P. 8
LX-(Q)-GSM / LX-(Q)-NET Techn. Docum. + Installation
01-2016
INITIAL SETUP
The initial setup is carried out after completed mounting.
Determine the tank data and enter them into the mode:
You find
3 push buttons
(blue) on the PCB positioned between the connection clamps.
Press ENTER => Device enters the setup mode
Displayed step „1. Measur probe“
You can step through the menu items by pressing PLUS or MINUS.
Press ENTER to step into a sub-menu.
Press PLUS or MINUS for selection; press ENTER to confirm.
After completing Step 7 you reach „8. Exit“.
Press ENTER to exit the setup mode:
The device returns to the display mode and shows the current stock.
You find additional setup options in step 9 to 24, reachable by pressing PLUS.
Setup / Programming :
You find the complete documentation of the setup in the enclosed leaflet,
refer to
Setup and Operation