Model SE126KM positioning: Methane

 (CH

4

) is a combustible gas lighter than air. Its density related to air is 

0.55; its LEL (Lower Explosion Limit) is 5% v/v (Volume). 

The instrument should be fixed at 30 cm from the ceiling

 

and be placed at 1-1.5 meter from the gas appliance, far from the room corners or from ventilation intakes. 

Model SE126KG positioning:

  

LPG

 is a gas mixture composed by 20-30% Propane (C

3

H

8

) and by 70-80% Bu-

tane (C

4

H

10

). LPG calibration must be carried out with Butane which is a combustible gas heavier than air. Its den-

sity related to air is 2; its LEL (Lower Explosion Limit) is 1.5%v/v (Volume). 

The instrument should be fixed at 30 

cm. from the floor

 and be placed at 1-1.5 meter from the gas appliance, far from the room corners or from ventila-

tion intakes 

Mounting

: The Fig. 2 shows the instrument size. It should be wall-mounted by three screw anchors. The 

normally 

closed manually resetting valve

 for the gas cut-off should be installed outside the room in a clearly indicated po-

sition and should be protected from rain. 

Electrical Connection:

 the instrument is supply with non reversible and plug-in terminals. Therefore the cables 

should be anchored to the case in order to avoid terminal overstress. The connection to the central unit does not 
need any hearting. 

Fig. 3

 shows the AC powering connection with alarm siren and normally closed manual resetting valve. 

Fig. 4

 shows the AC powering connection with alarm siren and normally open manual resetting valve. 

Fig. 5 shows the AC powering connection with alarm siren and our normally closed manual resetting valve with 

positioning sensor (models VR420÷VR480,) to verify, if an alarm occurs, the really gas cut-off. 

Fig. 5

 shows the 12Vdc powering connection with both 12Vdc alarm siren and normally closed manual resetting 

valve with, for example, our power supply unit PS175 with internal 12Vcc-7Ah battery to maintain the system pow-
ered on in absence of Main power supply. 

WARNING 

The detector doesn't need adjustments after being installed. 
Average life

the sensitive element used in this detector has an excellent stability in time. In fresh air and in normal 

working condition the sensor's life is more than 5 years from the date of installation. 

Important: Catalytic sensors can operate only in presence of Oxygen. Do not use pure gases or a lighter directly 
on the sensor since they could damage it irremediably

. The detector is not able to detect gas leaks occurring out-

side the room where it is installed, neither inside walls nor under the floor. 

Attention: please note that in polluted environments, where vapours of flammable agents, especially solvents, 
might be present, the sensor's life can be reduced. Some substances cause a permanent reduction in sensitivity. 
Avoid contacts of the sensor with vapours of Silicone compounds (paintings and sealing paste), Tetra-ethyl Lead 
and Phosphate esters. Some other substances produce a temporary loss of sensitivity. These “inhibitors” include 
Hydrogen sulphide, Chlorine, Chlorinated hydrocarbons and halogenated compounds. The sensitivity is recovered 
after a short period of running in clear air. 

FUNTIONAL TESTING 

Periodical testing

we advise to carry out working tests every 6-12 months. 

PAY ATTENTION

: This procedure has to be made with extreme attention and by authorized and trained people; 

because starting this procedure it will start both Outputs (relays) causing the activation of connected alarm devices. 
The “TEST” key is deactivating when an alarm condition occurs. 

Instrument operation check

: push the "TEST" button for 3 seconds until all Led and relays deactivates.  

Then the LED will illuminate in sequence. With the LEDs the corresponding relays will activate (Yellow LED - 
FAULT relay, 2

nd

 red LED - PREAL. Relay and 3rd red LED - ALARM relay). After 5 seconds the instrument returns 

to normal working condition. NOTE: during the Test some conditions occur: 

All 5 LEDs illuminates

ONLY

 when the central unit is connected with a control wire for certain types of valves. In 

this case the test results correct 

Yellow LED off (after red LEDs)

: indicates the lack of control wire of the valve or that the valve is closed. If this 

wire is disconnected from the central unit the test results correct, if not please check the valve and repeat test. If 
test result is unchanged, electrical problems are in place, please contact the supplier.  

The 3rd Red LED offONLY when the central unit is connected with a control wire for certain types of valves. The 
control wire is disconnected or the valve is open. In this case please check both the valve status and the wire con-
nection and repeat the test. If wire is disconnected, check the bridge on the terminal “AUX” that has to be con-
nected and repeat the test. 
All other cases: 

If some leds do not light on or some relays do not switch, the central unit is damaged. In this case 

please replace it or send it back to the supplier. 

Calibration testing with gas mixture

the calibration is carried out with specific gas in our laboratory. We advise 

to check the calibration only 

using sample gas bottles with a mixture abut 25%LEL Gas in Air (20.9% Oxygen) 

(Gas Methane for SE126KM and Butane for SE126KG). Catalytic sensors cannot work without Oxygen

Note

: The calibration routine is to be carried out by trained or authorised personnel only. In case the values are not 

the required ones please apply to our Laboratory. 
The calibration testing should be done with Calibration Kit model TC011 (See specific user’s manual). Connect the 
sample gas bottle to the flow meter, open Gas (0,3 l/min flow rate), wait for 3 minutes and check that the instru-
ment activate Alarms as shown in chapter “OPERATIONAL DESCRIPTION”. 

 

Содержание SE126K

Страница 1: ...ears ans Intervento allarme 1st Alarm intervention Seuil d intervention de alarme 10 LIE LEL Intervento blocco 2nd Alarm intervention Seuil d intervention de blocage 20 LIE LEL Contatti relè Contacts rating Contact relais 230Vac 3A SPDT Tempo di risposta T90 Response Time T90 Temps de réponse T90 30 secondi seconds secondes Temperatura Umidità di funzionamento Operation Temp Humidity Temp et humid...

Страница 2: ...nel caso in cui essa sia scattata si spegnerà il Led giallo e si disattiverà il relé FAULT vedi sezione Guasti più avanti Ripristino dopo un Allarme la centralina tornerà al funzionamento normale solo se la concentrazione di gas è inferiore al 10 del LIE il relè ALARM sarà disattivato il 3 e 4 Led rosso si spegneranno Se attivato sarà di sattivato il relé FAULT e si spegnerà il Led giallo vedi sez...

Страница 3: ...o una temporanea perdita di sensibilità Questi inibi tori sono gli Alogeni l Idrogeno solforato il Cloro gli Idrocarburi clorurati Trielina o Tetracloruro di carbonio Do po un breve tempo in aria pulita il sensore riprende il proprio funzionamento normale VERIFICA FUNZIONAMENTO Verifiche Periodiche Si consiglia di eseguire la verifica di funzionamento ogni 6 12 mesi in base all utilizzo IMPORTANTE...

Страница 4: ...ains latched LEDs and relays remain activated even if the gas concentra tion is reduced because the mounted valve is closed To reset the normal working conditions and or switch off the siren push the RESET button Buzzer the PREAL relay will be deactivated and the Red Led flashes only if the gas concentration is higher than 10 of LIE After 20 seconds both of them will return in preallarm the siren ...

Страница 5: ... the sensor s life can be reduced Some substances cause a permanent reduction in sensitivity Avoid contacts of the sensor with vapours of Silicone compounds paintings and sealing paste Tetra ethyl Lead and Phosphate esters Some other substances produce a temporary loss of sensitivity These inhibitors include Hydrogen sulphide Chlorine Chlorinated hydrocarbons and halogenated compounds The sensitiv...

Страница 6: ...e gaz est supérieure 10 de la LIE la relais PREAL serait désactivée et le deuxième Led rouge clignote Apres 20 seconds les deux revient in prealarme la sirène sonne Si la vanne NF à réarmement manuel avec senseur de fin de course a été utilisée et dans ce cas elle est activée la led jaune s étende et le relais Dérangement se désactive voir section relais Dérangement Réarmement après une d alarme L...

Страница 7: ...é Le contact occasionnel avec des sol vants type trichloréthylène ou tétrachlorure de carbone peuvent inhiber temporairement le capteur Après un bref temps en air pur le capteur reprend son fonctionnement normal VERIFICATIONS PERIODIQUES Vérification périodique il est conseillé d effectuer une vérification de fonctionnement tous les 6 12 mois ATTENTION cette procédure doit être exécutée avec une e...

Страница 8: ...ec vanne à réarmement manuel norm fermée 230Vca NC C NA NC C NA NC C NA L N SE301A PREAL ALARM Valvola NC FAULT AUX Fig 4 Collegamento con valvola a riarmo manuale Norm Aperta Wiring diagram with a normally open manual resetting valve Schéma avec vanne à réarmement manuel norm ouverte 230Vca NC C NA NC C NA NC C NA L N SE301A PREAL ALARM Valvola NA FAULT AUX Fig 5 Collegamento con valvola a riarmo...

Отзывы: