPUT SUPPLY 100 240 Vac Vdc 10 50 60 Hz 7 5VA max PROTECTION External switch or circuit breaker OUTPUTS RELAYS 5 relay output 10A 250Vac res COS 1 PORT Ethernet Suitable...