  W09Y

DIGITAL ELECTRONIC FREEZER

CONTROLLER

OPERATING INSTRUCTIONS

Vr. 01 (ENG) - 07/09 - cod.: ISTR-MW09YENG1

TECNOLOGIC S.p.A.

VIA INDIPENDENZA 56

27029 VIGEVANO (PV) ITALY

TEL.:  +39 0381 69871

FAX: +39 0381 698730

internet : http:\\www.tecnologic.it

e-mail: [email protected]

FOREWORD

This manual contains the information
necessary for the product to be installed
correctly and also instructions for its
maintenance and use; we therefore recommend
that the utmost attention is paid to the following
instructions and to save it.

This document is the exclusive property of TECNOLOGIC
S.p.A. which forbids any reproduction and divulgation , even
in part, of the document, unless expressly authorized. 
TECNOLOGIC S.p.A. reserves the right to make any formal or
functional changes at any moment and without  any notice.
Whenever a failure or a malfunction of the device may cause
dangerous situations for persons, thing or animals, please
remember that the plant has to be equipped with additional
devices which will guarantee safety.
Tecnologic S.p.A. and its legal representatives do not assume
any responsibility for any damage to people, things or animals
deriving from violation, wrong or improper use or in any case
not in compliance with the instrument’s features.

INDEX

INSTRUMENT ORDERING CODE

7.5

FUNCTIONAL DATA

7.4

MECHANICAL DIMENSIONS AND MOUNTING

7.3

MECHANICAL DATA

7.2

ELECTRICAL DATA

7.1

TECHNICAL DATA

7

GUARANTEE AND REPAIRS

6.3

CLEANING

6.2

SIGNALLING

6.1

PROBLEMS , MAINTENANCE AND GUARANTEE

6

PROGRAMMABLE PARAMETERS TABLE

5

FUNCTION OF KEYS “U” AND “DOWN/AUX”

4.11

OPEN DOOR ALARM

4.10.3

EXTERNAL ALARM (DIGITAL INPUT)

4.10.2

TEMPERATURE ALARMS

4.10.1

ALARM FUNCTIONS

4.10

EVAPORATOR FANS CONTROL

4.9

DEFROST DISPLAY LOCK

4.8.4

END DEFROST

4.8.3

MANUAL DEFROST

4.8.2

AUTOMATIC DEFROST STARTS

4.8.1

DEFROST CONTROL

4.8

COMPRESSOR PROTECTION FUNCTION AND DELAY
AT POWER-ON

4.7

TEMPERATURE CONTROL

4.6

ACTIVE SET POINT SELECTION

4.5

OUTPUTS AND BUZZER CONFIGURATION

4.4

DIGITAL INPUT

4.3

MEASURING AND VISUALIZATION

4.2

ON / STAND-BY FUNCTION

4.1

FUNCTIONS

4

ELECTRICAL WIRING DIAGRAM

3.4

ELECTRICAL CONNECTIONS

3.3

MECHANICAL MOUNTING

3.2

PERMITTED USE

3.1

INFORMATION ON INSTALLATION AND USE 

3

KEYBOARD LOCK FUNCTION

2.7

PARAMETERS CONFIGURATION BY “A01”

2.6

RESET PARAMETERS TO DEFAULT VALUE/LEVEL

2.5

CUSTOMIZED MODE PARAMETER PROGRAMMING 

(PARAMETERS PROGRAMMING LEVEL)

2.4

PARAMETER PROTECTION USING THE PASSWORD

2.3

STANDARD MODE  PARAMETERS PROGRAMMING

2.2

FAST PROGRAMMING OF SET POINT

2.1

PROGRAMMING

2

FRONT PANEL DESCRIPTION

1.2

GENERAL DESCRIPTION

1.1

INSTRUMENT DESCRIPTION

1

1 - INSTRUMENT DESCRIPTION

1.1 - GENERAL DESCRIPTION

The model W09Y is a digital controller with microprocessor that is
typically used in cooling applications that have temperature control

with ON/OFF regulation and defrosting control at intervals time or
at reaching temperature by stopping compressor or by means of

electrical heating or hot gas/reverse cycle.
The instrument has up to 3 relay outputs, up to 3 inputs for PTC or

NTC temperature probes and a digital input (aternative to an
temperature input), in addition can be equipped with an internal

buzzer that is the sound system for alarms.
The 3 outputs can be can all be configured for controlling the

compressor or the temperature control device, the defrosting
device, the evaporation fan or, alternatively any of the previous

functions, using an auxiliary device or an alarm.
The 3 inputs for temperature probes can be used to measure the

control temperature, the evaporator temperature, products or aux
temperature,  while the digital input alternative to evaporator or aux

temperature input can be programmed to carry out various
functions such as door opened signal, defrosting commands,

selecting a different set of temperature regulations, external alarm

TECNOLOGIC spa - W09Y 

 

