UPS EVO DSP TT
7
User’s Manual
According to EN 62040-1-2, the user shall place a warning label on the input distribution
panel and the other primary power isolators, in order to prevent the risk of electric
shock caused by a fault voltage on the UPS. The label shall carry the following wording:
ISOLATE THE UNINTERRUPTIBLE POWER SUPPLY (UPS) BEFORE WORKING ON THIS CIRCUIT
2.5 Connections
Connections shall be done by authorized technical staff only.
When the UPS is brought from a cold place to a warmer place, humidity of the air may
condensate in it. In this case, wait for two hours before beginning with the installation.
UPS front side
The layout of the Communication Interface board, Parallel board, slot
for SNMP Interface, circuit breakers and connection terminals, is shown
below (for accessing open the UPS front door):
A1: Communication Interface board
A2: Parallel board
(optional)
A3: Slot for SNMP Interface:
SNMP (Simple Network Management
Protocol) Interface is optional.
ATTENTION: bring the 2 dip switches of A1 board to ON position
before using SNMP Interface.
F1: Input mains circuit breaker
F2: Output circuit breaker
F3: Manual Bypass circuit breaker
F4: Static Bypass circuit breaker
(optional)
F5: Battery circuit breaker
F6: Inrush circuit breaker
X1: Battery terminals
(for connecting the batteries)
X2: Input terminals
(for connecting AC Input mains)
X3: Bypass terminals
(optional – for connecting AC Input mains for
Split Bypass)
X4: Output terminals
(for connecting Output line)
A1
A2
F5
F1 F3 F2
F6
F4
X1 X2
X3
X4
A3