1.7 Wiring main circuit and notice 

  Main circuit wiring 

The non-fusible-breaker (NFB) should be installed between the AC source and 

the R/L1-S/L2-T/L3 input terminal of 7200MA inverter. The user can make his own 
decision of installing electromagnetic contactor block (MCB) or not. To protect 
against the false triggering of leakage-current, the user should install a leakage 
current breaker with amperage sensitivity

200mA and operation time

0.1 sec. 

Table 3    220V and 440V class applicable wire size and connector 

7200MA model 

Wire size (mm

2

Power 

supply 

Applicable 

Power Rating 

(HP)

*1

 

Rated 

KVA 

Rated 

current 

(A) 

Main 

circuit

*2

 

Ground 

connection 

wire E (G)

Control 

wire

*3

 

NFB

*4

 MCB

*4

 

1HP 2 4.8 

2

5.5 2

5.5 0.5

TO-50EC(15A) CN-11 

2HP 2.7 6.4 2

5.5 3.5

5.5

0.5

TO-50EC(20A) CN-11 

220V 

1

ψ/

3

ψ

 

3HP 4 9.6 

3.5

5.5

3.5

5.5

0.5

TO-50EC(20A) CN-11 

5.4HP 7.5 17.5  5.5 

5.5  0.5

TO-50EC(30A) CN-16 

7.5HP 10.1  24 

5.5

8 0.5

TO-100S(50A) CN-18 

10HP 13.7 32 

8  5.5

8 0.5

TO-100S(60A) CN-25 

15HP 20.6 48 

14 

8  0.5

TO-100S(100A) CN-50 

20HP 27.4 64 

22 

8  0.5

TO-100S(100A) CN-65 

25HP 34 80  22 

14  0.5

TO-225S(150A) CN-80 

30HP 41 96  38 

14  0.5

TO-225S(175A) CN-100 

220V 

3

ψ

 

40HP 54 130  60 

22  0.5

TO-225S(175A) CN-125 

1HP 2.2 2.6 2

5.5 2

5.5 0.5

TO-50EC(15A) CN-11 

2HP 3.4 4 2

5.5 3.5

5.5

0.5

TO-50EC(15A) CN-11 

3HP 4.1 4.8 2

5.5 3.5

5.5

0.5

TO-50EC(15A) CN-11 

5.4HP 7.5 8.7 2

5.5 3.5

5.5

0.5

TO-50EC(15A) CN-18 

7.5HP 10.3  12  3

5.5 3.5

5.5

0.5

TO-50EC(20A) CN-18 

10HP 12.3 15 

5.5 

5.5  0.5

TO-50EC(30A) CN-25 

15HP 20.6 24 

8  0.5

TO-50EC(30A) CN-25 

20HP 27.4 32 

8  0.5

TO-100S(50A) CN-35 

25HP 34 40 

8  0.5

TO-100S(75A) CN-50 

30HP 41 48  14 

8  0.5

TO-100S(100A) CN-50 

40HP 54 64  22 

8  0.5

TO-100S(100A) CN-65 

50HP 68 80  22 

14  0.5

TO-125S(125A) CN-80 

60HP 82 96  38 

14  0.5

TO-225S(175A) CN-100 

440V 

3

ψ

 

75HP 110 128  60 

22  0.5

2

 

TO-225S(175A) CN-125 

*1  : It is assumed constant torque load. 
*2  : The main circuit has terminals of R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, B1/P, 

B2/R, B2,

Θ

*3  : The control wire is the wire led to the pin terminals of control board. 
*4  :  In Table 3, the specified Part No. of NFB and MC are the item No. of the 

products of Teco. The customer can use the same rating of similar products 
from other sources. To decrease the noise interference, be sure to add R-C 
surge suppressor (R: 10

Ω

/5W, C: 0.1

μ

F/1000VDC) at the 2 terminals of coils 

of electromagnetic contactor. 