- OPERATING INSTRUCTIONS - Vr. 01 - 07/09 -  ISTR-MW09YENG1 -  PAG. 1

Содержание W09Y

Страница 1: ...UNCTION AND DELAY AT POWER ON 4 7 TEMPERATURE CONTROL 4 6 ACTIVE SET POINT SELECTION 4 5 OUTPUTS AND BUZZER CONFIGURATION 4 4 DIGITAL INPUT 4 3 MEASURING AND VISUALIZATION 4 2 ON STAND BY FUNCTION 4 1 FUNCTIONS 4 ELECTRICAL WIRING DIAGRAM 3 4 ELECTRICAL CONNECTIONS 3 3 MECHANICAL MOUNTING 3 2 PERMITTED USE 3 1 INFORMATION ON INSTALLATION AND USE 3 KEYBOARD LOCK FUNCTION 2 7 PARAMETERS CONFIGURATIO...

Страница 2: ...GRAMMING 2 1 FAST PROGRAMMING OF SET POINT Press the key P then release it and the display will show SP or SP2 if the second set is active at that time alternating with the set value To change it press the UP key to increase the value or DOWN to decrease it These keys increase or decrease the value one digit at a time but if the button is pressed for more than one second the value increase or decr...

Страница 3: ...DAPTER 12 VDC For additional info please have a look at the A01 instruction manual 2 7 KEYBOARD LOCK FUNCTION On the instrument it s possibile to lock completely the keyboard This function is particularly useful when the regulator is reachable by the users and it s desired to avoid any modification To activate the keyboard lock it s enough program the par t Lo to a different value to oF The value ...

Страница 4: ... the same func tion priority goes to i P2 Using the parameter i Ft it is possible to set the time constant for the software filter for measuring the input values to be able to reduce the sensitivity to measurement disturbances increasing the time Through the parameter i dS it is possible to fix the normal visualisation on the display that can be the measurement of the probe Pr1 P1 the measurement ...

Страница 5: ...the ot output is disabled This function mode can be used as a command for a second compressor or for all other working utilities according to the same ot output conditions but which must be delayed after the start up of the compressor to avoid excess electricity absorption 2 Activation by front key U or DOWN AUX or by digital input with contact normally open the output is activated by pressing the...

Страница 6: ... d tE and fixed differential at 1 C and operate in order to evaporator probe EP 4 8 1 AUTOMATIC DEFROST STARTS The automatic control of defrost occours by interval times The automatic defrost function is activate when at the parameter d di is set the defrost interval time The first defrost after swiching on can be set by par d Sd This allows to perform the first defrost to a different interval fro...

Страница 7: ...temperature measured by the evaporator probe exceeds the temperature set in the parameter d tE If this temperature is not reached in the time set in the parameter d dE defrosting is interrupted In order to avoid pointless defrosting the parameter d tS in d dC rt ct cS mode is foreseen that sets the enablement temperature for defrosting If the temperature measured by the probe is higher than the on...

Страница 8: ... of memorised alarm can only be carried out manually by pressing any key when the alarm has ended typical application for light signal At when one wants the function described as At but with an inverse function output activated in normal condition and disabled in alarm status AL when one wants the function described as AL but with inverse logic output activated in normal conditions and disabled in...

Страница 9: ...vice versa 5 PROGRAMMABLE PARAMETERS TABLE Here below is a description of all the parameters available on the instrument Some of them may not be present because depend on the model type of instrument C1 C0 F0 C1 F1 Unit of measurement and resolution decimal point C0 C with 1 res i uP 7 nt Pt nt Probes Type i SE 6 i parameters relative to inputs 0 0 S LS S HS Set Point 2 SP2 5 0 0 S LS S HS Set Poi...

Страница 10: ... dt 23 d parameters relative to defrosting control o parameters relative to configuration of outputs and buzzer 3 00 oF 0 01 9 59 min sec 99 5 min sec x10 Alarm delay with door open A oA 52 1 00 oF 0 01 9 59 hrs min 99 5 hrs min x10 Temperature Alarms delay after defrost and continuous cycle and unlock display delay after defrost A dA 51 2 00 oF 0 01 9 59 hrs min 99 5 hrs min x10 Temperature Alarm...

Страница 11: ...d Reason Message 6 2 CLEANING We recommend cleaning of the instrument only with a slightly wet cloth using water and not abrasive cleaners or solvents 6 3 GUARANTEE AND REPAIRS The instrument is under warranty against manufacturing flaws or faulty material that are found within 12 months from delivery date The guarantee is limited to repairs or to the replacement of the instrument The eventual ope...

Страница 12: ...tion 1 or 0 1 Overall accuracy 0 5 fs 1 digit Sampling rate 130 ms Display 3 Digit Red Blue optional h 15 5 mm Software class and structure Class A Compliance ECC directive EMC 2004 108 CE EN55022 class B EN61000 4 2 8KV air 4KV cont EN61000 4 3 10V m EN61000 4 4 2KV supply inputs outputs EN61000 4 5 supply 2KV com mode 1 KV diff mode EN61000 4 6 3V LV 2006 95 CE EN 60730 1 EN 60730 2 7 EN 60730 2...