0.0

SPLL ÷ SPHL

Set Point 

SP

23

OFF

OFF ÷ 9999

Access Password to
parameter functions

PASS

22

0

 -3 / -2 / -1 / 0

/ 1 / 2 / 3

Function and function
logic  of digital input:

0, 1, 2 = No function
3= External alarm

diF

21

OFF

OFF / 1

Function mode key U:
OFF= No Function

1= ON/STAND-BY

USrb

20

2.00

OFF ÷ 24.00  

hrs.min

Temperature Alarms
delay at power on

PAL

19

OFF

OFF ÷ 99.59

min.sec

Temperature Alarms
delay

ALd

18

2.0

0.0 ÷ 30.0

°C/°F

Temperature Alarms
Differential

dAL

17

OFF

OFF ÷ 100.0

°C/°F

Relative Low

temperature Alarm
threshold

LAL

16

OFF

OFF ÷ 100.0

°C/°F

Relative High
temperature Alarm

threshold 

HAL

15

OFF

OFF ÷ 99.59

min.sec

Delay at power on

od

14

OFF

OFF ÷ 99.59  

min.sec

Compressor protection

time

PtC

13

1

1 - 2 - 3

Type of compressor
protection:

1= delay at switch on
2= delay after switch off

3= delay between starts

PSC

12

CooL

HEAt - CooL

Function mode output
OUT

Func

11

OFF

OFF ÷ 99.59

min.sec

Deactivation  time out-

put OUT for probe  
broken

toFE

10

OFF

OFF ÷ 99.59

min.sec

Activation time output

OUT for probe  broken

tonE

9

6 - PROBLEMS, MAINTENANCE AND GUARANTEE

6.1 - SIGNALLING
Error Signalling:

Check and if necessary
re-programme the

parameters function.

Internal memory error

EEPr

Check the correct

connection of the probe
with the instrument and

check the probe works
correctly

The probe may be

interrupted or in short
circuit, or may measure

a value outside the
range allowed

E1

-E1

Action 

Reason

Error

In probe error status, the output OUT behaves as set by the

parameters “tonE” and “toFE”.

Other Signalling:

Digital input alarm in progress

AL

Minimum temperature alarm in progress

LO

Maximum temperature alarm in progress

HI

Delay in switching on in progress

od

Reason

Message

6.2 - CLEANING

We recommend  cleaning of the instrument with a slightly wet cloth

using water and not abrasive cleaners or solvents which may
damage the instrument.

6.3 - GUARANTEE AND REPAIRS

The instrument is under warranty against manufacturing flaws or
faulty material, that are found within 12 months from delivery date. 

The guarantee is limited to repairs or to the replacement of the
instrument. 

The eventual opening of the housing, the violation of the instrument
or the improper use and installation of the product will bring about

the immediate withdrawal of the warranty’s effects. 
In the event of a faulty instrument, either within the period of

warranty, or further to its expiry, please contact our sales
department to obtain  authorisation for sending the instrument to

our company. 
The faulty product must be shipped to TECNOLOGIC with a

detailed description of the faults found, without any fees or charge
for Tecnologic, except in the event of alternative agreements.

7 - TECHNICAL DATA

7.1 - ELECTRICAL DATA

Power supply: 12 VAC/VDC, 24 VAC/VDC, 100..240 VAC +/- 10%

Frequency AC: 50/60 Hz
Power consumption: 3 VA approx.

Input/s: 1 input for temperature probes: Pt1000 or NTC (PT-24C2,
100 K 

 @ 25 °C); 1 digital input for free voltage contacts

Output/s: up to 2 relay outputs: OUT SPST-NO (16A-AC1, 6A-AC3
250 VAC) or SPDT 16A-AC1, 6A-AC3 250 VAC) and AL SPST-NO

(5A-AC1, 2A-AC3 250 VAC).
Electrical life for relay outputs: OUT SPST-NO: 100000 op. ; SPDT:

50000 op. (om. VDE); AL: 100000 op.
Installation category:  II

Measurement category:  I
Protection class against electric shock:  Class II  for Front panel
Insulation:

   

Reinforced insulation between the low voltage part

(supply H type and relay outputs) and front panel; Reinforced
insulation between the low voltage section (supply type H and relay

outputs) and the extra low voltage section (inputs); Reinforced
between supply and relay outputs; No insulation between supply F

type and inputs.

