0
-999 ÷ 9999
Minimum alarm A4
threshold
AL4H
11
0
-999 ÷ 9999
Minimum alarm A4
threshold
AL4L
10
0
-999 ÷ 9999
Alarm A4 threshold
AL 4
9
0
-999 ÷ 9999
Minimum alarm A3
threshold
AL3H
8
0
-999 ÷ 9999
Minimum alarm A3
threshold
AL3L
7
0
-999 ÷ 9999
Alarm A3 threshold
AL 3
6
"COnF" MENU PARAMETERS TABLE
30
1 ÷ 255 sec.
Output C1 cycle time
tcr2
28
1.00
0.00 ÷ 99.99
C2 / C1 Power ratio
Prat
27
30
1 ÷ 255 sec.
Output C1 cycle time
tcr1
26
30
0 ÷ 9999 sec.
Derivative time
dEr
25
500
0 ÷ 9999 sec.
Integral time
Int
24
100
1 ÷ 9999
Proportional band
Pb
23
SP
SP / Load
Autotuning optimisation
PidP
22
no
no / FaSt /
SP / LoSP
Autotuning
Auto
21
no
no / yES
Selftuning
SELF
20
AL4
AL4 /
Pid / 3Pt
Output C2/A4 functioning
mode
C2
19
HEat
HEat / CooL
Output C1 operating
mode
Func
18
Pid
Pid /
OnFS / OnFa
Control mode
Cont
17
9999
SPLL ÷ 9999
High/maximum Set Point
SPHL
16
-999
-999 ÷ 9999
Low/minimum Set Point
SPLL
15
no
no / yES
Alarms programming on
"ConF" menu
ALPr
14
0
0 ÷ 9999 sec.
Loop Break alarm
maximum time
LbAt
13
0
0 ÷ 100 %
Loop Break alarm power
LbAP
12
OPEn
OPEn / CLoS
Output HB logic mode
rLHb
11
OFF
OFF / On
A4 Alarm behaviour in
OFF control mode
AL4o
10
- - C
- - C / - - o
- SC / - So
L - C / L - o
LSC / LSo
Configuration of A4 alarm
functioning mode
AL4c
9
LOAb
LOAb / HIAb
LHAb / LOdE
HIdE / LHdE
A4 Alarm type
AL4t
8
OFF
OFF / On
A3 Alarm behaviour in
OFF control mode
AL3o
7
- - C
- - C / - - o
- SC / - So
L - C / L - o
LSC / LSo
Configuration of A3 alarm
functioning mode
AL3c
6
LOAb
LOAb / HIAb
LHAb / LOdE
HIdE / LHdE
A2 Alarm type
AL3t
5
Hb
AL3, Hb
A3/HB output functioning
mode
FAL3
4
1
-999 ÷ 9999
Alarm A4 hysteresis
HAL4
3
1
-999 ÷ 9999
Alarm A3 hysteresis
HAL3
2
1
0 ÷ 9999
Set point hysteresis for
ON/OFF control mode
HSEt
1
Notes
Def.
Range
Description
Par.
no
no / yES
Active Set-point change
using "UP" key
SPOL
55
no
no / yES
Manual contron activation
in "SEL" menu
EnOL
54
0
-99.9 ÷100.0 %
Manual control power
when activated by
AUXIN
rEdF
53
FF
FF /Fr /rF /rr
AUXIN input function
rEAr
52
1
1 ÷ 4
Programmable Set-point
number
nSP
51
LoCL
LoCL / LorE
Programming access
through serial port
PacS
50
4800
300/600/1200/
2400/4800/
9600 baud
Baud rate serial port
baud
49
1
1 ÷ 255
Address of the station for
serial comunication
nSta
48
50H
50H / 60H Hz
Frequency optimizing the
noise
FrEq
47
1
0 ÷ 50 sec.
Input digital filter
constant
Filt
46
0
-999 ÷ 9999
Calibration
OFFt
45
0
0 / no_0
Analogue outputs range
Aout
44
0
-999 ÷ 9999
Higher limit of analogue
input scale for normalized
signals
EndS
43
0
-999 ÷ 9999
Lower limit of analogue
input scale for normalized
signals
StrS
42
0
0 ÷ 3
Number of decimal
figures
dP
41
SSLo
SSLo / SSHi
Range of analogue input
for normalized signals
ScaL
40
C
C / F / r
Unit of measurement
Unit
39
0.0
-99.9 ÷ 999.9
°C/°F/°R
Cold junction temperature
compensation
tCJC
38
no
no / YES
Cold junction external
compensation
ECJC
37
J
b / E / J / CrAl
/ n / r / S / t / L
/ u / Pt1 / Pt2 /
0_50
Input probe
SEnS
36
0.00
0.00 ÷ 99.99
unit/min.
Gradient of fall ramp
SloF
35
0.00
0.00 ÷ 99.99
unit/min.
Gradient of rise ramp
Slor
34
no
no /
OPEn / CloS
Positioning at start-up of
motorized actuactor
PoSi
33
0
0 ÷ 9999
Dead zone
dbEr
32
0
0 ÷ 10 %
Minimum control value of
motorized actuator
SHrI
31
4
4 ÷ 1000 sec.
Travel time of the
motorized actuator
tcor
30
50.0
-99.9÷100.0 %
Manual reset
rS
29
7 - PROBLEMS, MAINTENANCE AND WARRANTY
ERRORS SIGNALLING:
The 2 displays are used as well to visualise
anomaly conditions of instrument functioning :
"- - - -"
= probe interruption.
"uuuu"
= the measured variable is gone under the probe limits.
"oooo"
= the measured variable is gone under the probe limits.
"u400"
= the temperature is gone under 400°C when it's used a
thermocouple "B" type. The regulation regularly proceeds considering PV
= 0°C.
"LbA"
= interruption of the regulation ring (see loop break alarm
function).
TECNOLOGIC - THP 84
USER MANUAL (I - GB) - Vr. 02 - ISTR 00132 - PAG. 20