Содержание 7200 MA Series

Страница 1: ...ely to the commercial carrier that have delivered your inverter Inverter nameplate MODEL INPUT OUTPUT SER NO JNTMBGBB0001AZSU 440V CLASS INVERTER AC 3PH 380 480V 50 60Hz AC 3PH 0 480V 2 2KVA 2 6A INVE...

Страница 2: ...mperature 10 40 AIR AIR 120 mm min 120 mm min a Space in Side b Space in Top bottom Fig 1 a Air clearance for 7200MA wall mounting 220 240V 380 480V Single ThreePhases L1 L 3Phases IM L2 N L3 T3 T2 T1...

Страница 3: ...you finished the wiring connection assemble Front Cover first then reinstall LCD Digital Operator 220V 30HP 40HP 440V 40 75HP Iron instructions you can disassemble Front Cover for wiring connection wi...

Страница 4: ...w 1 and lift the bottom of the cover in the direction of arrow 2 to remove the front cover 1 2 1 Front Cover c RS 232 Cable Connector Mounting the front cover and digital operator Insert the tab of th...

Страница 5: ...the upper part of front cover into the groove of the inverter and tighten the screws in the place c and d Connect the RS 232 cable connector on the back of the LCD digital operator Attach the digital...

Страница 6: ...meter settings will return to their initial settings at factory If the inverter is initially operated in 3 wire mode Sn 03 8 10 12 the motor will rotate in CCW sense after setting changed to 2 wire mo...

Страница 7: ...omagnetic contactor as the switch that control the operation of running or stop AC reactor The AC side reactor on the input AC side can improve the power factor and suppress the surge current Install...

Страница 8: ...lti Step Speed Ref 1 Jogging Acc Dec Switch Factory Preset P P P 0 10V 4 20 mA 0 10V 0V 4 20 mA 250 AO1 V T2 W T3 IM Grounding Lead 100 GND AO2 Analog Output 1 RA RB RC Multi Function Contact O t t 25...

Страница 9: ...nd set to SOURCE position for source type input 3 The terminal arrangement 4 The control board code No 4P101C0060002 P Shield Wire Shielded Twisted Wire 24VG 1 3 5 7 AUX VIN AIN 24V DO1 DOG IP12 A A E...

Страница 10: ...nused U T1 V T2 W T3 Inverter output E Grounding lead 3rd type grounding Terminal block configuration 220V 440V 1 2HP R L1 S L2 T L3 B1 P U T1 V T2 W T3 B2 220V 3 5HP 440V 3 5HP R L1 S L2 T L3 E B1 P...

Страница 11: ...Lower Bound of Frequency Command Frequency Jump 4 etc GND Analog Signal Common IP12 IG12 External Power Source For PG Feedback Use A A Signal Input of PG also can be the input terminal of Pulse Input...

Страница 12: ...1 12 1 6 Main Circuit Wiring Diagram Main Circuit Wiring Diagram of 7200MA 1 220V 440V 1 20HP 2 220V 25HP 440V 25 30HP 3 220V 30 40HP 440V 40 75HP DC Reactor built in DCL...

Страница 13: ...2 14 0 5 2 TO 225S 150A CN 80 30HP 41 96 38 14 0 5 2 TO 225S 175A CN 100 220V 3 40HP 54 130 60 22 0 5 2 TO 225S 175A CN 125 1HP 2 2 2 6 2 5 5 2 5 5 0 5 2 TO 50EC 15A CN 11 2HP 3 4 4 2 5 5 3 5 5 5 0 5...

Страница 14: ...lti function output terminals connect serially to an external relay an anti parallel freewheeling diode should be applied at both ends of relay as shown below free wheeling diode 100V 100mA 48V max 50...

Страница 15: ...f the rated voltage If there is the possibility of excessive voltage drop use a larger wire suitable to the required length Installing an AC reactor If the inverter is connected to a large capacity po...

Страница 16: ...60Hz Allowable Voltage Fluctuation 15 10 Power Supply Allowable Frequency Fluctuation 5 b 440V Series Inverter HP 1 2 3 5 7 5 10 15 20 25 30 40 50 60 75 Max Applicable Motor Output HP 1 KW 1 0 75 2 1...

