FIRST START-UP 

The first start-up procedure is very simple.  We advise you to follow the steps below explained. 
 
1.  Through the supplied cable connect the UPS to the AC line outlet. It is mandatory to 

ground the outlet according to the Safety Standards. Carefully check the grounding, 

make sure that the utility power is available, and that its range falls within the UPS 

specifications. 

2.  Switch the UPS ON and see that it operates correctly. Check that the UPS does not signal 

any sort of anomaly. Wait for the correct switching to LINE mode and make sure that the 

cooling fans are set in motion. Leave the UPS in LINE mode for at least 8 hours in order to 

completely recharge the batteries. 

3.  Switch the UPS OFF. 
4. 

Connect the devices to be supplied to the UPS output sockets. Then put 

all the 

main switch of each device in the ON position. 

 
5. Restart 

the 

UPS; 

and see that it operates correctly

; wait for the UPS to start working 

properly in LINE mode and that no overload signal or any other form of anomalies are 

present. Then make sure that all equipments switch on correctly.  
In case of Overload immediately reduce the power demand by disconnecting the devices 

that cause the overload.  Switch OFF the UPS and repeat point 4 and 5. 

6.  Carry out the LOAD TEST according the modalities described in charter LOAD CONTROL. 

Carry out step 3, 4, 5, 6, of the initial start up procedure to change the configuration of the 

devices protected by the UPS.   

WARNING 
It is compulsory to ground the UPS according to safety Standards. 
Risk of electric shock: do not remove the cover. The UPS contains internal parts 

which are at a high voltage and are potentially dangerous, capable of causing injury 

or death by electric shock. 
There are no internal parts in the UPS which are user serviceable. Any repair or 

maintenance work must be performed exclusively by qualified technical personnel 

authorized by TECNOWARE. TECNOWARE declines any responsibility if this warning 

is disregarded. 
Risk of electric shock at the output socket if the UPS is ON, even when the UPS is not 

connected to AC utility line. 
Risk of electric shock at the output socket while the unit is connected to AC utility 

line.  
Disregard for these warnings may lead to a risk of electric shock to operators.

 

 
 

 

  1

5

  COMPUTER INTERFACE 

EVO  is  gifted  with  an  RS-232 interface which can be used as a communication port with a 

computer.    

A 9 poles female connector (DB9) is fitted on the rear side.   
On the DB9 connector the following RS-232 signals are present:  

 

RX (pin 2) 

 

TX (pin 3) 

 

GND (pin 5 and pin 7) 

The RS-232 interface signals are isolated through photo-couplers. 
 

User’s manual 

13 UPS 

EVO

 

Содержание EVO 1.0

Страница 1: ...EVO Uninterruptible Power Supply EVO 1 0 EVO 2 0 EVO 3 0 USER S MANUAL...

Страница 2: ......

Страница 3: ...CEMENT FIRST START UP 5 COMPUTER INTERFACE page 12 6 TECHNICAL CHARACTERISTICS page 13 7 SUGGESTIONS FOR A CORRECT USE page 14 MAINTENANCE BATTERY MAINTENANCE SAFETY FOR THE OPERATOR 8 ANOMALIES AND T...

Страница 4: ...repair or maintenance must be performed exclusively by qualified technical personnel authorized by TECNOWARE TECNOWARE declines any responsibility if this warning is disregarded It is compulsory to g...

Страница 5: ...ATIC BYPASS that directly connects the AC input line with its outlets EVO is supplied with an RS 232 communication port and USB port which can be used to signal to a generic processor or computer the...

Страница 6: ...ere is an automatic SWITCHING On operation Automatic functioning test through a switch Automatic regulation to the input frequency 50 or 60 Hz Visual warnings by leds indicating operational mode and l...

Страница 7: ...ed This led blue is ON when the input AC line voltage amplitude is within the specification and it indicates the UPS is working in LINE mode If LINE led flashes every second it shows that Phase line a...

Страница 8: ...5 16 17 and 18 60 41 three leds are on led15 16 and 17 40 21 two leds are on led15 and led16 20 0 only one led is on led15 The LOW BAT yellow led led14 is on to warn of a LOW BATTERY condition during...

Страница 9: ...the UPS from the front panel The EPO terminals are isolated and do not need an external feeding voltage REMOTE ON OFF ON 1 2 Remote Button ON OFF 3 4 Remote Button OFF The EVO models have remote ON OF...

Страница 10: ...ormal closed output When UPS works normally Pin 6 and Pin 1 2 will be closed when UPS works in bypass mode Pin 6 and Pin 1 2 will be open 4 AC fail Pin 7 is the normal open output When UPS works norma...

Страница 11: ...gnal showing its own switching on The UPS immediately switches on BAT LEVEL bar then it effectuates an initial operating SELF TEST during which the red FAULT and OVERLOAD leds are switched on it switc...

Страница 12: ...mode is characterized by The BYPASS led and LINE led switched on The LOAD LEVEL and BAT LEVEL led bars switched on The UPS can be transferred in BYPASS mode even through a manual operation First of a...

Страница 13: ...ic signal every second and after it switches automatically to the BYPASS MODE In LINE mode EVO switches automatically to the BYPASS mode as soon as the overload is higher than 150 Once the requested p...

Страница 14: ...put line and to the equipment that needs to be powered The UPS is designed to operate in protected environments for example offices This UPS should be installed indoors with adequate airflow and free...

Страница 15: ...repeat point 4 and 5 6 Carry out the LOAD TEST according the modalities described in charter LOAD CONTROL Carry out step 3 4 5 6 of the initial start up procedure to change the configuration of the de...

Страница 16: ...8 15 minuts AUTONOMY 36 96 96 NOMINAL BATTERY VOLTAGE 3 units 12V 7 2Ah 8 units 12V 7 2Ah 8 units 12V 7 2Ah SEALED MAINTENANCE FREE LEAD ACID BATTERIES TYPICAL BATTERY CHARGE TIME 8 Hours EXPANDABLE A...

Страница 17: ...ioning test in BATTERY mode this will preserve the batteries in an excellent state and extend the life duration Leave the UPS in BATTERY mode until the end of autonomy condition is reached After which...

Страница 18: ...e UPS OFF and remove the UPS input voltage Check the Input Circuit Breaker Should it be snapped OFF position check if the UPS is overloaded then try to rearm the breaker by bringing it in the ON posit...

Страница 19: ...the UPS which are user serviceable Any repair or maintenance work must be performed exclusively by qualified technical personnel authorized by TECNOWARE TECNOWARE declines any responsibility if this...

Страница 20: ...19 FIGURES Figure 1 Operating modes UPS EVO 18 User s manual...

Страница 21: ...red 2 OFF Button 9 LOAD 100 led blue 10 LOAD 80 led blue 11 LOAD 60 led blue 12 LOAD 40 led blue 13 LOAD 20 led blue Operating modes leds BAT level led bar 3 LINE led blue 14 LOW BAT led yellow 4 BATT...

Страница 22: ...aker 3 Grounded output socket 4 Grounded power output socket EVO 2 0 and EVO 3 0 5 Computer Interface RS 232 6 RJ11 RJ45 IN OUT plugs 7 Slot for external batteries connector 8 Dty contacts board Slot...

Страница 23: ...and in any case any circumstances in which one cannot date back to the defective manufacture will not be covered by the guarantee Compensation is excluded for direct or in direct damages of any natur...

Страница 24: ...TECNOWARE S r l www service tecnoware com...

Отзывы: