2-3 Product Specifications 

Items 

Description 

Input 

Rated Voltage, 

Frequency 

Single/Three-phase    220V- 50/60Hz 
Three-phase    380V-50/60Hz 

Allowable Voltage    170~240V,    330~440V 

Output 

Allowable Voltage  170~240V,    330~440V 

Frequency 

0.10~400.0Hz   

Control Mode 

V/F control   

Display 

Five-digit LED display, Indicator display; 
Display setup frequency, Output frequency, 
Output current, DC voltage, Module 
temperature, Running state, and fault 

C

o

n

tr

o

l F

u

n

ct

io

n

 

Frequency Setup   

Digital setting: 0.01 Hz. Analog setup: 0.1% 
of maximum output frequency   

Frequency 

Accuracy 

0.1Hz   

V/F Control 

Changeable V/F curve by setting 

Torque Control 

Auto  raising  torque  by  loading  condition; 
Manual  increase:  enable  to  set  0  to  20  %  of 
raising torque 

Input Terminal 

4 multi-function input, take 15 speed control, 
process, 2 sets of acceleration/deceleration 

Output Terminal 

1 set of alarm 

Time Setup 

0~999.9s for speed up / down 

Other Function 

Analog  input  0~10V,  8  steps  of  multi-speed, 

auto stable voltage 

E

n

vi

ro

n

m

en

Temperature 

-10

 to 40

 (non-freezing) 

Humidity 

Max. 95% (non-condensing) 

Altitude 

Under 1000m 

Vibration 

Max. 0.5G 

Structure 

Cooling Mode 

Compulsory cooling   

Protection Level 

IP 20 

Содержание HC2-E1000 Series

Страница 1: ... to personnel The symbol indicates incorrect operation which can cause personnel injury or AC motor speed controller and mechanical system fault as determined by different situations the caution affairs may lead to serious consequence The figures in this instruction are for convenience with descriptions they may have slight differences compared to the products and the products update can also caus...

Страница 2: ...nance 6 1 6 Exception Processing 7 1 7 Scrapping Processing 7 Chapter 2 Product Introduction 8 2 1 Unpacking Inspection 8 2 2 Model Description 8 2 3 Product Specifications 9 2 4 Product Models 10 2 5 Dimensions 10 Chapter 3 Wiring and Operation 11 3 1 Wiring Diagram 11 3 2 Display Panel 11 3 3 Parameter Setting 12 Chapter 4 Table of Functional Parameters 13 Chapter 5 Fault Alarm and Solutions 17 ...

Страница 3: ...e specifications and whether there are unusual phenomena inside or outside AC motor speed controller 1 2 Moving and Installation Warning When moving the product please use proper moving instruments to prevent AC motor speed controller from damage When moving AC motor speed controller please fasten the bottom of AC motor speed controller holding the cover plate directly may lead to dropping and cau...

Страница 4: ...and locked firmly in accordance with user s instruction of the manual to prevent AC motor speed controller from falling During installation prevent screws wire pieces and other electricity conductive material from falling in AC motor speed controller Otherwise AC motor speed controller may be damaged or a serious accident may take place If two and more AC motor speed controller is installed in one...

Страница 5: ...ricians Please wire in accordance with the user s instruction of the manual The grounding connection shall be installed properly in accordance with relative regulations in the user s instruction Otherwise it may cause an electric shock or fire Please use independent power supply for AC motor speed controller Never use the same power supply with strong interference equipment like electric welder Pl...

Страница 6: ...ure that the power cables and signal cables are connected correctly otherwise it may cause AC motor speed controller damaged Please ensure all of the parameters are set correctly before running Before running please ensure machine not to damage running equipments It is recommended to take running with idle load Please provide an emergency stop switch when stop function setting is unavailable Do no...

Страница 7: ...rwise you may get an electric shock Before checking and maintaining please touch a nearby metal substance with your hand to eliminate the static electricity for preventing AC motor speed controller from damage caused by static electricity Please do not use Megohmmeter insulation resistance to test the control circuit of AC motor speed controller Danger Only authorized professional personnel can do...

Страница 8: ...motor speed controller If the fault is not eliminated Resetting and restarting AC motor speed controller can cause AC motor speed controller s or machine fault When AC motor speed controller fault takes place please do not treat it by your own and contact our company and our distributors 1 7 Scrapping Processing Warning When AC motor speed controller is scrapped please dispose it as industrial rub...