Страница 17: ...e Customer Application Software Environment C A S E SINK SOURCE Interface Stall Prevention During Acceleration Deceleration and constant Speed Running Current Level Can Be Selected During Acceleration...

Страница 18: ...rnal ACL option b 30 30 31 220V 3 40 269 553 277 Top 210 Bottom 180 530 M10 31 269 647 277 Top 210 Bottom 180 530 M10 32 DCL Built in Standard c 1 2 132 217 143 5 122 207 M5 2 3 a 3 5 140 279 5 176 5...

Страница 19: ...1 19 b 220V 3HP 25HP 440V 3HP 30HP 1 1 c 220V 30HP 40HP 440V 40HP 75HP Open Chassis Type IP00 Enclosed Wall mounted Type NEMA1 D W W1 H H1 d D H H1 d W W1...

Страница 20: ...m Voltage Inverter Capacity HP W H D W1 H1 d Weight kg 1 220V 1 3 2 6 3 3 5 198 335 217 115 315 M6 7 5 7 5 10 15 220V 3 20 223 460 245 140 440 M6 16 1 2 6 3 3 5 198 335 217 115 315 M6 7 5 7 5 10 15 44...

Страница 21: ...TBU 230 1 JNBR 4R8KW6R8 4800W 6 8 1 117 10 ED 220V 3 40 130 JNTBU 230 2 JNBR 3KW10 3000W 10 2 119 10 ED 1 2 6 JNBR 150W750 150W 750 1 126 10 ED 2 4 JNBR 150W400 150W 400 1 119 10 ED 3 4 8 JNBR 260W250...

Страница 22: ...4A 3M200D1610064 0 35mH 30A 10 32A 3M200D1610072 0 265mH 40A 15 48A 3M200D1610081 0 18mH 60A 20 64A 3M200D1610099 0 13mH 80A 25 80A 3M200D1610102 0 12mH 90A 30 96A 3M200D1610111 0 09mH 120A 220V 3 40...

Страница 23: ...300D1610007 JUNF32024S MA 24 A Fig a 7 5 24A 4H300D1620002 JUNF32048S MA 48 A Fig b 10 32A 4H300D1620002 JUNF32048S MA 48 A Fig b 15 48A 4H300D1730002 JUNF32070S MA 70 A Fig b 220V 3 20 64A 4H300D1730...

Страница 24: ...L3 L1 L2 L3 LINE LOAD PE PE L1 L2 L3 L1 L2 L3 LINE LOAD PE PE 225 250 50 100 4 6 5 70 c Dimension mm Model W W1 H H1 D d M KMF370A 93 79 312 298 190 7 M6 KMF3100A 93 79 312 298 190 7 M6 KMF3150A 126...

Страница 25: ...ach phase should be winded by following the same convention and one direction The more winding turns the better attenuation effect Without saturation If the wire size is too big to be winded all the w...

Страница 26: ...4H332D0040006 4H314C0040000 10m 4H332D0130005 4H314C0060001 4H300D1120000 1 Including special cable for LCD digital operator blank cover fixed use screws and installation manual 2 One special cable fo...

Страница 27: ...0V VIN Master Speed 0 10V 2k Master Freq Ref 976 1 4 W A01 GND FM B1 P B2 IM RA RB RC Multi Function Contact Output 250V AC max 1A 30V DC max 1A DO1 DOG DO2 Multi Function Output 1 2 Open Collector 48...

Страница 28: ...200 x 440V class MODEL HP KVA 100 CONT Output AMPS Rated Input AMPS FUSE Rating JNTMBG 0001AZ 1 2 2 2 6 3 6 JNTMBG 0002AZ 2 3 4 4 5 10 JNTMBG 0003AZ 3 4 1 4 8 6 10 JNTMBG 0005AZ 5 7 5 8 7 10 20 JNTMBG...

Отзывы: