ENGLISH
User’s manual
16
UPS EVO DSP PLUS TM
1.
Computer Interface (DB9 female connector
): it is the communication RS-232 port.
2.
Computer Interface (USB connector
): it is the communication USB port.
3.
EPO (Emergency Power OFF) connector
4.
Share Current port (only available for Parallel model)
5.
Parallel ports (only available for Parallel model)
6.
Slot for SNMP Interface (optional)
7.
Power stage fans
8.
External Battery Box connector
9.
Metallic panel for access to the Input/Output terminals:
upon
removal, it is possible to access the
Input/Output terminals (see figure 5).
10.
Line Input circuit breaker
11.
Maintenance Bypass switch
12.
Output Circuit Breaker (10A max Current)
:
it goes off in overload or short-circuit condition; push the
external button of the Circuit Breaker to reactivate it.
13.
Grounded Output socket (IEC C13 type, 10A Max Current, 250 Vac):
for connecting equipments to be
protected.
5.2.1
Input/Output Terminals
Figure 5 –
Input/Output Terminals
INPUT terminals
: to connect AC Input line
OUTPUT1 terminals
: to connect OUTPUT1 line
OUTPUT2 terminals
: to connect OUTPUT2 line
BATTERY terminals
: use only to connect an external Battery Box
GND
: GROUND screws to connect INPUT, OUTPUT and external Battery Box GROUND cables