Страница 9: ...is in accordance with your order Check whether AC motor speed controller is damaged and related accessories are completed If you find an omission or disagreement please contact the suppliers 2 2 Model Description MODEL HC201D5E24F INPUT 3PH 220V 50 60Hz OUTPUT 3PH 220V 6 0A 150 60s RANGE 0 1 400Hz 1 5KW HC2 E F Version F Voltage 24 AC 200 240V Model E1000 Capacity 0 4 0 15KW ...

Страница 10: ...ng 0 01 Hz Analog setup 0 1 of maximum output frequency Frequency Accuracy 0 1Hz V F Control Changeable V F curve by setting Torque Control Auto raising torque by loading condition Manual increase enable to set 0 to 20 of raising torque Input Terminal 4 multi function input take 15 speed control process 2 sets of acceleration deceleration Output Terminal 1 set of alarm Time Setup 0 999 9s for spee...

Страница 11: ...1 0 2 5 3 75 0 4 HC200D7E24F 0 75 2 0 5 0 7 5 0 75 HC201D5E24F 1 5 2 8 7 0 10 5 1 5 HC202D2E24F 2 2 4 4 11 16 5 2 2 Three phase 380V 50 60Hz HC200D7E48F 0 75 2 2 2 7 4 05 0 75 HC201D5E48F 1 5 3 2 4 0 6 0 1 5 HC202D2E48F 2 2 4 0 5 0 7 5 2 2 Model L W H L1 W1 F KG HC200D4E24F 141 5 85 113 130 5 74 5 1 HC200D7E24F HC201D5E24F HC202D2E24F 151 100 111 7 139 6 8 6 5 2 1 3 HC200D7E48F HC201D5E48F HC202D2...

Страница 12: ...apter 3 Wiring and Operation 3 1 Wiring Diagram 3 2 Display Panel The display panel of Series E1000 consists of LED tubes LED indicators buttons and digital elements The outline and functions as the following ...

Страница 13: ...owing is the example 50HZ is changed into 25 00HZ The operation as the picture shown pushing the shift button will switch the twinkle position for change This button has one way circle function ENTER ESC 50 00 F0 F000 F001 50 00 25 00 F002 F0 25 00 ENTER ENTER ESC ESC Status lamp display the present status Programming button Function option Save button Jog button Up Switch button Down Running butt...

Страница 14: ... F006 Rated voltage of motor 220V 220 V F008 Voltage of torque compensation 0 30 6 F012 Acceleration time 0 1 3600s 10s 0 5s F013 Deceleration time 0 1 3600s 10s 0 5s F014 Upper frequency limit 0 0 400Hz 50Hz F015 Lower frequency limit 0 0 F014 0Hz F1 group c Tool parameters Code Parameter Settings Default F105 Stop mode 0 Speed down 1 Coast 0 F106 Start frequency of DC braking 0 10Hz 6 Hz F107 St...

Страница 15: ... F203 X3 terminal 3 16 F204 X4 terminal 4 Jog 4 0 F216 Multi speed frequency 1 0 0 400 0Hz 5Hz F220 Multi speed frequency 2 10Hz F224 Multi speed frequency 3 15Hz F228 Multi speed frequency 4 20Hz F232 Multi speed frequency 5 30Hz F236 Multi speed frequency 6 40Hz F240 Multi speed frequency 7 50Hz F3 group Advanced parameters Code Parameter Settings Default F301 Carrier frequency adjustment 0 0 12...

Страница 16: ...record 2 F411 Fault record 3 F412 Fault record 4 Example Multi speed Parameter F203 3 F202 2 F20 1 1 Terminal X3 X2 X1 F001 F005 0 0 0 F216 0 0 1 F220 0 1 0 F224 0 1 1 F228 1 0 0 F232 1 0 1 F236 1 1 0 F244 1 1 1 Process of setting to default the factory setting Set F321 for 1 Press Up for 5 seconds Show 2 on the display Press Enter Show on the display complete Note Some default values will be the ...

Страница 17: ...end deceleration time 2 Add braking resistors 3 Select a suitable motor 4 Check the connection OC Over Current in Constant speed 1 Too low voltage 2 Less the capacity 3 Restart in running the motor 4 Too heavy load 1 Check the input power 2 Check the phrase 3 Select a suitable motor 4 Restart after running the motor 5 Check the connection OE 1 Over Voltage in Running 1 Abnormal input voltage 2 Res...

Страница 18: ...2 Too low voltage 3 Run with low speed and high torque for a long time 4 Set improper over loading coefficient of the motor 5 The motor is blocked or too high torque 1 Correct V F curve 2 Check the input power 3 Select a specialized inverter 4 Check the set parameters 5 Select a suitable motor 6 Check the connection EMS Failed to the External 1 Failed to terminals of the external equipment 1 Check...

Отзывы: