II_T9355/IP_07_eng  

   

Page 2 of 2 

 

The connection and installation of the interface has to be done by qualified personnel properly trained. 

 

RESET PROCEDURE

1) Connect the reset-box to any of the keypad/lock connector on the interface. 

2) Push and release the reset button. The LED blinks slowly. 

3) Wait for 10 seconds. Led turns off. 

4) Remove the reset-box. 

5) The interface is now reset and it is ready to be installed on the system. 

 

INSTALLATION PROCEDURE

Before installing the interface, make sure that no ethernet hub is present in the system of interest. The use of 

ethernet hub indeed, might cause malfunctions of the interface itself. It is instead allowed using ethernet 

switches. 

1) Make sure that the interface is in reset mode. 

2) Connect the interface to the keypad. 

3) Open the lock 1 and keep the bolt open. 

4) Enter in the configuration menu. 

5) Select 

‘Install I/O interface’ submenu. 

6) Enter Master code to complete the installation procedure. 

7) The interface is now installed and ready to work. 

8) When using the interface in 'RS485 mode', make sure the ID is set correctly.  

 