ENGLISH
UPS EVO DSP PLUS 1.2-2.4-3.6 MM
13
User’s manual
If neutral line and ground line are short circuited, please add isolation transformer
between UPS and devices. See the image below.
Never connect neutral line of input to neutral line of output. Otherwise, it will cause
the damage of the UPS. See the image below.
6.1
Installation
We advise you to follow the steps below explained:
1.
Through the included power cable connect the UPS Input socket to the AC line outlet (see figure 4).
It is
mandatory to ground the AC line outlet according to the Safety Standards
. Carefully check the grounding
of AC line outlet.
2.
Connect the devices to be supplied to the UPS outputs, by using only the included cables. Be sure all the
devices have the main switch in OFF position.
DEVICE
LINE
NEUTRAL
GND
LINE
NEUTRAL
LINE
NEUTRAL
UPS
ISOLATION
TRANSFORMER
INPUT
OUTPUT
LINE
NEUTRAL
LINE
NEUTRAL
UPS