1.7 Wiring main circuit and notice
■
Main circuit wiring
The non-fusible-breaker (NFB) should be installed between the AC source and
the R/L1-S/L2-T/L3 input terminal of 7200MA inverter. The user can make his own
decision of installing electromagnetic contactor block (MCB) or not. To protect
against the false triggering of leakage-current, the user should install a leakage
current breaker with amperage sensitivity
≧
200mA and operation time
≧
0.1 sec.
Table 3 220V and 440V class applicable wire size and connector
7200MA model
Wire size (mm
2
)
Power
supply
Applicable
Power Rating
(HP)
*1
Rated
KVA
Rated
current
(A)
Main
circuit
*2
Ground
connection
wire E (G)
Control
wire
*3
NFB
*4
MCB
*4
1HP 2 4.8
2
~
5.5 2
~
5.5 0.5
~
2
TO-50EC(15A) CN-11
2HP 2.7 6.4 2
~
5.5 3.5
~
5.5
0.5
~
2
TO-50EC(20A) CN-11
220V
1
ψ/
3
ψ
3HP 4 9.6
3.5
~
5.5
3.5
~
5.5
0.5
~
2
TO-50EC(20A) CN-11
5.4HP 7.5 17.5 5.5
5.5 0.5
~
2
TO-50EC(30A) CN-16
7.5HP 10.1 24
8
5.5
~
8 0.5
~
2
TO-100S(50A) CN-18
10HP 13.7 32
8 5.5
~
8 0.5
~
2
TO-100S(60A) CN-25
15HP 20.6 48
14
8 0.5
~
2
TO-100S(100A) CN-50
20HP 27.4 64
22
8 0.5
~
2
TO-100S(100A) CN-65
25HP 34 80 22
14 0.5
~
2
TO-225S(150A) CN-80
30HP 41 96 38
14 0.5
~
2
TO-225S(175A) CN-100
220V
3
ψ
40HP 54 130 60
22 0.5
~
2
TO-225S(175A) CN-125
1HP 2.2 2.6 2
~
5.5 2
~
5.5 0.5
~
2
TO-50EC(15A) CN-11
2HP 3.4 4 2
~
5.5 3.5
~
5.5
0.5
~
2
TO-50EC(15A) CN-11
3HP 4.1 4.8 2
~
5.5 3.5
~
5.5
0.5
~
2
TO-50EC(15A) CN-11
5.4HP 7.5 8.7 2
~
5.5 3.5
~
5.5
0.5
~
2
TO-50EC(15A) CN-18
7.5HP 10.3 12 3
~
5.5 3.5
~
5.5
0.5
~
2
TO-50EC(20A) CN-18
10HP 12.3 15
5.5
5.5 0.5
~
2
TO-50EC(30A) CN-25
15HP 20.6 24
8
8 0.5
~
2
TO-50EC(30A) CN-25
20HP 27.4 32
8
8 0.5
~
2
TO-100S(50A) CN-35
25HP 34 40
8
8 0.5
~
2
TO-100S(75A) CN-50
30HP 41 48 14
8 0.5
~
2
TO-100S(100A) CN-50
40HP 54 64 22
8 0.5
~
2
TO-100S(100A) CN-65
50HP 68 80 22
14 0.5
~
2
TO-125S(125A) CN-80
60HP 82 96 38
14 0.5
~
2
TO-225S(175A) CN-100
440V
3
ψ
75HP 110 128 60
22 0.5
~
2
TO-225S(175A) CN-125
*1 : It is assumed constant torque load.
*2 : The main circuit has terminals of R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, B1/P,
B2/R, B2,
Θ
.
*3 : The control wire is the wire led to the pin terminals of control board.
*4 : In Table 3, the specified Part No. of NFB and MC are the item No. of the
products of Teco. The customer can use the same rating of similar products
from other sources. To decrease the noise interference, be sure to add R-C
surge suppressor (R: 10
Ω
/5W, C: 0.1
μ
F/1000VDC) at the 2 terminals of coils
of electromagnetic contactor.