7.2 - MECHANICAL DATA

Housing: Self-extinguishing plastic, UL 94 V0
Dimensions: 33 x 75 mm, depth 64 mm

Weight: 115 g approx.
Mounting: Flush in panel in 29 x 71  mm hole

Connections:  2,5 mm

2

 screw terminals block

Degree of front panel protection : IP 65 mounted in panel with

gasket
Pollution situation: 2

Operating temperature:  0 ... 50 °C
Operating humidity: 30 ... 95 RH% without condensation

Storage temperature: -10 ... +60 °C

7.3 – MECHANICAL DIMENSIONS, PANEL CUT-OUT AND
MOUNTING [mm]

75

33

5

64

28

Out

AL

TLZ 11

RECOMMENDED

PANEL CUTOUT

29

71

min. 15 mm

mi

n. 12

 mm

TECNOLOGIC spa - TLZ 11

 

P

 

- OPERATING INSTRUCTIONS - Vr.01  - 09/05 - ISTR 06947 - PAG. 5

Содержание TLZ 11 P

Страница 1: ...UNCTION OF KEY U 4 6 DIGITAL INPUT 4 5 EXTERNAL ALARM 4 4 2 TEMPERATURE ALARMS 4 4 1 ALARM FUNCTIONS 4 4 COMPRESSOR PROTECTION FUNCTION AND DELAY AT POWER ON 4 3 TEMPERATURE CONTROL 4 2 MEASURING AND VISUALIZATION 4 1 FUNCTIONS 4 ELECTRICAL WIRING DIAGRAM 3 4 ELECTRICAL CONNECTIONS 3 3 MECHANICAL MOUNTING 3 2 PERMITTED USE 3 1 INFORMATION ON INSTALLATION AND USE 3 ON STAND BY FUNCTION 2 5 PARAMETE...

Страница 2: ...first parameter and it will be possible to set the parameters of the instrument using the same programming procedure described previously Once the parameter has been selected and the SET is on it means that the parameter can be programmed even on the first level visible If the LED is off it means that the parameter can only be programmed on this level i e hidden To change the visibility of the par...

Страница 3: ... mode programmed on the parameter Func the differential is automatically considered by the regulator with positive values for a Refrigeration control Func CooL or with negative values for a heating control Func HEAt In the event of probe error it is possible to set the instrument so that that the output OUT continues to work in cycles according to the times programmed in the parameter tonE activat...

Страница 4: ... as diF 3 see par 4 5 At the same time as the signalling of the alarm buzzer and or output the instrument signals the alarm by turning on the led AL and visualising AL and the measured temperature alternately on the display 4 5 DIGITAL INPUT The digital input present on the instrument accepts contacts free of voltage the function carried out is defined by the parameter diF The parameter diF can be...

Страница 5: ... is limited to repairs or to the replacement of the instrument The eventual opening of the housing the violation of the instrument or the improper use and installation of the product will bring about the immediate withdrawal of the warranty s effects In the event of a faulty instrument either within the period of warranty or further to its expiry please contact our sales department to obtain autho...

Страница 6: ...racy Pt1000 0 5 fs 1 digit NTC PT 24C2 1 fs 1 digit Sampling rate 130 ms Display 4 Digit Red h 12 mm Compliance ECC directive EMC 89 336 EN 61326 ECC directive LV 73 23 and 93 68 EN 61010 1 7 5 INSTRUMENT ORDERING CODE TLZ 11 a b c d ee P a POWER SUPPLY H 100 240 VAC L 24 VAC VDC F 12 VAC VDC b OUTPUT OUT TYPE S Relay SPDT 16A AC1 R Relay SPST NO 16A AC1 c ALARM OUTPUT R Relay None d INTERNAL BUZZ...

Отзывы: